Danfoss Type LLS 4000 Liquid Level Switch Installation Guide
- July 15, 2024
- Danfoss
Table of Contents
Type LLS 4000 Liquid Level Switch
“`html
Product Information
Specifications:
-
Product Name: Liquid Level Switch Type LLS 4000 / LLS
4000U -
Device Class: Class A
-
Electrical Connector: M12 male
-
Power Supply: 24 V DC +/- 25%
-
Electrical Supply Relay: 30 V DC 200 mA
-
Recommended Installation: Horizontal
Product Usage Instructions
Installation:
1. Ensure the device is mounted on a metallic tank in an
industrial area.
2. Clean the weld connector for particles before
installation.
3. For LLS 4000, use a torque of 10 Nm/7.4 lb ft pre-tightening
+ 45 degrees clockwise rotation.
4. Make sure to leave the sensor assembled during both
electrical and mechanical installation.
Electrical Connection:
1. Use a straight M12 female connector cable.
2. Connect the cables according to the color code: Red to 1,
Green to 2, White to 3, Black to 4.
3. Fasten the wire approximately 100 mm from the LLS.
LED Indicators:
– Green light LED: Indicates level detection.
– Yellow light LED: Indicates a fault in the LLS 4000/4000U.
– Red light LED: Indicates SIL2 fixed configuration.
FAQ
Q: What is the power supply specification for the product?
A: The power supply required is 24 V DC with a tolerance of +/-
25% and a maximum current of 80 mA.
Q: Can the device be installed vertically or inclined?
A: Vertical or inclined installation is not recommended due to
the risk of gas pockets.
Q: How can I detect faults in the LLS 4000/4000U?
A: Faults can be detected through LED indicators. Connect the
device to a Bluetooth app for detailed fault information.
“`
148R9650
148R9650
Installation guide/Quick start
Liquid Level Switch Type LLS 4000 / LLS 4000U
Warning! This is a Class A device. This device may cause radio interference in
residential areas. In case of interference, the operator may be required to
take appropriate measures. This instrument has to be mounted on a metallic
tank. The device is intended to be used in industrial areas.
M12 male Electrical connector
Electronic part
Info for UK customers only:Danfoss Ltd., 22 Wycombe End, HP9 1NB, GB
: ” ” 04080, 80, / 168,
Fig. 1
Mechanical part
Heat sink (insulation allowed, if media temperature is less than ambient
temperature)
Hexagon 32 mm Process connection G ¾” or ¾” NPT
Liquid sensing part
BSV BSV
SVA SVA
SFA +DSV
SVA
SVA
AKS 4100
SVA
EKE 347
GD
LLG LLS 4000
LLG
LLS 4000
SCA-X
FIA SNV
SNV
SNV
RT 260A
BSV
SVA
SNV SVA
SCA-X FIA
SNV
RT 260A
SNV
SVA
ICF 25-6-5A
REG
SVA
SVA
BSV
SNV
SNV
SVA
QDV 15
Fig. 2 © Danfoss | Climate solutions | 2024.01
AN317523977313en-000404 | 1
LLS 4000 Weld connector G ¾”
LLS 4000U Weld connector NPT ¾”
Note: Horizontal installation Recommended
Weld connector Clean for particles
Fig. 4
Note: Min. 30 mm uninterrupted hole size no reduction
Note: Vertical or inclined installation not recommended: Risk of Gas Pockets
Fig. 3
Always leave the complete sensor assembled, during both electrical and
mechanical installation. Only disassembly electronic and mechanical part, if
necessary at service.
LLS 4000
Alu-gasket
Fig. 5
Torque (LLS 4000 only): 10 Nm/7.4 lb ft pre-tightening + 45 degrees clockwise
rotation
45°
LLS 4000U
G ¾” Teflon (PTFE) tape
Fig. 6 2 | AN317523977313en-000404
NPT ¾”
32 mm Clean joining surfaces
25 mm 1 in min.
45 mm 1.8 in max.
© Danfoss | Climate solutions | 2024.01
Cable with straight M12 female connector. Cables with angled connector is not recommended
1
4
2
3
Black Green – White + Red
Fig. 7
Relay: 30 V DC 200 mA
24 V DC +/- 25%
Securely hand-tighten clockwise until meeting 1 a hard stop
3
2
Note: Fasten the wire approx. 100 mm from the LLS
Fig. 8
© Danfoss | Climate solutions | 2024.01
Color code M12 cable
Red
1
Green
2
White
3
Black
4
Danfoss M12 cables
034G2201, straight M12 cable female x 2 meter 034G2200, straight M12 cable
female x 8 meter Cables not included with LLS 4000/4000U
AN317523977313en-000404 | 3
Red light LED Yellow light LED
Fig. 9
High Level sensor High Level sensor
Level
Green light LED
Open at no Liquid
(Normally Open)*
Closed at no Liquid
(Normally Closed)*
Voltage connected
Green LED
Level detection
LLS 4000/4000U Fault
Yellow LED
Red LED
SIL2 fixed
configuration
Low Level sensor
2)
Low Level sensor
Voltage supply
outside
spec.
LLS 4000/4000U fault**
Green LED ON
Yellow LED ON
Red LED ON
Green LED Flashing. LLS 4000/4000U connected to Bluetooth device
- Configuration dependent. Non-SIL2 fully configurable. SIL2 fixed configuration and only applicable for High Level sensor ** For failure types please connect the device to the Bluetooth App, enter fault state mode, and read the failure type *** Fault can be detected at any detected level, ie. 2 or all 3 lights on
Not recommended in these applications because 1) A High Level Alarm may not be registered at a power failure 2) A Low Level Alarm may not be registered at a power failure
4 | AN317523977313en-000404
© Danfoss | Climate solutions | 2024.01
General specifications
Electrical data
Supply Relay (Solid state)
24 V DC +/-25%, 80 mA Standard power supply of type: SELV (Safety Extra Low
Voltage) with current limit of max. 8A.
