Honeywell TH8000 Vertical Non Programmable Thermostat Installation Guide
- July 26, 2024
- Honeywell
Table of Contents
- Honeywell TH8000 Vertical Non Programmable Thermostat
- Product Information
- Product Usage Instructions
- Wallplate installation
- Power options
- Wiring
- Remove tab and mount thermostat
- Set date and time
- Installer setup
- Installer system test
- Special functions
- Accessories & replacement parts
- Specifications
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Honeywell TH8000 Vertical Non Programmable Thermostat
Product Information
Specifications :
- Model: Touch-screen Programmable Thermostat
- Battery: Lithium battery with Perchlorate material
- Power Options: 24VAC primary power or battery backup
- Terminal Designations: R, Rc, C, W, W2, Y, Y2, G, S1, S2 (for different system types)
Product Usage Instructions
Wallplate Installation:
- Separate wallplate from thermostat.
- Mount wallplate by drilling 3/16 holes for drywall or 7/32 holes for plaster.
- Grasp top and bottom of wallplate and pull to remove from thermostat.
Power Options :
For primary power, connect the common side of the transformer to the C
terminal. Insert supplied batteries for backup power
Wiring:
Follow the terminal designations based on your system type and wiring guide
provided in the manual. Remove factory-installed jumper for two-transformer
systems.
Frequently Asked Questions (FAQ)
-
Q: How can I get assistance with this product?
A: For help with the product, visit http://customer.honeywell.com or call Honeywell Customer Care at 1-800-468-1502. -
Q: What should I do if my old control contains mercury?
A: Do not place the old control in the trash. Contact your local waste management authority for recycling and proper disposal instructions.
Installation Guide
VisionPRO® TH8000 Series
Touch-screen Programmable Thermostat
This manual covers the following models
- TH8110U: For 1 Heat/1 Cool systems
- TH8320U: For up to 3 Heat/2 Cool systems
- TH8321U: For up to 3 Heat/2 Cool systems with dehumidification (Pull thermostat from wallplate and turn over to find model number)
System Types
- Gas, oil, or electric heat with air conditioning
- Warm air, hot water, high efficiency furnaces, heat pumps, steam, gravity
- Heat only — two-wire systems, power to open and close zone valves (Series 20), and normally open zone valves
- Heat only with fan
- Cool only
- 750 mV heating systems
This thermostat contains a Lithium battery which may contain Perchlorate
material. Perchlorate Material—special handling may apply,
See
www.dtsc.ca.gov/hazardouswaste/perchlorate
Need Help?
For assistance with this product please visit http://customer.honeywell.com
or call Honeywell Customer Care toll-free at
1-800-468-1502
® U.S. Registered Trademark. Copyright © 2012 Honeywell International Inc. All rights reserved.
Wallplate installation
- Separate wallplate from thermostat.
- Mount wallplate as shown below.
Must be installed by a trained, experienced technician
-
Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.
-
CAUTION : ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation. -
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.
Power options
Wiring
Terminal Designations Shaded areas below apply only to TH8320/TH8321.
Conventional Terminal Letters:
- R Heating power. Connect to secondary side of heating system transformer.
- Rc Cooling power. Connect to secondary side of cooling system transformer.
- C Common wire from secondary side of cooling transformer (if 2 transformers).
- W 1st stage heat relay.
- W2 2nd stage heat relay.
- Y 1st stage compressor contactor.
- Y2 2nd stage compressor contactor.
- G Fan relay.
- S1 Optional outdoor or remote sensor.
- S2 Optional outdoor or remote sensor
Heat Pump Terminal Letters:
- R Heating power. Connect to secondary side of heating system transformer.
- Rc Cooling power. Connect to secondary side of cooling system transformer.
- C Common wire from secondary side of cooling system transformer.
- Y 1st stage compressor contactor.
- Y2 2nd stage compressor contactor.
- Aux/E Auxiliary/Emergency heat relay.
