TESLA TT38TF-1232IAW Split Type Air Conditioner User Manual
- July 29, 2024
- Tesla
Table of Contents
TESLA TT38TF-1232IAW Split Type Air Conditioner
Specifications
- Model: TT38TF-1232IAW
- Type: Split-Type Air Conditioner
- Inverter: R32 DC Inverter
Product Usage Instructions
Safety Precautions:
Before operating the air conditioner, ensure to read and follow all safety rules and recommendations provided in the user manual.
Accessories:
The package includes various accessories for both the indoor and outdoor units, such as remote controller, batteries, screws, user manual, filters, and more. Make sure all accessories are present before installation.
Names of Parts:
The indoor unit consists of parts like air outlet, air filter, front panel, while the outdoor unit includes features like air inlet, refrigerant pipe, and more. Refer to the user manual for detailed part names and locations.
Indoor Display:
The indoor display shows various indicators related to timer, temperature, error codes, fresh air function, Wi-Fi connectivity, and operation status. Familiarize yourself with the LED functions for efficient use.
Remote Controller:
The remote controller provides various functions like mode selection (Auto, Cool, Dry, Fan, Heat), timer settings, fan speed adjustment, sleep function, and more. Check the user manual for detailed button functions.
FAQs
- Q: What should I do if the air conditioner displays an error code?
- A: Refer to the user manual for error code meanings and troubleshooting steps. If the issue persists, contact customer support for assistance.
- Q: How often should I clean the air filters?
- A: Regularly clean the air filters every 2-4 weeks to maintain optimal performance and air quality. Follow the cleaning instructions provided in the user manual.
OPERATING INSTRUCTION
Note: All the pictures in this manual are just schematic diagrams, the actual
is the standard. Please read this owner’s manual carefully and thoroughly
before operating the unit! Take care of this manual for future reference.
BG
: , . , !
GR HR
: , . ! .
UPUTE ZA UPOTREBU
Napomena: Sve slike u ovom prirucniku su samo shematski dijagrami, fizicki
proizvod je standard. Molimo Vas da pazljivo i temeljito procitate ovo
uputstvo za upotrebu prije koristenja ureaja! Cuvajte ovaj prirucnik za buduce
koristenje.
HU
FELHASZNÁLÓI KÉZIKÖNYV
Megjegyzés: A kézikönyvben található képek csak sematikus ábrák, az aktuális a
szabvány. Kérjük, figyelmesen olvassa el ezt a kézikönyvet mieltt mködtetné az
eszközt! rizze meg ezt a kézikönyvet a késbbiekre is.
MKD RO SRB
: , . ! .
MANUAL DE UTILIZARE
Nota: Fotografiile din acest manual sunt doar diagrame schematice. V rugm s
citii “Manualul de Utilizare” cu atenie, înainte de a utiliza aerul
condiionat, pentru a asigura funcionarea corespunztoare. Pstrai manualul
pentru referine ulterioare.
UPUTSTVO ZA UPOTREBU
Napomena: Sve slike u ovom prirucniku su samo sematski dijagrami, fizicki
proizvod je standard. Molimo Vas da pazljivo i temeljno procitate ovo uputstvo
za upotrebu pre koriscenja ureaja! Sacuvajte ovo uputstvo za buducu upotrebu.
ENG
SAFETY PRECAUTIONS
SAFETY RULES AND RECOMMENDATIONS FOR THE INSTALLER
· Read this guide before installing and using the appliance. · During the
installation of the indoor and outdoor units the access to the working area
should be forbidden to
children. Unforeseeable accidents could happen. · Make sure that the base of
the outdoor unit is firmly fixed. · Check that air cannot enter the
refrigerant system and check for refrigerant leaks when moving the air
conditioner. · Carry out a test cycle after installing the air conditioner and
record the operating data. · Protect the indoor unit with a fuse of suitable
capacity for the maximum input current or with another overload
protection device. · Ensure that the mains voltage corresponds to that stamped
on the rating plate. Keep the switch or power plug
clean. Insert the power plug correctly and firmly into the socket, thereby
avoiding the risk of electric shock or fire due to insufficient contact. ·
Check that the socket is suitable for the plug , otherwise have the socket
changed. · The appliance must be fitted with means for disconnection from the
supply mains having a contact separation in all poles that provide full
disconnection under overvoltage category III conditions, and these means must
be incorporated in the fixed wiring in accordance with the wiring rules. · The
air conditioner must be installed by professional or qualified persons. · Do
not install the appliance at a distance of less than 50 cm from inflammable
substances (alcohol, etc.) or from pressurised containers (e.g. spray cans). ·
If the appliance is used in areas without the possibility of ventilation,
precautions must be taken to prevent any leaks of refrigerant gas from
remaining in the environment and creating a danger of fire · The packaging
materials are recyclable and should be disposed of in the separate waste bins
.Take the air conditioner at the end of its useful life to a special waste
collection centre for disposal. · Only use the air conditioner as instructed
in this booklet. These instructions are not intended to cover every possible
condition and situation . As with any electrical household appliance , common
sense and caution are therefore always recommended for installation, operation
and maintenance. · The appliance must be installed in accordance with
applicable national regulations. · Before accessing the terminals , all the
power circuits must be disconnected from the power supply. · The appliance
shall be installed in accordance with national wiring regulations. · This
appliance can be used by children aaged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance
shall not be made by children without supervision. · Do not try to install the
conditioner alone; always contact specialized technical personnel. · Cleaning
and maintenance must be carried out by specialized technical personnel. In any
case disconnect the appliance from the mains electricity supply before
carrying out any cleaning or maintenance. · Ensure that the mains voltage
corresponds to that stamped on the rating plate. Keep the switch or power plug
clean. Insert the power plug correctly and firmly into the socket , thereby
avoiding the risk of electric shock or fire due to insufficient contact. · Do
not pull out the plug to switch off the appliance when it is in operation,
since this could create a spark and cause a fire, etc. · This appliance has
been made for air conditioning domestic environments and must not be used for
any other purpose , such as for drying clothes, cooling food, etc. · Always
use the appliance with the air filter mounted . The use of the conditioner
without air filter could cause an excessive accumulation of dust or waste on
the inner parts of the device with possible subsequent failures. · The user is
responsible for having the appliance installed by a qualified technician , who
must check that it is earthed in accordance with current legislation and
insert a thermomagnetic circuit breaker. · The batteries in remote controller
must be recycled or disposed of properly. Disposal of Scrap Batteries –Please
discard the batteries as sorted municipal waste at the accessible collection
point. · Never remain directly exposed to the flow of cold air for a long
time. The direct and prolonged exposition
3
ENG
to cold air could be dangerous for your health .Particular care should be
taken in the rooms where there are children , old or sick people. · If the
appliance gives off smoke or there is a smell of burning, immediately cut off
the pow er supply and contact the Service Centre. · The prolonged use of the
device in such conditions could cause fire or electrocution. · Have repairs
carried out only by an authorised Service Centre of the manufacturer .
Incorrect repair could expose the user to the risk of electric shock, etc. ·
Unhook the automatic switch if you foresee not to use the device for a long
time. The airflow direction must be properly adjusted. · Only use the air
conditioner as instructed in this booklet. These instructions are not intended
to cover every possible condition and situation. As with any electrical
household appliance, common sense and caution are therefore always recommended
for installation , operation and maintenance. · Ensure that the appliance is
disconnected from the power supply when it will remain inoperative for a long
period and before carrying out any cleaning or maintenance. · Selecting the
most suitable temperature can prevent damage to the appliance.
SAFETY RULES AND PROHIBITIONS
· Do not bend, tug or compress the power cord since this could damage it.
Electrical shocks or fire are probably due to a damaged power cord.
Specialized technical personnel only must replace a damaged power cord.
· Do not use extensions or gang modules. · Do not touch the appliance when
barefoot or parts of the body are wet or damp. · Do not obstruct the air inlet
or outlet of the indoor or the outdoor unit. The obstruction of these openings
causes a reduction in the operative efficiency of the conditioner with
possible consequent failures or damages. · In no way alter the characteristics
of the appliance. · Do not install the appliance in environments where the air
could contain gas , oil or sulphur or near sources of
heat. · This appliance is not intended for use by persons (including children
) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given
supervision or instruction concerning use of the appliance by a person
responsible for their safety. · Do not climb onto or place any heavy or hot
objects on top of the appliance. · Do not leave windows or doors open for long
when the air conditioner is operating. · Do not direct the airflow onto plants
or animals. · A long direct exposition to the flow of cold air of the
conditioner could have negative effects on plants and animals. · Do not put
the conditioner in contact with water. The electrical insulation could be
damaged and thus causing electrocution. · Do not climb onto or place any
objects on the outdoor unit · Never insert a stick or similar object into the
appliance. It could cause injury. · Children should be supervised to ensure
that they do not play with the appliance. If the supply cord is damaged, it
must be replaced by the manufacturer,its service agent or similarly qualified
persons in order to avoid a hazard.
