TRANE DXHK Series Water Source Heat Pump Instruction Manual

July 15, 2024
Trane

TRANE DXHK Series Water Source Heat Pump

Specifications

  • Model Numbers: DXHK 024-070 – 60 Hz, DXVK 024-070 – 60 Hz, EXHK 009-070 – 60 Hz, EXVK 009-070 – 60 Hz
  • Refrigerant: R-454B (A2L)
  • Installation: Horizontal/Vertical
  • Power Supply: 60 Hz

Product Information

The Water Source Heat Pump AxiomTM is a versatile system designed for heating, ventilating, and air-conditioning applications. It comes in horizontal and vertical configurations to suit different installation needs. The system uses R-454B refrigerant, which is flammable (A2L), requiring specific handling and equipment for safe operation.

Installation:

  1. Ensure only qualified personnel handle the installation.
  2. Follow all safety warnings and precautions provided in the manual.
  3. Properly connect the system’s grounding terminal(s).

Operation:

  1. Read the manual thoroughly before operating the unit.
  2. Observe all safety advisories and precautions.
  3. Ensure proper field wiring and grounding as per NEC codes.

Maintenance:

  1. Regularly inspect the system for any signs of damage or wear.
  2. Perform routine maintenance tasks as outlined in the manual.
  3. Only service the equipment if qualified to do so.

FAQs

  • Q: Can unqualified individuals service the equipment?
    • A: No, only qualified personnel should install and service the equipment to avoid hazards and ensure proper operation.
  • Q: What refrigerant does the system use?
    • A: The system uses R-454B refrigerant, which is flammable (A2L), requiring specific handling and equipment for safe operation.
  • Q: What precautions should be taken for field wiring?
    • A: All field wiring must be performed by qualified personnel to avoid hazards like fire and electrocution. Proper installation and grounding are essential as per NEC and electrical codes.

Installation, Operation, and Maintenance
Water Source Heat Pump AxiomTM Horizontal/Vertical — EXH/EXV, DXH/DXV
0.75 to 6 Tons ­ 60 Hz, High Efficiency and TwoStage High Efficiency

Model Numbers: DXHK 024-070 – 60 Hz DXVK 024-070 – 60 Hz EXHK 009-070 – 60 Hz EXVK 009-070 – 60 Hz
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air- conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

April 2024

WSHP-SVX019A-EN

Introduction

Read this manual thoroughly before operating or servicing this unit.

Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION NOTICE

Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
· Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/ sleeves, butyl gloves, safety glasses, hard hat/ bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
· When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
· If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

©2024 Trane

WSHP-SVX019A-EN

WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
· All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
· Non-Trane personnel should always follow local regulations.
WARNING
R-454B Flammable A2L Refrigerant!
Failure to use proper equipment or components as described below could result in equipment failure, and possibly fire, which could result in death, serious injury, or equipment damage. The equipment described in this manual uses R-454B refrigerant which is flammable (A2L). Use ONLY R454B rated service equipment and components. For specific handling concerns with R-454B, contact your local representative.

Introduction
WARNING
Electrical Shock Hazard!
Failure to follow instructions below could result in death or serious injury. Properly connect the system’s oversized protective earthing (grounding) terminal(s).
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Product Safety Information
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
Maximum altitude of use 3000 meters.
This appliance incorporates an earth connection for functional purposes only.