- G Fan relay.
- L Heat pump reset (powered continuously when System is set to Em Heat; system monitor when set to Heat, Cool or Off).
- O/B Changeover valve for heat pumps.
- S1 Optional outdoor or remote sensor.
- S2 Optional outdoor or remote sensor.
Wiring
Wiring guide—conventional systems
Shaded areas below apply only to TH8320/TH8321.
-
1H/1C System (1 transformer)
-
1H/1C System (2 transformers)
-
Heat Only System
-
Heat Only System With Fan
-
Heat Only System (Series 20)
-
2H/2C System (1 transformer)
-
__**Y2 **Cool relay 2
-
__**W2 **Heat relay 2
-
Rc **** Power [1]
| R| [R+Rc joined by jumper]
__**W __**
Y
| Heat relay 1
Cool relay 1
G| Fan relay
C| 24VAC common [3]
__**S1 __**
__**S2 __**
| Optional outdoor/remote sensor Optional outdoor/remote sensor
2H/2C System (2 transformers)
Y2 **** Cool relay 2
| W2| Heat relay 2
Rc| Power (cooling transformer) [1, 2]
R| Power (heating transformer) [1, 2]
W| Heat relay 1
Y| Cool relay 1
G| Fan relay
C| 24VAC common [3, 4]
S1| Optional outdoor/remote sensor
S2| Optional outdoor/remote sensor
See [notes] below
- Power supply. Provide disconnect means and overload protection as required.
- Remove jumper for 2-transformer systems.
- Optional 24VAC common connection.
- Common connection must come from cooling transformer.
Wiring guide—heat pump systems
Shaded areas below apply only to TH8320/TH8321.
-
1H/1C Heat Pump (no auxiliary heat)
-
2H/2C Heat Pump (no auxiliary heat)
-
2H/1C Heat Pump (with auxiliary heat)
-
L **** Equipment monitor [6, 7]
| __**Aux/E Auxiliary/Emergency heat relay (Heat 2 )
Rc ** Power [1]
R| [R+Rc joined by jumper]
__**O/B **| Changeover valve [5]
Y| Compressor relay
G| Fan relay
C| 24VAC common [3]
S1| Optional outdoor/remote sensor
S2| Optional outdoor/remote sensor
- 2H/2C Heat Pump (no auxiliary heat)
- Y2 **** Compressor 2 relay
| Rc| Power [1]
R| [R+Rc joined by jumper]
O/B| Changeover valve [5]
Y| Compressor 1 relay
G| Fan relay
C| 24VAC common [3]
S1| Optional outdoor/remote sensor
S2| Optional outdoor/remote sensor
- 3H/2C Heat Pump (with auxiliary heat)
- Y2 **** Compressor 2 relay
| L| Equipment monitor [6, 7]
Aux/E Auxiliary/Emergency heat relay (Heat 2)
Rc| Power [1]
R| [R+Rc joined by jumper]
O/B| Changeover valve [5]
Y| Compressor 1 relay
G| Fan relay
C| 24VAC common [3]
S1| Optional outdoor/remote sensor
S2| Optional outdoor/remote sensor
See [notes] below
- Power supply. Provide disconnect means and overload protection as required
- Optional 24VAC common connection.
- O/B set to control as either O or B in installer setup.
- If L terminal is used, 24VAC common (terminal C) must be connected.
- Heat pump reset (powered continuously when thermostat is set to Em. Heat; system monitor when set to Heat, Cool, or Off).
Remove tab and mount thermostat
Set date and time
Installer setup
Setup functions Settings & Options (factory default in bold)
Shaded areas below apply only to TH8320/TH8321.