4
ENG
ACCESSORIES
Indoor Unit
Remote controller
x 2 AAA battery
x 6
Screw
User manual
Fresh air filter
Wall sleeve cover
Insulating tape
x 2 Metal strap supporter
x 2 Fresh air
pipe
Straight Connecter
Protection Cover
x 6 Plastic anchors
x 4 Refrigerant pipe nuts
Outdoor Unit
x 2 Drainage hose
Insulating tape
Sealant
TDS sheet and Energy label
Drainage joint
Insulation pipe
5
ENG
NAMES OF PARTS
Indoor unit
Air outlet
Air deflector and flap
Air filter Mounting plate
Front panel
Outdoor unit
Air outlet
Note: This figure shown may be different from the actual object. Please take the latter as the standard.
With the protective cover removed
6
Refrigerant connecting pipe
Air inlet
Drainage pipe Connection wiring Valve protective cover
Gas valve (Low pressure valve) Liquid valve (High pressure valve)
ENG
Indoor Display
No. LED Function
1
Indicator for Timer, temperature and Error codes.
2
Lights up when Fresh Air function is on.
3
Lights up when Wi-Fi is on.
4
Operation indicator/Air quality status indicator (if TVOC function is available).
Note: The air conditioner automatically adjusts the display brightness and
buzzer sound according to the ambient light intensity. When the air
conditioner detects that the ambient light is weak for a period of time, it
will automatically turns off the display temporarily. If there is a remote
control or APP operation, the display will display at a low brightness for a
short time, and the buzzer will respond at a lower volume; When the air
conditioner detects that the ambient light is strong for a period of time,
exit the above operation.
The shape and position of switches and indicators may be different according
to the model, but their function is the same.
7
ENG
REMOTE CONTROLLER
Remote control DISPLAY
No.
Button
Function
1
Battery indicator
2
Auto Mode
3
Cooling Mode
4
Dry Mode
5
Fan only Mode
6
Heating Mode
7
ECO Mode
8
Timer
9
Temperature indicator
10
Fan speed: Auto/ low/ low-mid/ mid/ mid-high/ high
11
Mute function
12
TURBO function
13
Up-down auto swing
14
Left-right auto swing
15
SLEEP function
16
Health function
17
I FEEL function
18
8 C heating function
19
Signal indicator
20
Gentle wind
21
Child-Lock
22
Display ON/OFF
23
GEN function
24
Self-Clean function
25
Anti-mildew function
26
Fresh air
8
The display and some functions of the remote control may vary according to the model.
ENG
No.
Button
Function
1
To turn on/off the air conditioner .
2
To decrease temperature, or Timer setting hours.
3
To increase temperature, or Timer setting hours.
4
MODE
To select the mode of operation (AUTO, COOL, DRY, FAN, HEAT).
To activate/deactivate the ECO function.
5
ECO
Long press to activate/deactivate the 8C heating function (depending on models).
6
TURBO
To activate/deactivate the TURBO function.
7
FAN
To select the fan speed of auto/mute/low/low-mid/mid/mid-high/high/turbo.
8
TIMER
To set the time for timer on/off.
9
SLEEP
To switch-on/off the function SLEEP.
10
DISPLAY
To switch-on/off the LED display.
11
To stop or start horizontal louver movement or set the desired up/down air flow direction.
12
To stop or start horizontal louver movement or set the desired left/rightair flow direction.
13
I FEEL
To switch-on/off the I FEEL function.
To switch-on/off the MUTE function.
14
MUTE
Long press to activate/deactivate the GEN function (depending on models).
15
MODE + TIMER
To activate/deactivate the CHILD-LOCK function.
16
GENTLE WIND
To activate/deactivate the GENTLE WIND function (depending on models).
To activate/deactivate the HEALTH function (depending on models).
17
HEALTH
To activate/deactivate the SELF-CLEAN function when switch OFF.
18 FRESH AIR To activate/deactivate the Fresh Air function and select the fan speed.
The display and some functions of the remote control may vary according to the model.
The shape and position of buttons and indicators may vary according to the
model, but their function is the same.
The unit confirms the correct reception of each button with the beep.
9
ENG
Replacement of Batteries
Remove the battery cover plate from the rear of the remote control, by
pressing and sliding it in direction as the arrow. Install the batteries by
putting ( -) at the side with spring on the remote controller. Reinstall the
battery cover by sliding it into place.
Use 2 pieces LRO3 AAA (1.5V) batteries. Do not use rechargeable batteries.
Replace the old batteries with new ones of the same type when the display is
no longer legible. Do not dispose batteries as unsorted municipal waste.
Collection of such waste separately for special treatment is necessary.
Each time when insert the batteries in the remote controller for the first time, you can set the Cooling only or
Heating pump control type. As soon as you insert the batteries, turn off the remote controller, and operate as
below.
1. Long press the
button, until the ( ) icon flash, to set the Cooling only type.
2. Long press the
button, until the ( ) icon flash, to set the Heating pump type.
Note: If you set the remote control in cooling mode, it will not be possible to activate the heating function in
units with a heating pump. If you need to reset, take out the batteries and install again.
You can program the temperature display between C and F.
1. Press and hold the
button over 5 seconds to get into the change mode;
2. Press and hold the
button, until it switch to C and F;
3. Then release the pressing and wait for 5 seconds, the function will be selected.
Note: 1. Direct the remote control toward the Air conditioner. 2. Check that there are no objects between the remote control and the Signal receptor in the indoor unit. 3. Never leave the remote control exposed to the rays of the sun. 4. Keep the remote control at a distance of at least 1m from the television or other electrical appliances.
MODES
Cooling mode
DRY MODE
The cooling function allows the air conditioner to cool the room and reduce
Air humidity at the same time.
To activate the cooling function (COOL), press the button until the symbol
appears on the
display. With the button or set a temperature lower than that of the room.
FAN MODE (Not FAN button)
This function reduces the humidity of the air to make the room more comfortable.
To set the DRY mode, Press
until appears
in the display. An automatic function of pre-setting is
activated.
AUTO MODE
Automatic mode.
Fan mode, air ventilation only.
To set the FAN mode, press
until
on the display.
appears
To set the AUTO mode, press
until
appears on the display. In AUTO mode the run mode
will be set automatically according to the room
temperature.
10
ENG
HEATING MODE
The heating function allows the air conditioner to heat the room.
To activate the heating function (HEAT), press the button until the symbol
appears on the
display. With the button or set a temperature higher than that of the room.
In HEATING operation, the appliance can automatically activate a defrost
cycle, which is essential to clean the frost on the condenser so as to recover
its heat exchange function. This procedure usually lasts for 2-10 minutes.
During defrosting, indoor unit fan stop operation. After defrosting, it
resumes to HEATING mode automatically.
(For North American market) If necessary, you can press ECO button 10 times
within 8 seconds under heating mode to start the forced defrosting. It will
defrost the outdoor ice much more fast.
decreases by half an hour between 0 and 10 hours
and by one between 10 and 24 hours.
3. Press
button second time to confirm.
4. After Timer-on setting, set the needed mode (Cool/
Heat/ Auto/ Fan/ Dry), by press the
button.
And set the needed fan speed, by press
button. And press or to set the needed operation
temperature.
CANCEL it by press
button.
TIMER function —- TIMER OFF
To automatic switch off the appliance.
When the unit is switch-on, you can set the TIMER OFF.
To set the time of automatic switch-off, as below:
1. Confirm the appliance is ON.
2. Press the
button at first time to set the
switch-off.
Press or to set the needed timer.
3. Press
button at the second time to confirm.
FAN SPEED function (FAN button)
Change the operating fan speed.
Press
button to set the running fan speed, it can
be set to AUTO/ MUTE/ LOW/ LOW-MID / MID/ MID-
HIGH/ HIGH/ TURBO speed circularly.
Child-Lock function
1. Long press
and
button together
to active this function, and do it again to deactivate
this function.
2. Under this function, no single button will active.
TIMER function —- TIMER ON
CANCEL it by press
button.
Note: All programming should be operated within 5 seconds, otherwise the setting will be cancelled.
SWING function
1. Press the button SWING to activate the louver, 1.1 Press to activate the
horizontal flaps to swing from up to down, the will appear on the remote
display. 1.2 Press to active the vertical deflectors to swing from left to
right, the will appear on the remote display. 1.3 Do it again to stop the
swing movement at the current angle.