Model Number Description

EXVH/DXVH Models

Digits 1­3 — Unit Configuration

Digit 13 — Freeze Protection2

Digit 23 — Unit Mounted Disconnect

EXV = High Efficiency Vertical DXV = Two-stage High Efficiency Vertical EXH = High Efficiency Horizontal DXH = Two-stage High Efficiency Horizontal
Digit 4 — Development Sequence
K = R-454B
Digits 5­7 — Nominal Size (MBH)
009 = 9.0 MBH (EX only) 012 = 12.0 MBH (EX only) 015 = 15.0 MBH (EX only) 018 = 18.0 MBH (EX only) 024 = 24.0 MBH 030 = 30.0 MBH (EX only) 036 = 36.0 MBH 042 = 42.0 MBH (EX only) 048 = 48.0 MBH 060 = 60.0 MBH 070 = 70.0 MBH
Digit 8 — Voltage (Volts/Hz/Phase)
4 = 460/60/3 7 = 265/60/1 A = 208-230/60/1 B = 208-230/60/3
Digit 9 — Heat Exchanger
1 = Copper-Water Coil 2 = Cupro-Nickel Water Coil 7 = Insulated Copper-Water Coil/Suction Line 8 = Insulated Cupro-Nickel Water Coil/Suction Line
Digit 10 — Design Sequence
A = First Design Sequence
Digit 11 — Refrigeration Circuit
0 = Heating and Cooling Circuit 2 = Heating and Cooling Circuit with Hot Gas Reheat 3 = Heating and Cooling Circuit with Waterside Economizer 4 = Heating and Cooling Circuit with Waterside Economizer, Hot Gas Reheat
Digit 12 — Blower Configuration
K = Variable ECM Motor, Constant Torque

A = 20°F Freezestat (For Glycol Loop) B = 35°F Freezestat (For Water Loop)
Digit 14 — Open Digit = 0
Digit 15 — Supply-Air Arrangement
T = Top Supply-Air Arrangement B = Back Supply-Air Arrangement L = Left Supply-Air Arrangement R = Right Supply-Air Arrangement
Digit 16 — Return-Air Arrangement
L = Left Return-Air Arrangement R = Right Return-Air Arrangement
Digit 17 — Control Types
D = Deluxe 24V Controls H = SymbioTM 400-B J = Symbio 400-B w/Air-Fi® Wireless Communications
Digit 18 — Tstat/Sensor Location
0 = Wall Mounted Location
Digit 19 — Fault Sensors
1 = Condensate Overflow Sensor 3 = Condensate Overflow and Filter Maintenance Timer 6 = Condensate Overflow and Fan Status J = Fan Status, Filter Maintenance Timer and Condensate Overflow Sensor
Digit 20 — Temperature Sensor
0 = No Additional Temperature Sensor 1 = Entering Water Sensor
Digit 21 — Insulation 1 = Matte Faced Insulation 2 = Foil Faced Insulation
Digit 22 — Electric Heat 0 = No Electric Heat 6 = Field Mounted External Boilerless LOW Electric Heat 7 = Field Mounted External Boilerless MED Electric Heat 8 = Field Mounted External Boilerless HIGH Electric Heat 9 = Boilerless Electric Heat Ready

0 = No Unit Mounted Disconnect 2 = Unit Mounted Disconnect
Digit 24 — Filter Type
1 = 1-inch Throwaway Filter 2 = 2-inch Throwaway Filter 4 = 2-inch MERV 8 5 = 2-inch MERV 13
Digit 25 — Acoustic Arrangement
1 = Standard Sound Attenuation 2 = Deluxe Sound Attenuation
Digits 26­36 — Does Not Apply
00000000000 = Digits 26-36 are not applicable to the EXV or DXV products
Digit 37 — Ducted Filter Rack
0 = Non-ducted filter rack A = Ducted Filter Rack Side Access/LH-RH C = Ducted Filter Rack (Bottom Access)
Digit 38 — Isolation Valve
0 = No Isolation Valve 1 = Factory Mounted Isolation Valve
Digit 39 — Power Connection
1 = Single Point 2 = Electric Heat Power Separate from Unit
Digit 40 — Drain Pan
A = Polymer Drain Pan B = Stainless Steel Drain Pan
Model Number Note: Notes:
1. Deluxe Sound option to be made available in later product release.
2. 20°F Freezestat is typically used in a geothermal application. 35°F Freezestat is typically used in a boiler/tower application

6

WSHP-SVX019A-EN

Overview of Manual
Note: One copy of this document ships inside the control panel of each unit and is customer property. It must be retained by the unit’s maintenance personnel.
This booklet describes proper installation, operation, and maintenance procedures for air cooled systems.
By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual.
Should equipment failure occur, contact a qualified service organization with qualified, experienced technicians to properly diagnose and repair this equipment.
Unit Nameplate
The unit nameplate is located on the outside of the control box access panel at the front of the unit. It includes the unit

model number, serial number, electrical characteristics, refrigerant charge, and other pertinent unit data.
Compressor Nameplate
The nameplate for the compressors are located on the compressor shell.
Model Number Description
All products are identified by a multiple-character model number that precisely identifies a particular type of unit. Its use will enable the owner/operator, installing contractors, and service engineers to define the operation, specific components, and other options for any specific unit.
When ordering replacement parts or requesting service, be sure to refer to the specific model number and serial number printed on the unit nameplate.

