ActronAir CRA130T 2 Piece Fan Coil System Instruction Manual
- July 17, 2024
- ActronAir
Table of Contents
TWO-PIECE FAN COIL STANDARD CYCLING MODELS
3-PHASE MODELS
CRA130T 2 Piece Fan Coil System
The innovative 2 – PIECE fan coil system can provide a solution to difficult
and tight roof space installations. This versatile system comes as separate
fan and coil sections. Each compact and lightweight section is simply
installed in two separate locations and is then joined by flexible ducting.
Ducting is attached to each section by either a 1, 2 or 3 way EASY FIT supply
plenum or a twin spigot duct plate, these can be fitted to either side of each
section.
NOTE: Refer to the Technical Selection Data Catalogue for more detailed
product information such as specifications, fan curves and wiring diagrams.
UNIT FEATURES
- Designed for ease of installation in difficult roof spaces.
- 3-Speed Fan Setting.
- Mounting studs for perforated hanging strap.
- External Condensate Drain Tray.
- Incorporates the EASY FIT supply & return air plenum system.
- Reduce return air noise.
- Integrated Primary and Safety Drain Trays.
- Supplied with Drain Kit & P-Trap (Except Model EAA230S).
MODEL COMBINATION CAPACITY RATINGS AND ELECTRICAL DATA
Outdoor Unit| Indoor Coil Section| Indoor Fan Section| Total Cooling Capacity (kW)| Total Heating Capacity (kW)| Airflow (l/s) (Min / Nom / Max)| RLA
(OD / ID / Total)
| FLA
(OD / ID / Total)
CRA130T| EAA130S| EFA130S| 13.00| 11.85| 590 / 650 / 750| 6.3
/ 4.2 / 10.5| 8.3 / 4.3 / 12.6
CRA150T| EAA150S| EFA150S| 15.27| 14.45| 690 / 770 / 880| 7.1
/ 4.2 / 11.3| 11.7 / 4.3 / 16.0
CRA170T| EAA170S| EFA170S| 17.56| 17.38| 770 / 850 / 900| 8.7
/ 4.1 / 12.8| 12.3 / 4.3 / 16.6
CRA200T| EAA200S| EFA200S| 19.69| 19.27| 900 / 1000 / 1150|
9.0 / 4.5 / 13.5| 13.9 / 5.9 / 19.8
CRA230T| EAA230S| EFA230S| 23.21| 22.88| 1020 / 1200 / 1380|
12.0 / 4.8 / 16.8| 15.9 / 6.4 / 22.3
WEIGHTS AND DIMENSIONS
Coil Section| Weight (kg)| Height (mm)| Depth (mm)|
Width (mm)| Fan Section| Weight (kg)| Height (mm)|
Depth (mm)| Width (mm)
EAA130S| 24| 410| 342| 1054| EFA130S| 31| 408| 362| 1072
EAA150S| 27| 410| 342| 1252| EFA150S| 31| 408| 362| 1072
EAA170S| 29| 410| 342| 1252| EFA170S| 31| 408| 362| 1072
EAA200S| 39| 435| 342| 1360| EFA200S| 41| 433| 412| 1268
EAA230S| 43| 486| 342| 1410| EFA230S| 43| 483| 412| 1269
NOTES:
- Airflow across the coil must be no less than the complete fan sections minimum airflow.
- External static pressure is the same as the standard EVA model fan coil. Refer to the comparable fan curves for each model.
- Refer to installation section for plenum combination options.
- Weights and dimensions are nominal values.
UNIT DIMENSIONS
EFA130S/EFA150S/EFA170S
F FAN SECTION
OVERALL NOMINAL DIMENSION (H X W X D) = 408 X 1072 X 362 SUPPLY DUCT (H X W) = 168 X 708 RETURN DUCT = 378 X 900
MINIMUM SERVICE ACCESS CLEARANCES
UNIT MODEL NUMBER| UNIT WEIGHT
(kg)
---|---
EFA130S / EFA150S / EFA170S| 31
NOTES:
- Do not scale drawing. All dimensions are in mm unless specified. Refer to corresponding unit dimensional drawing for mounting hole details.
- Service Access Areas and Spaces for Airflow Clearances given above are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkaway passages of 1000 mm between the units or between the unit and the outside perimeter is available.
- Minimum Service Access Areas and spaces for Airflow Clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow.
EFA200S
F FAN SECTION
OVERALL NOMINAL DIMENSION (H x W x D) = 433 x 1268 x 412 SUPPLY DUCT (H x W) = 200 x 714 RETURN DUCT (H x W) = 403 x 1095
MINIMUM SERVICE ACCESS CLEARANCES
UNIT MODEL NUMBER | UNIT WEIGHT (kg) |
---|---|
EFA200S | 41 |
NOTES:
- Do not scale drawing. All dimensions are in mm unless specified. Refer to corresponding unit dimensional drawing for mounting hole details.