2. If the vertical deflectors are positioned manually which placed under the
flaps, they allow to move the air flow direct to rightward or leftward.
3.Long press or over 3 seconds to select more angles of the airflow direction.
To automatic switch on the appliance.
When the unit is switch-off, you can set the TIMER ON.
To set the time of automatic switch-on as below:
1. Press
button first time to set the switch-on,
and
will appear on the remote display and
flashes.
2. Press or to button to set desired Timer-on time.
Each time you press the button, the time increases/
11
ENG
Never position Flaps manually, the delicate mechanism might seriously damaged!
Never put fingers, sticks or other objects into the air inlet or outlet vents.
Such accidental contact with live parts might cause unforeseeable damage or
injury.
TURBO function
ECO function
In this mode the appliance automatically sets the operation to save energy.
Press the
button, the appears on the display,
and the appliance will run in ECO mode.
Press again to cancel it.
Note: The ECO function is available in both COOLING
and HEATING modes.
To activate turbo function, press the
button,
and will appear on the display. Press again to
cancel this function. In COOL/ HEAT mode, when you
select TURBO feature, the appliance will turn to quick
COOL or quick HEAT mode, and operate the highest
fan speed to blow strong airflow.
MUTE function
DISPLAY function (Indoor display)
Switch ON/OFF the LED display on panel.
Press
button to switch off the LED
display on the panel. Press again to switch on the
LED display.
GEN function (Optional)
1. Press
button to active this function, and
will appears on the remote display. Do it again to
deactivate this function.
2. When the MUTE function runs, the remote controller
will display the auto fan speed, and the indoor unit
will operate at lowest fan speed to be quiet feeling.
3. When press FAN/ TURBO button, the MUTE function
will be cancel. MUTE function can not be activated
under dry mode.
SLEEP function
Pre-setting automatic operating program.
Press
button to activate the SLEEP function,
and appears on the display.
Press again to cancel this function.
After 10 hours running in sleep mode, the air
conditioner will change to the previous setting mode.
I FEEL function (Optional)
Press
button to active the function, the will
appear on the remote display. Do it again to deactivate
this function.
This function enables the remote control to measure the
temperature at its current location, and send this signal
to the air conditioner to optimize the temperature
around you and ensure the comfort.
It will automatically deactivate 2 hours later.
1. Turn on the indoor unit at first, and long press
button 3 seconds to activate.
2. Under this function, short press
button to
select the General type L3 – L2 – L1 – OF.
3. Select OF and wait 2 seconds to exit it.
Reset Wi-Fi
1. Method 1: Press button DISPLAY 6 times in 8 seconds.
2. Method 2: Press button ECO 6 times in 8 seconds. 3. Method 3: Long press
MODE and over 3 seconds.
You will hear 2 beeps and CF or AP will show on the indoor display after the
operation.
SELF-CLEAN function (Optional)
Only optional for some heating pump inverter
appliance.
To active this function, turn off the indoor unit at first,
then press
button then you will hear a beep,
will appear on the indoor LED, and will
appear on the remote display .
1. This function helps carry away the accumulated dirt,
bacteria, etc from the indoor evaporator.
2. This function will run about 30 minutes, and it will
return to the pre-setting mode. You can press
12
ENG
button to cancel this function during the process.
Health function (Optional)
You will hear 2 beeps when it’s finished or cancelled.
It’s normal if there is some noise during this function process, as plastic
materials expand with heat and contract with cold.
We suggest operating this function at the following ambient conditions to
avoid certain safety protection features.
Indoor unit Temp < 86°F (30°C) Outdoor unit 41°F (5°C) < Temp < 86°F (30°C)
It’s suggested to utilize this function every 3 months.
8C heating function (Optional)
1. Long press
button over 3 seconds to active
this function, and
will appear on the
remote display. Do it again to deactivate this function.
2. This function will auto start the heating mode when
the room temperature is lower than 8C (46F), and it
will return to standby if the temperature reaches 9C
(48F).
3. If the room temperature is higher than 18C (64F),
the appliance will cancel this function automatically.
Gentle Wind function (Optional)
1. Turn on the indoor unit, and change to COOL mode,
then press
button or to active this
function, will appear on the display. Do it again to
deactivate it.
2. This function will auto close the vertical flaps, and give
you the comfortable gentle wind feeling.
1. Turn on the indoor unit at first, press
to
active this function, will appear on the display.
Do it again to deactivate it.
2. When the HEALTH function is initiated, the Ionizer/
Plasma/ Bipolar Ionizer/ UVC Lights (depending on
models) will be energized and running.
Fresh Air function
This function will pump the fresh air FRESH AIR from outside to inside.
Continue press
button until select your desired
Fresh Air fan speed or deactivate this functionas
circulation Low-Mid-High-OFF, then loose button.
The following indicator will appear on the display:
Auto fan speed High fan speed
(Flash)
Low fan speed Mid fan speed
OFF (no indicator)
Note:
1. This function is available when in OFF/Heating
Cooling/Fan/Auto mode.
2. In OFF mode, the system may run automatically
because of the big difference of temperature
between indoor and outside.
3. If the indoor display shows the Fresh Air indicator and
shows CL. You can replace the filter and long press
button
over 5 seconds to clear the indicator
CL.
13
ENG
OPERATION INSTRUCTIONS
Attempt to use the air conditioner under the temperature beyond the specified range may cause the air conditioner protection device to start and the air conditioner may fail to operate. Therefore, try to use the air conditioner in the following temperature conditions.
Inverter air conditioner: Temperature
Room temperature Outdoor temperature
Heating 0°C~27°C (32°F~80°F)
-20°C~24°C (-4°F~75°F)
Mode
Cooling
Dry
17°C~32°C (63°F~90°F)
15°C~50°C (59°F~122°F) (Low temperature cooling: -15°C~50°C (5°F~122°F))
With the power supply connected, restart the air conditioner after shutdown, or switch it to other mode during operation, and the air conditioner protection device will start. The compressor will resume operation after 3 minutes.
Characteristics of heating operation (applicable to Heating pump) Preheating:
When the heating function is enabled, the indoor unit will take 2~5 minutes
for preheating, after that the air conditioner will start heating and blows
warm air. Defrosting: During heating, when the outdoor unit frosted, the air
conditioner will enable the automatic defrosting function to improve the
heating effect. During defrosting, the indoor and outdoor fans stop running.
The air conditioner will resume heating automatically after defrosting finish.
Emergency button: Open the panel and find the emergency button on the
electronic control box when the remote controller fails . (Always press the
emergency button with insulation material.)
Current status Standby
Standby (Only for heating pump)
Running
Operation Press the emergency button once Press the emergency button twice in
3 seconds
Press the emergency button once
Respond It beeps briefly once.
It beeps briefly twice.
It keeps beeping for a while
Enter mode Cooling mode Heating mode
Off mode
control-box cover
ON/OFF (open the panel of indoor unit)
14
ENG
INSTRUCTION FOR SERVICING
1. Check the information in this manual to find out the dimensions of space
needed for proper installation of the device, including the minimum distances
allowed compared to adjacent structures.
2. Appliance shall be installed, operated and stored in a room with a floor
area larger than 4m2. 3. The installation of pipe-work shall be kept to a
minimum. 4. The pipe-work shall be protected from physical damage, and shall
not be installed in an unventilated space if
the space is smaller than 4m2 . 5. The compliance with national gas
regulations shall be observed. 6. The mechanical connections shall be
accessible for maintenance purposes. 7. Follow the instructions given in this
manual for handling, installing, cleaning, maintaining and disposing of the
refrigerant. 8. Make sure ventilation openings clear of obstruction. 9.
Notice:The servicing shall be performed only as recommended by the
manufacturer. 10. Warning: The appliance shall be stored in a well-ventilated
area where the room size corresponds to the room
area as specified for operation. 11. Warning:The appliance shall be stored in
a room without continuously operating open flames (for example
an operating gas appliance) and ignition sources (for example an operating
electric heater). 12. The appliance shall be stored so as to prevent
mechanical damage from occurring. 13. It is appropriate that anyone who is
called upon to work on a refrigerant circuit should hold a valid and up-to-
date certificate from an assessment authority accredited by the industry and
recognizing their competence to handle refrigerants, in accordance with the
assessment specification recognized in the industrial sector concerned.