0120 | Year | 20 | ( 20 01- 20 99) |
---|---|---|---|
(first two digits) | 21 | ( 21 00- 21 78) | |
0130 | Year |
(second two digits)
| 12| (20 12 ) [Other options: 00-99]
0140| Month| 6| [Other options: 1-12]
0150| Date| 15| [Other options: 1-31]
0160| Schedule format| 4| 7-day programming
| | 0| Non-programmable
0170| System type| 1| 1 heat/1 cool conventional
| | 2| 1 heat/1 cool heat pump (no aux. heat)
| | 3| Heat only (2-wire systems)
| | 4| Heat only with fan
| | 5
6
| Hot water Series 20 system (power to open & close zone valves/normally open zone valves)
Cool only
| | 7| 2 heat/1 cool heat pump (with aux. heat)
| | 8| 2 heat/2 cool multistage conventional
| | 9| 2 heat/1 cool multistage conventional
| | 10| 1 heat/2 cool multistage conventional
| | 11| 2 heat/2 cool heat pump (no aux. heat)
| | 12| 3 heat/2 cool heat pump (with aux. heat)
0180| Fan control| 0| Gas/Oil heat (equipment controls
heating fan)
| (heating)| 1| Electric furnace (thermostat controls heating fan)
0190| Changeover valve| 0| O/B terminal controls valve in
cooling
| (O/B terminal)| 1| O/B terminal controls valve in heating
0200| Auxiliary heat| 0| Electric backup heat
| | 1| Fossil fuel backup heat
0210| External fossil| 1| External fossil fuel kit controls
backup heat
| fuel kit| 0| Thermostat controls backup heat (outdoor sensor required)
0220| 1st stage com- pressor cycle rate| 3| Recommended for
most compressors [Other options: 1, 2, 4, 5 or 6 CPH]
0230| 2nd stage com- pressor cycle rate| 3|
- Recommended for most compressors
- [Other options: 1, 2, 4, 5 or 6 CPH]
Shaded areas below apply only to TH8320/TH8321.
Setup functions Settings & Options (factory default in bold)
0500 | Furnace filter | 0 | Off |
---|---|---|---|
change reminder | 1 | 10-day run time (about 1 month) | |
2 | 30-day run time (about 3 months) | ||
3 | 60-day run time (about 6 months) | ||
4 | 90-day run time (about 9 months) | ||
5 | 120-day run time (about 1 year) | ||
6 | 365-day run time (about 3 years) | ||
0510 | Humidifier pad | 0 | Off |
change reminder | 1 | 90 calendar days | |
2 | 180 calendar days | ||
3 | 365 calendar days | ||
0520 | UV lamp change | 0 | Off |
reminder | 1 | 365 calendar days | |
0530 | Adaptive Intelligent | 1 | On ** See page 11 |
Recovery™ | 0 | Off | |
0540 | Program periods | 4 | **4 program periods (Wake, Leave, |
Return, Sleep)
| | 2| 2 program periods (Wake, Sleep)
0580| Compressor protection| 5| 5 minute compressor off
time ** See page 11 [Other options: 0, 1, 2, 3 or 4-minute off time]
0600| Heat temperature range stop| 90| Max. heat temperature
setting is 90°F (32°C) [Other options: 40-89°F (4.5°C to 32°C)]
0610| Cool temperature range stop| 50| Min. cool temperature
setting is 50°F (10°C) [Other options: 51-99°F (10.5°C to 37°C)]
0640| Clock format| 12| 12-hour time (i.e., “3:30 pm”)
| | 24| 24-hour time (i.e., “15:30”)
0650| Extended fan| 0| Off
| timer (heat)| 90| Fan runs for 90 seconds after call for heat ends
0660| Extended fan| 0| Off
| timer (cool)| 90| Fan runs for 90 seconds after call for cooling ends
0670| Keypad lock| 0| Keypad unlocked (fully functional)
| | 1| Partially locked (access to temperature settings only)
| | 2| Fully locked
0680| Heat temperature| 2| Standard temperature control
(recommended)
| control| 1| Choose if room is warmer than set temperature
| | 3| Choose if room does not reach set temperature
0690| Cool temperature| 2| Standard temperature control
(recommended)
| control| 1| Choose if room is cooler than set temperature
| | 3| Choose if room does not reach set temperature
0700| Temperature display offset**| 0|
- Thermostat displays actual room temperature
- [Other options: -3, -2, -1, 1, 2, 3°F offset (-1.5°C to 1.5°C)
0710| RESET| 0| No reset
| | 1| Reset installer options & program schedule to factory default (only
date and time settings are retained)
Installer system test
During installer setup, press repeatedly until “Test” appears.