- Service Access Areas and Spaces for Airflow Clearances given above are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkaway passages of 1000 mm between the units or between the unit and the outside perimeter is available.
- Minimum Service Access Areas and spaces for Airflow Clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow.
EFA230S
F FAN SECTION
OVERALL NOMINAL DIMENSION (H x W x D) = 483 x 1269 x 412 SUPPLY DUCT (H x W) = 200 x 714 RETURN DUCT (H x W) = 453 x 1095
MINIMUM SERVICE ACCESS CLEARANCES
UNIT MODEL NUMBER | UNIT WEIGHT (kg) |
---|---|
EFA200S | 43 |
NOTES:
- Do not scale drawing. All dimensions are in mm unless specified. Refer to corresponding unit dimensional drawing for mounting hole details.
- Service Access Areas and Spaces for Airflow Clearances given are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkway passage of 1000 mm between the units or between the unit and the outside perimeter is available.
- Minimum Service Access Areas and Spaces for Airflow Clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow.
EAA130S
A COIL SECTION
OVERALL NOMINAL DIMENSION (H x W x D) = 410 x 1054 x 342 SUPPLY DUCT (H x W) = 345 x 900 RETURN DUCT = 345 x 900
REAR VIEW – RETURN AIR
MINIMUM SERVICE ACCESS CLEARANCES
TOP VIEW
NOTES:
- Do not scale drawing. All dimensions are in mm unless specified. Refer to corresponding unit dimensional drawing for mounting hole details.
- Service Access Areas and Spaces for Airflow Clearances given are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkway passage of 1000 mm between the units or between the unit and the outside perimeter is available.
- Minimum Service Access Areas and Spaces for Airflow Clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow.
EAA150S / EAA170S
A COIL SECTION
OVERALL NOMINAL DIMENSION (H x W x D) = 410 x 1252 x 342 SUPPLY DUCT (H x W) = 345 x 900 RETURN DUCT = 345 x 900
MINIMUM SERVICE ACCESS CLEARANCES
NOTES:
-
Do not scale drawing. All dimensions are in mm unless specified.
Refer to corresponding unit dimensional drawing for mounting hole details. -
Service Access Areas and Spaces for Airflow Clearances given above are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkaway passages of 1000 mm between the units or between the unit and the outside perimeter is available.
-
Minimum Service Access Areas and spaces for Airflow Clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow.
EAA200S
A COIL SECTION
OVERALL NOMINAL DIMENSION (H x W x D) = 435 x 1360 x 342 SUPPLY DUCT (H x W) = 362 x 1094 RETURN DUCT = 362 x 1094
MINIMUM SERVICE ACCESS CLEARANCES
NOTES:
-
Do not scale drawing. All dimensions are in mm unless specified.
Refer to corresponding unit dimensional drawing for mounting hole details. -
Service Access Areas and Spaces for Airflow Clearances given above are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkaway passages of 1000 mm between the units or between the unit and the outside perimeter is available.
-
Minimum Service Access Areas and spaces for Airflow Clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow.
EAA230S
A COIL SECTION
OVERALL NOMINAL DIMENSION (H x W x D) = 486 x 1410 x 342 SUPPLY DUCT (H x W) = 410 x 1094 RETURN DUCT = 410 x 1094
MINIMUM SERVICE ACCESS CLEARANCES
NOTES:
-
Do not scale drawing. All dimensions are in mm unless specified. Refer to corresponding unit dimensional drawing for mounting hole details.
-
Service Access Areas and Spaces for Airflow Clearances given above are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkaway passages of 1000 mm between the units or between the
unit and the outside perimeter is available. -
Minimum Service Access Areas and spaces for Airflow Clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow.
SUPPLY PLENUM / DUCT PLATE OPTIONS – STD SPLIT FAN COIL
EAA130S-EFA130S EAA150S-EFA150S EAA170S-EFA170S EAA200S-EFA200S EAA230S-
EFA230S
SUPPLY PLENUM / DUCT PLATE OPTIONS – STD SPLIT FAN COIL
EAA130S-EFA130S EAA150S-EFA150S EAA170S-EFA170S EAA200S-EFA200S EAA230S-
EFA230S
ONE WAY SUPPLY PLENUM
TWO WAY SUPPLY PLENUM
THREE WAY SUPPLY PLENUM
TWIN SPIGOT DUCT PLATES
NOTES:
- For air flow purposes, please refer to supply and return air matrix for details of required number of spigots in operation.
- All dimensions are in mm unless specified.
- Do not scale drawing.
ActronAir is constantly seeking ways to improve the design of its products. Therefore, specifications are subject to change without notice, please check prior to purchase. Copyright © 2020 Actron Engineering Pty. Ltd.
9590-0012-11
Ver. 3 240513