Service operations should only be carried out in accordance with the
recommendations of the equipment manufacturer. Maintenance and repair
operations that require the assistance of other qualified persons must be
conducted under the supervision of the person competent for the use of
flammable refrigerants. 14. Every working procedure that affects safety means
shall only be carried out by competent persons. 15. Warning: · Do not use
means to accelerate the defrosting process or to clean, other than those
recommended by the
manufacturer. · The appliance shall be stored in a room without continuously
operating ignition sources (for example: open
flames, an operating gas appliance or an operating electric heater. · Do not
pierce or burn. · Be aware that refrigerants may not contain an odour.
Caution: Risk of fire
Operating instructions
Read technical manual
16. Information on servicing: 1. Checks to the area Prior to beginning work
on systems containing flammable refrigerants, safety checks are necessary to
ensure that the risk of ignition is minimized. For repair to the refrigerating
system, the following precautions shall be complied with prior to conducting
work on the system. 2. Work procedure Work shall be undertaken under a
controlled procedure so as to minimize the risk of a flammable gas or vapour
being present while the work is being performed. 3. General work area All
maintenance staff and others working in the local area shall be instructed on
the nature of work being carried out. Work in confined spaces shall be
avoided. The area around the workspace shall be sectioned off. Ensure that the
conditions within the area have been made safe by control of flammable
material. 4. Checking for presence of refrigerant The area shall be checked
with an appropriate refrigerant detector prior to and during work, to ensure
the technician is aware of potentially flammable atmospheres. Ensure that the
leak detection equipment being used is suitable for use with flammable
refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe 5.
Presence of fire extinguisher If any hot work is to be conducted on the
refrigeration equipment or any associated parts, appropriate fire
15
ENG
extinguishing equipment shall be available to hand. Have a dry powder or CO2
fire extinguisher adjacent to the charging area. 6. No ignition sources No
person carrying out work in relation to a refrigeration system which involves
exposing any pipe work shall use any sources of ignition in such a manner that
it may lead to the risk of fire or explosion. All possible ignition sources,
including cigarette smoking, should be kept sufficiently far away from the
site of installation, repairing, removing and disposal, during which
refrigerant can possibly be released to the surrounding space. Prior to work
taking place, the area around the equipment is to be surveyed to make sure
that there are no flammable hazards or ignition risks. “No Smoking” signs
shall be displayed. 7. Ventilated area Ensure that the area is in the open or
that it is adequately ventilated before breaking into the system or conducting
any hot work. A degree of ventilation shall continue during the period that
the work is carried out. The ventilation should safely disperse any released
refrigerant and preferably expel it externally into the atmosphere. 8. Checks
to the refrigeration equipment Where electrical components are being changed,
they shall be fit for the purpose and to the correct specification. At all
times the manufacturer’s maintenance and service guidelines shall be followed.
If in doubt consult the manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable
refrigerants: – The charge size is in accordance with the room size within
which the refrigerant containing parts are installed; – The ventilation
machinery and outlets are operating adequately and are not obstructed; – If an
indirect refrigerating circuit is being used, the secondary circuit shall be
checked for the presence of refrigerant; – Marking to the equipment continues
to be visible and legible. Markings and signs that are illegible shall be
corrected; – Refrigeration pipe or components are installed in a position
where they are unlikely to be exposed to any substance which may corrode
refrigerant containing components, unless the components are constructed of
materials which are inherently resistant to being corroded or are suitably
protected against being so corroded. 9. Checks to electrical devices Repair
and maintenance to electrical components shall include initial safety checks
and component inspection procedures. If a fault exists that could compromise
safety, then no electrical supply shall be connected to the circuit until it
is satisfactorily dealt with. If the fault cannot be corrected immediately but
it is necessary to continue operation, an adequate temporary solution shall be
used. This shall be reported to the owner of the equipment so all parties are
advised.
Initial safety checks shall include: -That capacitors are discharged: this
shall be done in a safe manner to avoid possibility of sparking; -That there
no live electrical components and wiring are exposed while charging,
recovering or purging the system; -That there is continuity of earth bonding.
17. Repairs to sealed components 1. During repairs to sealed components, all
electrical supplies shall be disconnected from the equipment being worked upon
prior to any removal of sealed covers, etc. If it is absolutely necessary to
have an electrical supply to equipment during servicing, then a permanently
operating form of leak detection shall be located at the most critical point
to warn of a potentially hazardous situation. 2. Particular attention shall be
paid to the following to ensure that by working on electrical components, the
casing is not altered in such a way that the level of protection is affected.
This shall include damage to cables, excessive number of connections,
terminals not made to original specification, damage to seals, incorrect
fitting of glands, etc. Ensure that apparatus is mounted securely. Ensure that
seals or sealing materials have not degraded such that they no longer serve
the purpose of preventing the ingress of flammable atmospheres. Replacement
parts shall be in accordance with the manufacturer’s specifications. NOTE: The
use of silicon sealant may inhibit the effectiveness of some types of leak
detection equipment. Intrinsically safe components do not have to be isolated
prior to working on them.
18. Repair to intrinsically safe components Do not apply any permanent
inductive or capacitance loads to the circuit without ensuring that this will
not exceed the permissible voltage and current permitted for the equipment in
use. Intrinsically safe components are the only types that can be worked on
while live in the presence of a flammable atmosphere. The test apparatus shall
be at the correct rating.
16
ENG
Replace components only with parts specified by the manufacturer. Other parts
may result in the ignition of refrigerant in the atmosphere from a leak.
19. Cabling Check that cabling will not be subject to wear, corrosion,
excessive pressure, vibration, sharp edges or any other adverse environmental
effects. The check shall also take into account the effects of aging or
continual vibration from sources such as compressors or fans.
20. Detection of flammable refrigerants Under no circumstances shall
potential sources of ignition be used in the searching for or detection of
refrigerant leaks. Ahalide torch (or any other detector using a naked flame)
shall not be used.
21. Leak detection methods The following leak detection methods are deemed
acceptable for systems containing flammable refrigerants. Electronic leak
detectors shall be used to detect flammable refrigerants, but the sensitivity
may not be adequate, or may need re-calibration. (Detection equipment shall be
calibrated in a refrigerant-free area.) Ensure that the detector is not a
potential source of ignition and is suitable for the refrigerant used. Leak
detection equipment shall be set at a percentage of the LFL of the refrigerant
and shall be calibrated to the refrigerant employed and the appropriate
percentage of gas (25 % maximum) is confirmed. Leak detection fluids are
suitable for use with most refrigerants but the use of detergents containing
chlorine shall be avoided as the chlorine may react with the refrigerant and
corrode the copper pipe-work. If a leak is suspected, all naked flames shall
be removed/ extinguished. If a leakage of refrigerant is found which requires
brazing, all of the refrigerant shall be recovered from the system, or
isolated (by means of shut off valves) in a part of the system remote from the
leak. Oxygen free nitrogen (OFN) shall then be purged through the system both
before and during the brazing process.
22. Removal and evacuation When breaking into the refrigerant circuit to make
repairs or for any other purpose conventional procedures shall be used.
However, it is important that best practice is followed since flammability is
a consideration. The following procedure shall be adhered to: – Remove
refrigerant; – Purge the circuit with inert gas; – Evacuate; – Purge again
with inert gas; -Open the circuit by cutting or brazing. The refrigerant
charge shall be recovered into the correct recovery cylinders. The system
shall be flushed with OFN to render the unit safe. This process may need to be
repeated several times. Compressed air or oxygen shall not be used for this
task. Flushing shall be achieved by breaking the vacuum in the system with OFN
and continuing to fill until the working pressure is achieved, then venting to
atmosphere, and finally pulling down to a vacuum. This process shall be
repeated until no refrigerant is within the system. When the final OFN charge
is used, the system shall be vented down to atmospheric pressure to enable
work to take place. This operation is absolutely vital if brazing operations
on the pipe-work are to take place. Ensure that the outlet for the vacuum pump
is not close to any ignition sources and there is ventilation available.
23. Decommissioning Before carrying out this procedure, it is essential that
the technician is completely familiar with the equipment and all its detail.
It is recommended good practice that all refrigerants are recovered safely.
Prior to the task being carried out, an oil and refrigerant sample shall be
taken in case analysis is required prior to re-use of reclaimed refrigerant.
It is essential that electrical power is available before the task is
commenced. a. Become familiar with the equipment and its operation. b. Isolate
system electrically. c. Before attempting the procedure, ensure that: –
mechanical handling equipment is available, if required, for handling
refrigerant cylinders; – all personal protective equipment is available and
being used correctly; – the recovery process is supervised at all times by a
competent person; – recovery equipment and cylinders conform to the
appropriate standards. d. Pump down refrigerant system, if possible. e. If a
vacuum is not possible, make a manifold so that refrigerant can be removed
from various parts of the system. f. Make sure that cylinder is situated on
the scales before recovery takes place. g. Start the recovery machine and
operate in accordance with manufacturer’s instructions. h. Do not overfill
cylinders. (No more than 80 % volume liquid charge). i. Do not exceed the
maximum working pressure of the cylinder, even temporarily.