Shaded areas below apply only to TH8320/TH8321.
CAUTION : EQUIPMENT DAMAGE HAZARD. Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.
Special functions
-
Shaded areas below apply only to TH8320/TH8321.
-
Auto Changeover (Setup Function 0300): When set to Auto, the thermostat automatically selects heating or cooling depending on the indoor temperature. Heat and cool settings must be at least 2 degrees apart. If function 0380 is set to On, the heat and cool settings must be at least 5 degrees apart.
Remote Sensor (Setup Function 0340): If an optional outdoor sensor is installed, the thermostat can display the outside temperature. If an optional remote indoor sensor is installed, the thermostat will display the temperature at the sensor location (the internal sensor in the thermostat is not used). -
Adaptive Intelligent Recovery (Setup Function 0530): Allows the thermostat to “learn” how long the furnace and air conditioner take to reach programmed temperature settings, so the temperature is reached at the scheduled time.
-
Compressor Protection (Setup Function 0580): Forces the compressor to wait a few minutes before restarting, to prevent damage. During this time, the message “Wait” flashes on the display.
-
Dehumidification control (Setup Function 0380): TH8321 models monitor the indoor humidity level and automatically activate the cooling system to reduce humidity by lowering the temperature by up to 3 degrees below the current cool setting.
-
Heat Pump Temperature Lockout (with fossil-fuel backup): If the thermostat is installed with an optional outdoor sensor, you can select a compressor lockout temperature (Function 0350). When the outdoor temperature is below the lockout temperature, only the auxiliary heat operates. When the outdoor temperature is above the lockout temperature, only the compressor operates.
-
Heat Pump Temperature Lockouts (with electric heat backup): If the thermostat is installed with an optional outdoor sensor, you can select a compressor lockout temperature (Function 0350) and/or an auxiliary heat lockout temperature (Function 0360). When the outdoor temperature is below the compressor lockout temperature, only the auxiliary heat operates. When the outdoor temperature is above the auxiliary lockout temperature, only the compressor operates. If the outdoor temperature is between the compressor and auxiliary lockout temperatures, both the compressor and auxiliary heat can operate.
Accessories & replacement parts
- Please contact your distributor to order replacement parts.
- Outdoor temperature sensor…………………………. Part Number C7089U1006
- Remote indoor temperature sensor………………. Part Number C7189U1005
- Cover plate*……………………………………………………. Part Number 32003796-001
- (Use to cover marks left by old thermostats.)
Specifications
- Temperature Ranges
- Heat: 40° to 90°F (4.5° to 32°C)
- Cool: 50° to 99°F (10° to 37°C)
- Operating Ambient Temperature
- 0° to 120°F (-18° to 48.9°C)
- Shipping Temperature
- -30° to 150°F (-34° to 66°C)
- Operating Relative Humidity
- 5% to 90% (non-condensing)
- Physical Dimensions
- 4-9/16” H x 6” W x 1-3/8” D
- 116 mm H x 152 mm W x 35 mm D
Electrical Ratings
Need Help?
For assistance with this product please visit http://customer.honeywell.com
or call Honeywell Customer Care toll-free at
1-800-468-1502
- Automation and Control Solutions
- Honeywell International Inc.
- 1985 Douglas Drive North
- Golden Valley, MN 55422
- http://customer.honeywell.com
- ® U.S. Registered Trademark.
- © 2012 Honeywell International Inc.
- 69-2693—01 M.S. 01-12
- Printed in U.S.A.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>