MOXA 5134 Series 2-Port Industrial NAT Device Installation Guide

June 4, 2024
MOXA

MOXA 5134 Series 2-Port Industrial NAT Device

Overview

The MGate 5134 is an industrial Ethernet gateway for Modbus RTU/ASCII/TCP and PROFINET network communications.

Package Checklist

Before installing the MGate 5134, verify that the package contains the following items:

  • 1 MGate 5134 gateway
  • Quick installation guide (printed)
  • Warranty card

NOTE: Please notify your sales representative if any of the above items is missing or damaged.

Optional Accessories (can be purchased separately)

  • Mini DB9F-to-TB: DB9 female to terminal block connector
  • WK-25: Wall-mounting kit, 2 plates, 4 screws, 25 x 43 x 2 mm

Hardware Introduction

LED Indicators

LED Color Description
PWR 1, PWR 2 Green Power is on.
Off Power is off.






Ready

| Off| Power is off.



Green

| Steady: Power is on, and the MGate is

functioning normally.

Blinking (1 sec.): The MGate has been located by the Moxa utility DSU Location function.




Red

| Steady: Power is on, and the MGate is

booting up.

Blinking slowly (0.5 sec.): Indicates an IP conflict, or the DHCP server is not responding properly.
Flashing quickly Blinking (0.1 sec.): the microSD card failed.



PROFINET I/O

Device

| Off| No connection with PROFINET I/O controller.


Green

| Steady: PROFINET I/O is exchanging data, and Controller is in RUN mode.
Blinking (1 sec.): PROFINET DCP flash LED.


Red

| Steady: Incorrect slot configuration.
Blinking (1sec.): One or more connections timed out or in STOP mode.



Modbus RTU/ASCII/TCP

Client

| Off| No communication with the Modbus device.
Green| Steady: Normal communication in progress.



Red

| Blinking (1 sec.): Communication error.

1.    The Modbus slave device returned an error (exception).

2.    Received a frame error (parity error,

checksum error).

LED Color Description
    3.    Timeout (the slave device does not respond).

4.    TCP connection failed (only for Modbus

TCP).



ETH 1, ETH 2

| Green| Steady ON: Ethernet link on at 100Mbps.
Blinking: Data transmitting at 100Mbps.
Amber| Steady ON: Ethernet link on at 10Mbps.
Blinking: Data transmitting at 10Mbps.
Off| Link is down or not connected.

Dimensions

MOXA 5134 Series 2-Port Industrial NAT Device 1

Reset Button

Restore the MGate to factory default settings by using a pointed object (such as a straightened paper clip) to hold the reset button down until the Ready LED stops blinking (approximately five seconds).

Hardware Installation Procedure

  1. Connect the power adapter. Connect the 12-48 VDC power line or DIN-rail power supply to the MGate 5134’s terminal block.
  2. Use a serial cable to connect the MGate to the Modbus device.
  3. Use an Ethernet cable to connect the MGate to the PROFINET I/O controller.
  4. The MGate 5134 is designed to be attached to a DIN rail or mounted on a wall. For DIN-rail mounting, push down the spring and properly attach it to the DIN rail until it “snaps” into place. For wall mounting, install the wall-mounting kit (optional) first and then screw the device onto the wall.

The following figure illustrates the two mounting options:

MOXA 5134 Series 2-Port Industrial NAT Device 2

Wall- or Cabinet-mounting

We provide two metal plates to mount the unit on a wall or inside a cabinet. Attach the plates to the unit’s rear panel with screws. With the plates attached, use screws to mount the unit on the wall. The heads of the screws should be 5 to 7 mm in diameter, the shafts should be 3 to 4 mm in diameter, and the length of the screws should be over 10.5 mm.

Software Installation Information

Please download the User Manual and Device Search Utility (DSU) from Moxa’s website: www.moxa.com For using the DSU, refer to the User’s Manual. The MGate 5134 also supports login via a web browser.
Default IP address: 192.168.127.254
Create your administration account and password when you log in the first time.

Pin Assignments

Modbus Serial Port (Male DB9)

Pin RS- 232 RS-422/ RS-485 (4W) RS-485 (2W)
1 DCD TxD-(A)
2 RXD TxD+(B)
3 TXD RxD+(B) Data+(B)
4 DTR RxD-(A) Data-(A)
5* GND GND GND
6 DSR
7 RTS
8 CTS
9

Ethernet Port (RJ45)

Pin Signal
1 Tx+
2 Tx-
3 Rx+
6 Rx-

Power Input and Relay Output Pinouts

MOXA 5134 Series 2-Port Industrial NAT Device 6


V2+

| ****

V2-

| |

V1+

| ****

V1-

---|---|---|---|---
DC

Power Input 2

| DC

Power Input 2

| ****

N.O.

| ****

Common

| ****

N.C.

| DC

Power Input 1

|

Specifications

Power Parameters

Power Input| 12 to 48 VDC
Power Consumption| 455 mA max.
Relays
Contact Current Rating| Resistive load: 2 A @ 30 VDC
Environmental Limits
Operating Temperature| Standard models: -10 to 60°C (14 to 140°F)

Wide temp. models: -40 to 75°C (-40 to

167°F)

Storage Temperature (package included)| -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity| 5 to 95% RH
Physical Characteristics
Dimensions| 25 x 90 x 129.6 mm (0.98 x 3.54 x 5.1 in)
Weight| 294 g (0.65 lb)
Reliability
Alert Tools| Built-in buzzer and RTC
MTBF|

ATTENTION

  • Power terminal plug wiring size is 28-14 AWG, tighten to 1.7 in-lbs, wire min. 80°C. Use copper conductors only.
  • This device is an open-type equipment and intended to be installed in a suitable enclosure.
  • If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
  •  When installing the device, the assembler is responsible for the securing the safety of the system in which the equipment is incorporated.

NOTE

  • This device is intended for use indoors and at altitudes up to 2,000 meters.
  • Pollution degree 2.
  • Clean the device with a soft cloth, dry or with water.
  • The power input specification complies with the requirements of SELV (Safety Extra Low Voltage), and the power supply should comply with UL 61010-1 and UL 61010-2-201.

For any repair or maintenance needs, please contact us. Moxa Inc.
No. 1111, Heping Rd., Bade Dist., Taoyuan City 334004, Taiwan +886-03-2737575