17
ENG
j. When the cylinders have been filled correctly and the process completed,
make sure that the cylinders and the equipment are removed from site promptly
and all isolation valves onthe equipment are closed off. k. Recovered
refrigerant shall not be charged into another refrigeration system unless it
has been cleaned and checked. 24. Labelling Equipment shall be labelled
stating that it has been de-commissioned and emptied of refrigerant. The label
shall be dated and signed. Ensure that there are labels on the equipment
stating the equipment contains flammable refrigerant. 25. Recovery When
removing refrigerant from a system, either for servicing or decommissioning,
it is recommended good practice that all refrigerants are removed safely. When
transferring refrigerant into cylinders, ensure that only appropriate
refrigerant recovery cylinders are employed. Ensure that the correct number of
cylinders for holding the total system charge are available. All cylinders to
be used are designated for the recovered refrigerant and labelled for that
refrigerant (i.e. special cylinders for the recovery of refrigerant).
Cylinders shall be complete with pressure-relief valve and associated shut-off
valves in good working order. Empty recovery cylinders are evacuated and, if
possible, cooled before recovery occurs. The recovery equipment shall be in
good working order with a set of instructions concerning the equipment that is
at hand and shall be suitable for the recovery of all appropriate refrigerants
including, when applicable, flammable refrigerants. In addition, a set of
calibrated weighing scales shall be available and in good working order. Hoses
shall be complete with leak-free disconnect couplings and in good condition.
Before using the recovery machine, check that it is in satisfactory working
order, has been properly maintained and that any associated electrical
components are sealed to prevent ignition in the event of a refrigerant
release. Consult manufacturer if in doubt. The recovered refrigerant shall be
returned to the refrigerant supplier in the correct recover cylinder, and the
relevant waste transfer note arranged. Do not mix refrigerants in recovery
units and especially not in cylinders. If compressors or compressor oils are
to be removed, ensure that they have been evacuated to an acceptable level to
make certain that flammable refrigerant does not remain within the lubricant.
The evacuation process shall be carried out prior to returning the compressor
to the suppliers. Only electric heating to the compressor body shall be
employed to accelerate this process. When oil is drained from a system, it
shall be carried out safely.
INSTALLATION PRECAUTIONS (R32)
Important considerations
1. The air conditioner you buy must be installed by professional personnel
and the Installation manual is used only for the professional installation
personnel! The installation specifications should be subject to our aftersale
service regulations.
2. When filling the combustible refrigerant, any of your rude operations may
cause serious injury or injuries to human body or bodies and object or
objects.
3. A leak test must be done after the installation is completed. 4. It is a
must to do the safety inspection before maintaining or repairing an air
conditioner using combustible
refrigerant in order to ensure that the fire risk is reduced to minimum. 5. It
is necessary to operate the machine under a controlled procedure in order to
ensure that any risk arising
from the combustible gas or vapor during the operation is reduced to minimum.
6. Requirements for the total weight of filled refrigerant and the area of a
room to be equipped with an air
conditioner (are shown as in the following Tables GG.1 and GG.2)
18
ENG
The maximum charge and the required minimum floor area
m = (4 m3) x LFL , m = (26 m3) x LFL, m = (130 m3 ) x LFL
1
2
3
Where LFL is the lower flammable limit in kg/m3, R32 LFL is 0.038 kg/m3.
For the appliances with a charge amount m1 < M = m2: The maximum charge in a room shall be in accordance with the following:
m = 2.5 x (LFL)(5/4) x h x (A)1/2
max
0
The required minimum floor area Amin to install an appliance with refrigerant charge M (kg) shall be in accordance
with following: A = (M/ (2.5 x (LFL)(5/4) x h ))2
min
0
Where:
Table GG.1 – Maximum charge (kg)
Category
LFL (kg/m3)
h0 (m)
4
Floor area (m2)
7
10
15
20
30
50
1
1.14
1.51
1.8
2.2
2.54
3.12
4.02
R32
0.306
1.8
2.05
2.71
3.24
3.97
4.58
5.61
7.254
2.2
2.5
3.31
3.96
4.85
5.6
6.86
8.85
Table GG.2 – Minimum room area (m2)
Category
LFL (kg/m3)
R32
0.306
h0 (m)
0.6 1 1.8 2.2
4 1.224kg
Charge amount (M) (kg) Minimum room area (m2)
7
10
15
20
30
1.836kg 2.448kg 3.672kg 4.896kg 6.12kg
29
51
116
206
321
10
19
42
74
116
3
6
13
23
36
2
4
9
15
24
50 7.956kg
543 196 60 40
Installation Safety Principles
1. Site Safety · Open Flames Prohibited · Ventilation Necessary
2. Operation Safety
· Mind Static Electricity · Must wear protective clothing and anti-static
gloves · Don`t use mobile phone
3. Installation Safety
· Refrigerant Leak Detector · Appropriate Installation Location
The left picture is the schematic diagram of a refrigerant leak detector.
19
ENG
Please note that: 1. The installation site should be well-ventilated.
2. The sites for installing and maintaining an air conditioner using
Refrigerant R32 should be free from open fire or welding, smoking, drying oven
or any other heat source higher than 548 which easily produces open fire.
3. When installing an air conditioner, it is necessary to take appropriate
anti-static measures such as wear antistatic clothing and/or gloves.
4. It is necessary to choose the site convenient for installation or
maintenance wherein the air inlets and outlets of the indoor and outdoor units
should be not surrounded by obstacles or close to any heat source or
combustible and/or explosive environment.
5. If the indoor unit suffers refrigerant leak during the installation, it is
necessary to immediately turn off the valve of the outdoor unit and all the
personnel should go out till the refrigerant leaks completely for 15 minutes.
If the product is damaged, it is a must to carry such damaged product back to
the maintenance station and it is prohibited to weld the refrigerant pipe or
conduct other operations on the user’s site.
6. It is necessary to choose the place where the inlet and outlet air of the
indoor unit is even.
7. It is necessary to avoid the places where there are other electrical
products, power switch plugs and sockets, kitchen cabinet, bed, sofa and other
valuables right under the lines on two sides of the indoor unit.
Suggested Tools
Tool
Standard Wrench
Adjustable/ Crescent Wrench
Picture
Tool
Pipe Cutter
Screw drivers (Phillips & Flat blade)
Picture
Tool Vacuum Pump
Safety Glasses
Picture
Torque Wrench
Manifold and Gauges
Work Gloves
Hex Keys or Allen Wrenches
Level
Refrigerant Scale
Drill & Drill Bits
Flaring tool
Micron Gauge
Hole Saw
Clamp on Amp Meter
20
ENG
Pipe Length and Additional Refrigerant Inverter Models Capacity (Btu/h) Lenght of pipe with standard charge Maximum distance between indoor and outdoor unit Additional refrigerant charge Max. diff. in level between indoor and outdoor unit Type of refrigerant
9K-12K 5m/16ft 15m/49ft 15g/m 10m/32ft
R32
Torque Parameters
PIPE
1/4″ (6) 3/8″ (9.52) 1/2″ (12) 5/8″ (15.88)
Newton meter [N x m] 18 – 20 30 – 35 45 – 50 60 – 65
Pound-force foot (1bf-ft)
24.4 – 27.1 40.6 – 47.4 61.0 – 67.7 81.3 – 88.1
Kilogram-force meter (kgf-m) 2.4 – 2.7
4.1 – 4.8
6.2 – 6.9
8.2 – 8.9
Dedicated Distribution Device and Wire for Air Conditioner
Maximum Operating Current of Air Conditioner (A)
8
Minimum Wire Crosssectional Area (mm2)
0.75
Specification of Socket or Switch (A)
10
8 and 10
1.0
10
10 and 15
1.5
16
15 and 24
2.5
25
24 and 28
4.0
32
28 and 32
6.0
40
Fuse Specification (A)
20 20 32 32 64 64
NOTE
This table is only for reference, the installation shall meet the requirements of local laws and regulations.
INSTALLATION
INDOOR UNIT INSTALLATION
Step 1: Select Installation location
1. Ensure the installation complies with the installation minimum dimensions
(defined below) and meets the minimum and maximum connecting piping length and
maximum change in elevation as defined in the System Requirements section.
2. Air inlet and outlet will be clear of obstructions, ensuring proper
airflow throughout the room. 3. Condensate can be easily and safely drained.
4. All connections can be easily made to outdoor unit. 5. Indoor unit is out
of reach of children. 6. A mounting wall strong enough to withstand four times
the full weight and vibration of the unit. 7. Filter can be easily accessed
for cleaning.
21
ENG
8. Leave enough free space to allow access for routine maintenance. 9.
Install at least 10 ft. (3 m) away from the antenna of TV set or radio.
Operation of the air conditioner may
interfere with radio or TV reception in areas where reception is weak. An
amplifier may be required for the affected device. 10. Do not install in a
laundry room or by a swimming pool due to the corrosive environment.
Minimum Indoor Clearances
Ceiling
33cm If the tube sticks out from the left side.
53cm If the tube sticks out from the right side.
Floor
Step 2: Install Mounting Plate
1. Take the mounting plate from the back of indoor unit. 2. Ensure to meet
the minimum installation dimension requirements as step 1, according to the
size of mounting
plate, determine the position and stick the mounting plate close to the wall.
3. Adjust the mounting plate to a horizontal state with a spirit level, then
mark out the screw hole positions on the
wall. 4. Put down the mounting plate and drill holes in the marked positions
with drill. 5. Insert expansion rubber plugs into the holes, then hang the
mounting plate and fix it with screws.
Reference screw positions
Spirit level
Mounting plate
NOTE: (I) Make sure the mounting plate is firm enough and flat against the
wall after installation. (II) This figure shown may be different from the
actual object, please take the latter as the standard.
22
ENG
Step 3: Drill Wall Hole
3.1 Three optional piping modes show be determined Mode1: Left, the Fresh air
pipe, the refrigerant piping ,the drainage pipe, and connecting cables all are
through
one hole to the outside. Mode2: Right, the Fresh air pipe, the refrigerant
piping ,the drainage pipe, and connecting cables all are through
one hole to the outside Mode3: Back, the Fresh air pipe, the refrigerant
piping ,the drainage pipe, and connecting cables go through two
side-by-side wall holes. 3.2 For Mode3, follow the reference size for mounting
plate and hole to determine location.
For Mode1 and Mode2, Determine the location of wall hole base on the following
size.
3.3 Drill the wall hole with 70mm core drill and with small oblique angle
lower than the indoor end about 5mm to 10mm.
3.4 Place the wall sleeve and wall sleeve cover (both are optional parts) to
protect the connection parts.
Wall sleeve Cover (Optional)
Indoor
Wall sleeve (Optional)
Outdoor
Small bolique angle
Caution: When drill the wall hole, maker sure to avoid wires, plumbing and other sensitive components.
23
ENG
Step 4: Connecting Refrigerant Pipe
1. According to the wall hole position, select the appropriate piping mode.
There are three optional piping modes for indoor units as shown in the figure
below: In Piping Mode 1 or Piping Mode 3, a notch should be made by using
scissors to cut the plastic sheet of piping outlet and cable outlet on the
corresponding side of the indoor unit.
Note: When cutting off the plastic sheet at the outlet, the cut should be
trimmed to smooth.
2. Bending the connecting pipes with the port facing up as shown in the figure.
Piping outlet Cable outlet
YES
NO
3. Take off the plastic cover in the pipe ports and take off the protective
cover on the end of piping connectors. 4. Check whether there is any sundry on
the port of the connecting pipe and make ensure the port is clean. 5. After
align the center, rotate the nut of the connecting pipe to tighten the nut as
tightly as possible by hand. 6. Use a torque wrench to tighten it according to
the torque values in the torque requirements table;
(Refer to the torque requirements table on section INSTALLATION PRECAUTIONS)
7. Wrap the joint with the insulation pipe.
Note: For R32 refrigerant, the connector should be placed outdoors.
Indoor
Outdoor
The connector should be outdoor
24
ENG
Step 5: Connect Drainage Hose
1. Adjust the drainage hose(if applicable) In some model, both sides of the
indoor unit are provided with drainage ports, you can choose one of them to
attache the drainage hose. And plug the unused drain port with the rubber
attached in one of the ports.
Drainage ports 2. Connect the drainage hose to the drainage port, ensure the
joint is firm and the sealing effect is good. 3. Wrap the joint firmly with
teflon tape to ensure no leaks. Note: Make sure there is no twists or dents,
and the pipes should be placed obliquely downward to avoid
blockage, to ensure proper drainage.
Step 6: Connect Wiring
1. Choose the right cables size determined by the maximum operating current
on the nameplate. (Check the cables size refer to section INSTALLATION
PRECAUTIONS)
2. Open the front panel of indoor unit. 3. Use a screwdriver, open the
electric control box cover, to reveal the terminal block. 4. Unscrew the cable
clamp. 5. Insert one end of the cable into the position of control box from
the back of the right end of the indoor unit. 6. Connect the wires to
corresponding terminal according to the wiring diagram on the electric control
box
cover. And make sure that they are well connected. 7. Screw the cable clamp to
fasten the cables. 8. Reinstall the electric control box cover and front
panel.
Control box cover
Cable clamp
Wiring diagram
25
ENG
Step7: Connecting Fresh Air Pipe and place the filter
1. According to the wall hole position, select the appropriate piping mode.
Mode1: Left, together with refrigerant piping ,the drainage pipe, and
connecting cables. Mode2: Right, together with refrigerant piping ,the
drainage pipe, and connecting cables. Mode3: Back, the fresh air pipe is not
bundled with other pipes.
2. Measure the length of the fresh air pipe assembly. Connect the fresh air
pipe and the-through-wall pipe assembly to form a fresh air pipe assembly.
For mode 1: Measure the distance between the left bottom corner of the mounting plate and the center of the wall hole, the length of the fresh air pipe assembly is equal to the measured length plus 650mm.
Indoor
Outdoor
Measured length
Unit fresh air inlet
Measured length + 650mm
Crop line
For mode 2: Measure the distance between the left bottom corner of the mounting plate and the center of the wall hole, the length of the fresh air pipe assembly is equal to the measured length.
Unit fresh air inlet
Indoor
Measured length
Crop line
Measured length
Outdoor
For mode 3: The length of the fresh air pipe assembly is 310mm and the exposed length of the fresh air pipe is 50mm.
Note: The length of the fresh air pipe assembly refers to the fresh air pipe except the hard pipe through the wall, including the fresh air pipe and soft joints.
26
ENG
3. Adjusting the length of the fresh air pipe assembly According to the
installation environment, determine to adjust the length of fresh air pipe
assembly. 3.1 Shorten the length Cut the fresh air pipe to the appropriate
length, keeping the section with the through-wall pipe.
Crop line Fresh air pipe Through-wall pipe assembly
If it is nessary to cut the through-wall pipe assembly due to installation needs. first, cut the through-wall pipe assembly to a suitable length. Then cut a piece of new air pipe of a suitable length. Take out the adapter from the accessory bag, and insert the adapter into the through-wall pipe and fix it firmly with glue.Finally, screw the suitable new air pipe into the adapter.
Crop line
Through-Crop line wall pipe assembly
Suitable length of fresh air pipe Adapter
Crop line Through-wall pipe
Connect fresh air pipe, adapters, and through- wall pipe
Note: 1. The overlapping part of the adapter and the through-wall pipe needs
to be pressed flat withtools and cannot
be warped; 2. The adapter cannot be forced into the through-wall pipe,
otherwise it may cause the connecting part to warp,
and the distance between the round pipe end of the adapter and the through-
wall pipe is 65mm;
3.2 Increase the length Use the extension joint to connect the appropriate length of fresh air pipe to the fresh air pipe assembly, make sure the interface is in the middle of the extension joint, and finally wrap the connection position with tape.
Extension joint
Through-wall pipe assembly
Fresh air pipe for extension
Two-pipe connection interface Note: The number of bends of the fresh air pipe
and the length of the pipe will affect the amount of fresh air. It is
recommended to use the mode 3 and avoid increasing the length of the fresh air
pipe when the installation conditions allow.
27
ENG 4. Screw the fresh air pipe into the fresh air inlet hole at the back of
the indoor unit.
5. Open the indoor panel and take out the filter holder, place HEPA filter
for fresh air then restore the holder. filter holder
HEPA filter
Step 8: Wrap Piping and Cable
After the refrigerant pipes, connecting wires and drainage hose are all
installed, in order to save space, protect and insulate them, it must be
bundle with insulating tape before passing them through the wall hole.
1. Arrange the pipes ,cables and drainage hose well as the following picture.
Fresh air pipe
Metal strap supporter
Fresh air pipe Refrigerant pipe Connecting wiring
Mode 1 After arrange all pipes and cables, take the Metal strap supporter out
of the accessories of fresh air. Insert into the slot as the picture to fix
the pipes.
Refrigerant pipe Drainage Hose
28
Metal strap supporter
Refrigerant pipe Connecting wiring
Drainage hose
ENG
Mode 2 After arrange all pipes and cables, take the Metal strap supporter out
of the accessories of fresh air. Insert into the slot as the picture to fix
the pipes.
Refrigerant pipe Fresh air pipe
Refrigerant pipe
Protection net
Drainage
Hose
Top cover
Connecting wiring Refrigerant pipe
Mode3
Note: Avoid crossing and bending of parts.
2. Using the insulating tape wrap the fresh air pipes, the refrigerant pipes,
connecting wires and drainage hose together tightly.
Outdoor Through-wall pipe
Refrigerant pipe Drainage Hose
Connecting wiring
Indoor Wall sleeve cover (optional)
Mode 1
29
ENG
Indoor
Outdoor Through-wall pipe
Wall sleeve cover (optional)
Refrigerant pipe Drainage Hose
Connecting wiring
Mode 2
Indoor
Mode 3
Sealant Through-wall pipe
Refrigerant pipe Drainage Hose Connecting wiring
Outdoor
Note: 1. The distance between the fresh air inlet and the wall should not
exceed 350mm; 2. During installation, the fresh air pipe assembly can be
rotated at an appropriate angle according to the position
of the outdoor unit, so that the connecting pipe does not block the fresh air
inlet. 3. The fresh air pipe should be slightly inclined downward, and there
should be no rising section to prevent
rainwater from entering the room. 4. If it is necessary to bend the fresh air
pipe, the minimum radius of the bend of the fresh air pipe should be
greater than 60mm, otherwise it may affect the fresh air effect. 5. The fresh
air inlet should not be placed in the air outlet of the outdoor unit, in a
closed space or in a place with
bad air.
Step 9: Mount Indoor Unit
1. Slowly pass the refrigerant pipes, connecting wires and drainage hose
wrapped bundle through the wall hole. 2. Hook the top of indoor unit on the
mounting plate. 3. Apply slight pressure to the left and right sides of the
indoor unit, make sure the indoor unit is hooked firmly. 4. Push down the
bottom of indoor unit to let the snaps onto the hooks of the mounting plate,
and make sure it
is hooked firmly.
30
ENG
Step 10: Place the protection cover for Fresh air inlet
Take out the protection cover and rotate it into the fresh air pipe, use tape
to tighten the joint. And keep the cover facing to the ground to prevent the
rain flow into the fresh air pipe. Make sure the fresh air inlet is over 200mm
from the wall or other blocks.
Sealant
Drainage hose Connecting wiring
Refrigerant pipes
Fresh Air pipe Protection cover
OUTDOOR UNIT INSTALLATION
Step 1: Select Installation Location
Select a site that allows for the following: 1. Do not install the outdoor
unit near sources of heat, steam or flammable gas. 2. Do not install the unit
in too windy or dusty places. 3. Do not install the unit where people often
pass. Select a place where the air discharge and operating sound will not
disturb the neighbors. 4. Avoid installing the unit where it will be exposed
to direct sunlight ( other wise use a protection, if necessary, that should
not interfere with the air flow). 5. Reserve the spaces as shown in the
picture for the air to circulate freely. 6. Install the outdoor unit in a safe
and solid place. 7. If the outdoor unit is subject to vibration, place rubber
blankets onto the feet of the unit.
Over 50cm
Over 30cm
Over 30cm
Over 200cm
Over 50cm
31
ENG
Step 2: Install Drainage Hose
1. This step only for heating pump models. 2. Insert the drainage joint to
the hole at the bottom of the outdoor
unit. 3. Connect the drainage hose to the joint and make the connection
well enough.
Drainage joint
Drainage hose
Step 3: Fix Outdoor Unit
1. According to the outdoor unit installation dimensions to mark the
installation position for expansion bolts . 2. Drill holes and clean the
concrete dust and place the bolts . 3. If applicable install 4 rubber blankets
on the hole before place the outdoor unit (Optional). This will reduce
vibrations and noise. 4. Place the outdoor unit base on the bolts and pre-
drilled holes. 5. Use wrench to fix the outdoor unit firmly with bolts
Note: The outdoor unit can be fixed on a wall-mounting bracket. Follow the instruction of the wall-mounting bracket to fix the wall-mounting bracket on the wall, and then fasten the outdoor unit on it and keep it horizontal. The wall-mounting bracket must be able to support at least 4 times of the weight of outdoor unit.
Install 4 rubber blankets (Optional)
Step 4: Install Wiring
1. Use a phillips screwdriver to unscrew wiring cover, grasp and press it
down gently to take it down. 2. Unscrew the cable clamp and take it down. 3.
According to the wiring diagram pasted inside the wiring cover, connect the
connecting wires to the
corresponding terminals, and ensure all connections are firmly and securely.
4. Reinstall the cable clamp and wiring cover. Note: When connecting the wires
of indoor and outdoor units, the power should be cut off.
Terminal block
Cable clamp Wiring cover
Wiring diagram
32
ENG
Step 5: Connecting Refrigerant Pipe
1. Unscrews the valve cover, grasp and press it down gently to take it
down(if the valve cover is applicable). 2. Remove the protective caps from the
end of valves. 3. Take off the plastic cover in the pipe ports and check
whether there is any sundry on the port of the
connecting pipe and make ensure the port is clean. 4. After align the center,
rotate the flare nut of the connecting pipe to tighten the nut as tightly as
possible by
hand. 5. Use a spanner hold the body of the valve and use a torque wrench to
tighten the flare nut according to the
torque values in the torque requirements table. (Refer to the torque
requirements table on section INSTALLATION PRECAUTIONS)
connection pipes
Take down the valve cover
flare nuts
Step 6: Vacuum Pumping
1. Use a spanner to take down the protective caps from the service port, low
pressure valve and high pressure valve of the outdoor unit.
2. Connect the pressure hose of manifold gauge to the service port on the
outdoor unit low pressure valve. 3. Connect the charge hose from the manifold
gauge to the vacuum pump. 4. Open the low pressure valve of the manifold gauge
and close the high pressure valve. 5. Turn on the vacuum pump to vacuum the
system. 6. The vacuum time should not be less than 15 minutes, or make sure
the compound gauge indicates -0.1 MPa
(-76 cmHg) 7. Close the low pressure valve of the manifold gauge and turn off
the vacuum. 8. Hold the pressure for 5 minutes, make sure that the rebound of
compound gauge pointer does not exceed
0.005 MPa. 9. Open the low pressure valve counterclockwise for 1/4 turn with
hexagonal wrench to let a little refrigerant fill
in the system, and close the low pressure valve after 5 seconds and quickly
remove the pressure hose. 10. Check all indoor and outdoor joints for leakage
with soapy water or leak detector. 11. Fully open the low pressure valve and
high pressure valve of the outdoor unit with hexagonal wrench. 12. Reinstall
the protective caps of the service port, low pressure valve and high pressure
valve of the outdoor unit. 13. Reinstall the valve cover.
33
ENG
compound gauge
Low pressure valve Service port
High pressure valve Valve protective caps
Pressure hose
Manifold gauge
Pressure gauge High pressure valve Low pressure valve
Charge hose
Vacuum pump
TEST OPERATION
Inspections Before Test Run
Do the following checks before test run.
Description
Electrical safety inspection
Inspection method
· Check whether the power supply voltage complies with specification. · Check
whether there is any wrong or missing connection between the power
lines, signal line and earth wires. · Check whether the earth resistance and
insulation resistance comply with
requirements.
Installation safety inspection
Refrigerant leakage detection
· Confirm the direction and smoothness of drainage pipe. · Confirm that the
joint of refrigerant pipe is installed completely. · Confirm the safety of
outdoor unit, mounting plate and indoor unit installation. · Confirm that the
valves are fully open. · Confirm that there are no foreign objects or tools
left inside the unit. · Complete installation of indoor unit air inlet grille
and panel.
· The piping joint, the connector of the two valves of the outdoor unit, the
valve spool, the welding port, etc., where leakage may occur.
· Foam detection method: Apply soapy water or foam evenly on the parts where
leakage may occur, and observe whether bubbles appear or not, if not, it
indicates that the leakage detection result is safe.
· Leak detector method: Use a professional leak detector and read the
instruction of operation, detect at the position where leakage may occur.