Max 30 V DC, 200 mA. Same power supply as to supply can be used. Observe: In
applications with request for SIL2, another separate SELV power supply may be
needed.
Min. cycles: 1.000.000 Default delay between detection and relay switching: PV
(Product Version) All SIL devices, regardless of PV: 1 second All non-SIL,
PV02: 1 second All non-SIL, PV03 or greater: 2 seconds Product Version number
can be found on product label. Actual delay highly influenced by media
viscosity and shall be validated before commissioning.
Mechanical Data
Max. medium viscosity
5000 cP (Un-detection is delayed up to 20 seconds)
Max. working pressure
140 bar (2030 psi)
Ambient temperature range
-40 °C to +65 °C (-40 °F to +149 °F)
Medium temperature range Operating environment
-50 °C to +120 °C (-58 °F to +248 °F). Observe restrictions on saturation temperature for approved medias
Pollution degree 3, altitude 2000 max., outdoor use Relative humidity RH4 to
RH99 % (IEC 60721-3-4: 1995 Class 4K4)
Connection type
G ¾ in. or NPT ¾ in.
Weight
350 g (0.77 lbs.)
Approved media
Media
Saturation temperature range
R717 (Ammonia) -50 °C +105 °C (-58 °F +221 °F)
R22 (HCFC)
-50 °C +86 °C (-58 °F +187 °F)
R507A (HCFC) -50 °C +60 °C (-58 °F +140 °F)
R134a (HFC)
-50 °C +91 °C (-58 °F +196 °F)
Ammonia and listed H(C)FCs and HFOs.
R404A (HFC)
-50 °C +63 °C (-58 °F +145 °F)
Note:
R407A (HFC)
For other medias and mixed medias, please contact Danfoss. R410A (HFC)
-50 °C +72 °C (-58 °F +162 °F) -50 °C +61 °C (-58 °F +142 °F)
R513A (HFC)
-50 °C +83 °C (-58 °F +181 °F)
R1234ze(E) (HFO)* -50 °C +85 °C (-58 °F +185 °F)
PAO (Oil)**
Max 5000 cP and +120 °C (Max 5000 cP and +248 °F)
POE (Oil)**
Max 5000 cP and +120 °C (Max 5000 cP and +248 °F)
Mineral (Oil)** Max 5000 cP and +120 °C (Max 5000 cP and +248 °F)
Approvals
CE: PED, EMC, RED, RoHS, LVD CRN SIL2 FCC IC UA CMIIT ANATEL (1) NBTC (2)
- R1234ze(E) with POE oils (miscible) ** When detecting oils in Ammonia, H(C)FC and HFO systems, the refrigerant gas temperature above the oil must be lower than 80 °C
(1) Este equipamento não tem direito à proteção contra interferência prejudicial e não pode causar interferência em sistemas devidamente autorizados. Para maiores informações, consulte o site da ANATEL www.anatel.gov.br.
(2) . This telecommunication equipment conforms to the technical standards or requirements of NBTC.
© Danfoss | Climate solutions | 2024.01
AN317523977313en-000404 | 5
M12x1
M12x1
2.8
71,3
Fig. 10
142,4
1 5
2 0
2
36
H32 34
G3/4
19,5 LLS 4000 (mm)
5.6
0.6 0.78
1.4
H32 3/4 NPT
0.77 LLS 4000U (in)
6 | AN317523977313en-000404
© Danfoss | Climate solutions | 2024.01
LLS Bluetooth app download
1
2
Search LDLaSn4f0o0s0s
Configuration
11
3
dow nl oad
LLS 4000 AB C DEFGHIJ K L
Observe!
4
Always download or update to latest App version.
Devices with Firmware PV01 (see product label) must be
Firmware updated to latest firmware before configuration.
Please contact Danfoss.
2
3
4
5
6
Pin code: 0000 7©|DAaNn3fo17ss52| 3C9li7m7a3t1e3esonl-u0t0io0n4s0|42024.01
} Configurable
AN317523977313en-000404 | 7
Configuration continued
7
8
Password: 12131400*
- In Service menu a unique password for Service menu can be entered. Go to menu upper right -> Go login -> Go to settings -> Go to Service Password -> Enter new Service Password
Note: For commissioning, service and proof testing see LLS 4000/4000U Safety Manual
Read and apply safety instructions contained in product documentation.
Direct current.
General warnings/precautions
– Every use that is not described in this guide is considered incorrect and is
not authorized by the manufacturer. – The LLS device should only be used with
approved media listed under General specifications. Use with other medias must
be
validated by Danfoss before installation. – Verify that the installation and
operating conditions of the device respects those specified in this guide,
especially concerning
the supply voltage and environmental conditions. – All service and maintenance
operations must be performed by qualified personnel. – Installation must
comply with local standards and legislation. – Before carrying out any
maintenance operations on the device, disconnect the device from the main
power supply. – Before unscrewing the LLS device from the pipe or tank ensure
that pipe or tank is empty and not under pressure. – Liability for injury or
damage caused by incorrect use of the device lies solely with the user. –
Depending on the application, the metallic part of the instrument may be hot
or cold. – If media detection or non-detection by the level switch could
generate a hazard the SIL version and specific instructions described
in the safety manual (periodic proof test) should be used. The SIL safety
manual can be downloaded from Danfoss web site or by scanning the QR code
below.
For further documents (Data sheet, SIL2 safety manual etc.) scan this QR code: