Schneider Electric RM17TG20 Harmony 3 Phase Control Relay Instruction Manual

July 26, 2024
Schneider Electric

Schneider Electric RM17TG20 Harmony 3 Phase Control Relay

Product Information

Specifications

  • Product Models: RM17TG00, RM17TG20, RM17TT00, RM17TA00, RM17TU00, RM17TE00, RM17UB310, RM22TG20, RM22TA31, RM22TA33
  • Input Voltage: 380V, 400V, 415V, 220V, 440V, 208V, 480V
  • Output Voltage: 380V, 400V, 415V
  • Time Delay: 0.1s
  • Asymmetry: 8%, 10%, 12%
  • Operating Temperature: -10°C to 60°C

Product Usage Instructions

Installation

  1. Ensure power supply is turned off before installation.
  2. Follow the wiring diagram provided in the user manual for correct connections.
  3. Securely mount the device in a suitable location using appropriate fasteners.

Operation

  1. Apply the input power within the specified voltage range.
  2. Adjust the settings as per your requirements using the control panel.
  3. Monitor the device for any abnormal behavior during operation.

Maintenance

  1. Regularly inspect the device for any signs of damage or wear.
  2. Keep the device clean and free from dust accumulation.
  3. Refer to the user manual for any troubleshooting steps if needed.

FAQ

  • Q: What should I do if the device is not functioning properly?
    A: Check the power supply, connections, and settings to ensure everything is correct. If issues persist, refer to the troubleshooting section in the user manual or contact customer support.

  • Q: Can this device be used in outdoor environments?
    A: It is recommended to install the device in a controlled indoor environment to ensure optimal performance and longevity.

Harmony 3 Phase Control Relay

This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations.
As standards, specifications and designs develop from time to time, always ask for confirmation of the information given in this publication.

Product Feature

  1. Relay ouput status (yellow) LED R/R1/R2
  2. 2 35 mm rail clip-in spring
  3. Power supply status (green) LED. Un/Dial pointer
  4. Voltage range selection switch (RM22TR – with ON/OFF Delay selector)
  5. Time delay adjustment potentiometer. Tt/Tt1/Tt2
  6. Overvoltage threshold adjustment potentiometer. >U
  7. Undervoltage threshold adjustment potentiometer. <U
  8. Overvoltage & Undervoltage threshold adjustment potentiometer.
  9. Asymmetry threshold adjustment potentiometer. Asy/Asym
  10. Fault detection status (yellow) LED.
  11. Diagnostic button

For product comparison, refer to Harmony Control Relays Catalog or datasheet for more information.

Dimension

Safety Information

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Disconnect all power before servicing equipment.
  • Confirm that the product power supply voltage and its tolerances are compatible with those of the network.

Failure to follow these instructions will result in death or serious injury.

WARNING
UNINTENDED EQUIPMENT OPERATION OR INADEQUATE OVERCURRENT PROTECTION

  • Do not use in safety critical system.
  • Do not disassemble, repair or modify the product.
  • Install the product in the operating environment conditions described in this document.
  • Install properly rated fuses as recommended in this document.
  • Do not connect 3 phase control relay to monitor output of Variable Speed Drive (VSD).
  • Ensure 3 phase input does not exceed the surge voltage limits stated in datasheet.

Failure to follow these instructions can result in death, serious injury, or equipment damage.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

Mounting & Installation

Recommended Distance

Connection Example

RM17T 00 / RM17UB310

RM17TG20 / RM22 / RM35TF30

  1. A fuse. UL…Class CC ; IEC…gG
  2. Warning : Do not connect 3 phase control relay to monitor output of Variable Speed Drive (VSD).
  3. Light indicator

Setting Example

Example 1: To set 3 phase voltage monitoring at 220VAC L-L +/-12 %, Asymmetry monitoring 5 %, Fault delay = 5 s using RM17TE00

Example 2: To set 3 phase voltage monitoring at 415VAC L-L, >U at 18 %, <U at 16 %, On delay = 5 s using RM22TR33

Example 3: To set 3 phase voltage monitoring at 220VAC L-N?>U at 18 %, <U at 16 %, >U Fault delay = 12 s?<U Fault delay = 9 s using RM35UB3N30

Setting Change & Reset
If the voltage range selection switch 1 position is changed while the device is operating, all the LEDs will blink, but the product continues to operate with the voltage selection preceding the change of position. The product has to be powered off and on again for the new selection to take effect. All LED’s return to their normal state if the switch is returned to the original position.

Function Diagram

L1/L2/L3 is referring to line-line voltage except for RM35UB3N30 / L1/L2/L3 fait référence à la tension ligne-ligne sauf pour RM35UB3N30 /

Phase Loss & Phase Sequence

Table 1

 | RM17TG00| RM17TG20| RM17TT00| RM17TU00| RM17TA00| RM17TE00| RM17UB310| RM22TG20| RM22TR31| RM22TR33| RM22TU21| RM22TU23| RM22TA31| RM22TA33| RM35TF30| RM35UB330| RM35UB3N30
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Phase Loss Threshold| 100V| 100V| 70%Un/150V (2)| 150V| 150V| 150V| 150V| 100V| 150V| 250V| 150V| 250V| 70%Un/150V (2)| 70%Un/250V (2)| 150V| 150V| 80V

  1. Refer to Table 1 for phase loss threshold
  2. Phase loss threshold will follow whichever of higher value
  3. Refer to Table 2 for Response time (Tr). Time Delay (Tt) does not apply to phase loss or phase sequence.

Undervoltage

Overvoltage & Undervoltage

Overvoltage & Undervoltage

Asymmetry

Table 2

 | RM17TG00| RM17TG20| RM17TT00| RM17TU00| RM17TA00| RM17TE00| RM17UB310| RM22TG20| RM22TR31| RM22TR33| RM22TU21| RM22TU23| RM22TA31| RM22TA33| RM35TF30| RM35UB330| RM35UB3N30
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Response Time (Tr)| ** <300ms
ON/OFF Delay (Tt/Tt1/Tt2)|
| | | 0.1…10s| 0.1…10s| 0.1…10s| 0.3…30s| | 0.1…30s| 0.1…30s| | | 0.1…30s| 0.1…30s| 0.1…10s| 0.3…30s| 0.3…30s**
Hysteresis (H)| 2% V

  1. Refer to Table 2 for Response time (Tr). Time Delay (Tt) does not apply to phase loss or phase sequence.
  2. Response Time (Tr) not shown together with Time Delay (Tt).

LED Indication

Off
On
Slow Blink
Fast Blink

Phase Loss & Phase sequence

Only RM22TG20 has 2 relay ouputs

Overvoltage & Undervoltage (>U & <U)

Overvoltage & Undervoltage (>U & <U) /

Absence of Neutral/Phase (N?/N)

Asymmetry

  1. Time delay in progress
  2. End of the preset time delay

Diagnostic

  1. Time delay in progress
  2. End of the preset time delay (adjustable on front panel)

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>