MOXA 5134 Series 2-Port Industrial NAT Device
Overview
The MGate 5134 is an industrial Ethernet gateway for Modbus RTU/ASCII/TCP and PROFINET network communications.
Package Checklist
Before installing the MGate 5134, verify that the package contains the following items:
- 1 MGate 5134 gateway
- Quick installation guide (printed)
- Warranty card
NOTE: Please notify your sales representative if any of the above items is missing or damaged.
Optional Accessories (can be purchased separately)
- Mini DB9F-to-TB: DB9 female to terminal block connector
- WK-25: Wall-mounting kit, 2 plates, 4 screws, 25 x 43 x 2 mm
Hardware Introduction
LED Indicators
LED | Color | Description |
---|---|---|
PWR 1, PWR 2 | Green | Power is on. |
Off | Power is off. |
Ready
| Off| Power is off.
Green
| Steady: Power is on, and the MGate is
functioning normally.
Blinking (1 sec.): The MGate has been located by the Moxa utility DSU Location function.
Red
| Steady: Power is on, and the MGate is
booting up.
Blinking slowly (0.5 sec.): Indicates an IP conflict, or the DHCP server is
not responding properly.
Flashing quickly Blinking (0.1 sec.): the microSD card failed.
PROFINET I/O
Device
| Off| No connection with PROFINET I/O controller.
Green
| Steady: PROFINET I/O is exchanging data, and Controller is in RUN mode.
Blinking (1 sec.): PROFINET DCP flash LED.
Red
| Steady: Incorrect slot configuration.
Blinking (1sec.): One or more connections timed out or in STOP mode.
Modbus RTU/ASCII/TCP
Client
| Off| No communication with the Modbus device.
Green| Steady: Normal communication in progress.
Red
| Blinking (1 sec.): Communication error.
1. The Modbus slave device returned an error (exception).
2. Received a frame error (parity error,
checksum error).
LED | Color | Description |
---|---|---|
3. Timeout (the slave device does not respond). |
4. TCP connection failed (only for Modbus
TCP).
ETH 1, ETH 2
| Green| Steady ON: Ethernet link on at 100Mbps.
Blinking: Data transmitting at 100Mbps.
Amber| Steady ON: Ethernet link on at 10Mbps.
Blinking: Data transmitting at 10Mbps.
Off| Link is down or not connected.
Dimensions
Reset Button
Restore the MGate to factory default settings by using a pointed object (such as a straightened paper clip) to hold the reset button down until the Ready LED stops blinking (approximately five seconds).
Hardware Installation Procedure
- Connect the power adapter. Connect the 12-48 VDC power line or DIN-rail power supply to the MGate 5134’s terminal block.
- Use a serial cable to connect the MGate to the Modbus device.
- Use an Ethernet cable to connect the MGate to the PROFINET I/O controller.
- The MGate 5134 is designed to be attached to a DIN rail or mounted on a wall. For DIN-rail mounting, push down the spring and properly attach it to the DIN rail until it “snaps” into place. For wall mounting, install the wall-mounting kit (optional) first and then screw the device onto the wall.
The following figure illustrates the two mounting options:
Wall- or Cabinet-mounting
We provide two metal plates to mount the unit on a wall or inside a cabinet. Attach the plates to the unit’s rear panel with screws. With the plates attached, use screws to mount the unit on the wall. The heads of the screws should be 5 to 7 mm in diameter, the shafts should be 3 to 4 mm in diameter, and the length of the screws should be over 10.5 mm.
Software Installation Information
Please download the User Manual and Device Search Utility (DSU) from Moxa’s
website: www.moxa.com For using the DSU, refer to the
User’s Manual. The MGate 5134 also supports login via a web browser.
Default IP address: 192.168.127.254
Create your administration account and password when you log in the first
time.
Pin Assignments
Modbus Serial Port (Male DB9)
Pin | RS- 232 | RS-422/ RS-485 (4W) | RS-485 (2W) |
---|---|---|---|
1 | DCD | TxD-(A) | – |
2 | RXD | TxD+(B) | – |
3 | TXD | RxD+(B) | Data+(B) |
4 | DTR | RxD-(A) | Data-(A) |
5* | GND | GND | GND |
6 | DSR | – | – |
7 | RTS | – | – |
8 | CTS | – | – |
9 | – | – | – |
Ethernet Port (RJ45)
Pin | Signal |
---|---|
1 | Tx+ |
2 | Tx- |
3 | Rx+ |
6 | Rx- |
Power Input and Relay Output Pinouts
V2+
| ****
V2-
| |
V1+
| ****
V1-
---|---|---|---|---
DC
Power Input 2
| DC
Power Input 2
| ****
N.O.
| ****
Common
| ****
N.C.
| DC
Power Input 1
|
Specifications
Power Parameters
Power Input| 12 to 48 VDC
Power Consumption| 455 mA max.
Relays
Contact Current Rating| Resistive load: 2 A @ 30 VDC
Environmental Limits
Operating Temperature| Standard models: -10 to 60°C (14 to 140°F)
Wide temp. models: -40 to 75°C (-40 to
167°F)
Storage Temperature (package included)| -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity| 5 to 95% RH
Physical Characteristics
Dimensions| 25 x 90 x 129.6 mm (0.98 x 3.54 x 5.1 in)
Weight| 294 g (0.65 lb)
Reliability
Alert Tools| Built-in buzzer and RTC
MTBF|
ATTENTION
- Power terminal plug wiring size is 28-14 AWG, tighten to 1.7 in-lbs, wire min. 80°C. Use copper conductors only.
- This device is an open-type equipment and intended to be installed in a suitable enclosure.
- If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
- When installing the device, the assembler is responsible for the securing the safety of the system in which the equipment is incorporated.
NOTE
- This device is intended for use indoors and at altitudes up to 2,000 meters.
- Pollution degree 2.
- Clean the device with a soft cloth, dry or with water.
- The power input specification complies with the requirements of SELV (Safety Extra Low Voltage), and the power supply should comply with UL 61010-1 and UL 61010-2-201.
For any repair or maintenance needs, please contact us. Moxa Inc.
No. 1111, Heping Rd., Bade Dist., Taoyuan City 334004, Taiwan +886-03-2737575