· The duration of leak detection for each position should last for 3 minutes
or more; If the test result shows that there is leakage, the nut should be
tightened and tested again until there is no leakage; After the leak detection
is completed, wrap the exposed pip connector of indoor unit with thermal
insulation material and wrap with insulation tape.
34
ENG
Test Run Instruction
1. Turn on the power supply. 2. Press the ON/OFF button on the remote
controller to turn on the air conditioner. 3. Press the Mode button to switch
the mode COOL and HEAT. In each mode set as below:
COOL-Set the lowest temperature HEAT-Set the highest temperature 4. Run about
8 minutes in each mode and check all functions are properly run and respond
the remote controller. Functions check as recommended: 4.1 If the outlet air
temperature respond the cool and heat mode 4.2 If the water drains properly
from the drainage hose 4.3 If the Louver and deflectors(optional) rotate
properly 5. Observe the test run state of the air conditioner at least 30
minutes. 6. After the successfully test run, return the normal setting and
press ON/OFF button on the remote controller to turn off the unit. 7. Inform
the user to read this manual carefully before use, and demonstrate to the user
how to use the air conditioner, the necessary knowledge for service and
maintenance, and the reminder for storage of accessories.
Note: If the ambient temperature is excess the range refer to section
OPERATION INSTRUCTIONS, and it can not run COOL or HEAT mode, lift the front
panel and refer to the emergency button operation to run the COOL and HEAT
mode.
MAINTENANCE
Warning
· When cleaning, you must shut down the machine and cut off the power supply
for more than 5 minutes.
· Under no circumstances should the air conditioner be flushed with water.
· Volatile liquid (e.g. thinner or gasoline) will damage the air conditioner,
so only use soft dry cloth or wet cloth dipped with neutral detergent to clean
the air conditioner.
· Pay attention to cleaning the filter screen regularly to avoid dust covering
which will affect the filter screen effect. When the operating environment is
dusty, the cleaning frequency should be increased appropriately.
· After removing the filter screen, do not touch the fins of the indoor unit
to avoid scratching.
Clean the unit
Wring it dry
Gentle wipe the unit surface
Tip: Wipe frequently to keep air conditioner clean and good appearance .
Disassembly and
assembly of filter
· Grasp the raised handle on the filter by hand, and then pull the filter out
in the direction deviating from the unit, so that the upper edge of the filter
is separated from the unit. The filter can be removed by lifting the filter
upwards.
· When installing the filter, first insert the lower end of the filter screen
into the corresponding position of the unit, and then squeeze the upper end of
the filter into the corresponding buckling position of the unit body.
35
ENG
Disassembly and
assembly of filter
Handle
Clean the filter
Cleaning of inner air duct
Opposite to the direction of taking out the filter
Take out the filter from the unit
Clean the filter with soapy water and air dry it
Replace the filter
Tip: When you find accumulated dust in the filter, please clean the filter in time to ensure the clean, healthy and efficient operation inside the air conditioner.
· First, loosen the knob on the middle of louver and bend the louver outwards to take it out. · Then, grasp both sides of bottom plate push downwards to take down the bottom plate. · Finally, loosen the buckle of deflector assembly with your thumb and take it out. · Wipe the air duct and fan assembly with a clean and wrung wet rag. · Clean the removed parts with soapy water and air dry it. · After cleaning, restore the removed parts in turn.
Louver
Cleaning or replace
filter of Fresh Air
First, Open the panel and take out the filter holder. Use a dust catcher to
clean the filter or replace a new one. We suggest replace the filter 6 months
or when get the reminder indicator CL on the indoor display.
filter holder
HEPA filter
Service and maintenance
· When the air conditioner is not in use for a long time, do the following
work: Take out the batteries of the remote controller and disconnect the power
supply of the air conditioner.
· When starting to use after long-term shutdown: 1. Clean the unit and filter
screen; 2. Check whether there are obstacles at the air inlet and outlet of
indoor and outdoor units; 3. Check whether the drain pipe is unobstructed;
Install the batteries of the remote controller and check whether the power is
on.
36
ENG
TROUBLESHOOTING
Malfunction
The appliance does not operate
Strange odor Noise of running water A fine mist comes from the air outlet A
strange noise can be heard
Insufficient airflow, either hot or cold
The appliance does not respond to commands
The display is off
Switch off the air conditioner immediately and cut off the power supply in the
event of:
Possible causes Power failure/plug pulled out. Damaged indoor/outdoor unit fan motor. Faulty compressor thermomagnetic circuit breaker. Faulty protective device or fuses. Loose connections or plug pulled out. It sometimes stops operating to protect the appliance. Voltage higher or lower than the voltage range. Active TIMER-ON function. Damaged electronic control board. Dirty air filter. Back flow of liquid in the refrigerant circulation. This occurs when the air in the room becomes very cold, for example in the COOLING or DEHUMIDIFYING/DRY modes. This noise is made by the expansion or contraction of the front panel due to variations in temperature and does not indicate a problem. Unsuitable temperature setting. Obstructed air conditioner intakes and outlets. Dirty air filter. Fan speed set at minimum. Other sources of heat in the room. No refrigerant. Remote control is not close enough to indoor unit. The batteries of remote control need to be replaced. Obstacles between remote control and signal receiver in indoor unit. Active DISPLAY function. Power failure. Strange noises during operation. Faulty electronic control board. Faulty fuses or switches. Spraying water or objects inside the appliance. Overheated cables or plugs. Very strong smells coming from the appliance.
37
ENG
Error code on the display
In case of error, the display on the indoor unit shown the following error
codes:
Display
Description of the trouble Indoor temperature sensor fault Indoor pipe temperature sensor fault Outdoor pipe temperature sensor fault Refrigerant system leakage or fault Malfunction of indoor fan motor Outdoor air temperature sensor fault Indoor and outdoor communication fault
Display
Description of the trouble Outdoor discharge temperature sensor fault Outdoor
IPM module fault Outdoor current detect fault Outdoor PCB EEPROM fault Outdoor
fan motor fault Outdoor suction temperature sensor fault
Filter cleaning reminder
DISPOSAL GUIDELINE (EUROPEAN)
This appliance contains refrigerant and other potentially hazardous materials.
When disposing of this appliance,the law requires special collection and
treatment. DO NOT dispose of this product as household waste or unsorted
municipal waste. When disposing of this appliance, you have the following
options:
· Dispose of the appliance at designated municipal electronic waste collection
facility. · When buying a new appliance, the retailer will take back the old
appliance free of charge. · The manufacturer will also take back the old
appliance free of charge. · Sell the appliance to certifid scrap metal
dealers. · Disposing of this appliance in the forest or other natural
surroundings endangers your health
and is bad for the environment. Hazardous substances may leak into the ground
water and enter the food chain.
Smart WiFi app user manual can be found at: https://tesla.info/wp-
content/uploads/pdf/TeslaO2WiFiapp.pdf
38
: https://tesla.info/wp-content/uploads/pdf/TeslaO2WiFiapp.pdf
77
O : . . . 84 1303 , T: +359 882 915 403
Serial No. ……………………………………………………………………………………………………………………………………………..
Purchase Date: …………………………………………………………………………………………………………………………………….
, ………………………………………………………………………………………………………………………….
Customer: ……………………………………………………………………………………………………………………………………………
Customer’s Phone No.: ………………………………………………………………………………………………………………………..
Customer’s Address: ……………………………………………………………………………………………………………………………
Dealer’s Name: …………………………………………………………………………………………………………………………………….
. Dealer’s Address and tel. …………………………………………………………………………………………………………………
Customer’s Signature: ………………………………………………………………………………………………………………………….
Dealer’s Signature & Stamp ………………………………………………………………………………………………………………….
78
Smart WiFi : https://tesla.info/wp-content/uploads/pdf/TeslaO2WiFiapp.pdf
120
Comtrade Distribution 128, 164 52, , ,
/ Product Type:
/ Serial No:
/ Purchase Date:
/ Customer:
/ Customer’s Phone No.:
/ Customer’s Address:
TESLA
1. TESLA (2) (10) , . . : . . . www.teslagiveaways.com (30) / . . . 3 . . (
10-) 2 .
2. , TESLA , , , , .
3. , , .
4. , .
5. . 6. (..
121
). 7. : · . · ,
. · , service TESLA . · , , , , / , , , , . · . · TESLA · , , , , , ( ), . 8.
. 9. . TESLA , . 10. .
email: warranty.gr@comtrade.com
122
( & )
…./…./….
1 Service …./…./….
2 Service …./…./….
3 Service …./…./….
4 Service …./…./….
5 Service …./…./….
6 Service …./…./….
7 Service …./…./….
8 Service …./…./….
9 Service …./…./….
123
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>