WSHP-SVX019A-EN

7

General Information

Unit Description
Before shipment, each unit is leak tested, dehydrated, charged with refrigerant, and run tested for proper control operation.

Air-to-Refrigerant Coil
The air-to-refrigerant coil is aluminum fin, mechanically bonded to the copper tubing.

Water-to-Refrigerant Coil
The water-to-refrigerant coil is a copper or cupro-nickel (option) and steel tube (tube-within-a-tube) design, leak tested to confirm there is no cross leakage between the water tube (copper/cupro-nickel) and refrigerant gas (steel tube).

Table 1. High/low pressure switch

Trip

Recover

Unit

LP

40 +/-4

56 +/-4

psig

HP

600 +/-10

550 +/-10

psig

Additives like glycol can be added to reduce the freezing point of the water. Units are not intended to be connected to sanitary water.
· Entering water temperatures range from 25°F to 120°F.
· Leaving water temperature deltas range from 10°F to 15°F.
· Maximum water pressure allowed in system is 400 psi.
Controls
The available control type is a Deluxe 24V control option, a SymbioTM 400-B control option for all unit sizes.
All power wiring to the equipment is made at the unit’s compressor contactor or optional disconnect switch for the EXH/V 0.75 to 6 ton units and the DXH/V 2 to 6 ton units. For units without the disconnect switch, the power wiring needs to be connected to the screw terminals of the compressor contactor. All low-voltage wiring is made at the unit’s low voltage terminal plug.
System Input Devices and Functions
A thermostat, zone sensor, or building automation system is required to operate the water-source heat pump. The flexibility of having several mode capabilities depends upon the type of sensor and/or remote panel selected.
Troubleshooting and connection diagrams for the 24V control systems may be located in the back of this manual. All digital control troubleshooting tips and connection
8

diagrams are located in SymbioTM 400­B/500 Programmable Controllers Water Source Heat Pump (WSHP) Installation, Operation, and Maintenance guide (BAS- SVX092-EN).
Deluxe 24V Controls (option)
Units containing the Deluxe 24V control design will incorporate a microprocessor-based control board. The Trane microprocessor board is factory wired to a terminal plug to provide all necessary terminals for field connection. The deluxe board is equipped with a random start relay, anti-short cycle timer, brown out protection, compressor disable, condensate overflow, unit safety control, diagnostics, and a generic relay (which may be available for field use).
SymbioTM 400-B (option)
The Symbio 400-B is a BTL Listed BACnet® controller that can operate stand- alone or within a Building Automation System (BAS) such as Tracer® SC+. For installation, operation, and maintenance, see SymbioTM 400­B/500 Programmable Controllers Water Source Heat Pump (WSHP) Installation, Operation, and Maintenance guide (BAS-SVX092
-EN).
Pump Module (Field Installed Accessory)
The pump module consists of either a single or dual 1/6 HP cast iron pump and a brass three-way shut-off valve. The pump module kits contains the necessary components for the installation, operation, and maintenance of the water circuit of a closed-loop distributed pumping application.
Waterside Economizer (Option)
Instructions for mechanical connection of the waterside economizer to the water-source heat pump may be found in the dimensional section of this manual.
The waterside economizer is designed to begin economizing mode when water temperatures fall below the field adjustable temperature of 25, 35, 45, 55 or 60°F (for the Deluxe control option), or below the programmed setpoint (for the SymbioTM 400-B control option).
When the temperature is less than the setpoint, fluid will flow into the economizing coil, while simultaneously halting mechanical operation of the compressor. Mechanical cooling will continue on a call for a second stage from the thermostat or system control. Entering water temperature sensor is factory provided for field installation on the entering water side of the coil.
WSHP-SVX019A-EN

Boilerless Control/Electric Heat (Option)
This option targets building designs that do not incorporate a boiler to heat the loop system. During a heavy heating load, the loop temperature may begin to fall. As the loop temperature decreases, the heating capacity of the heat pump also decreases. In the heating mode, when the loop temperature falls below 55°F (factory setting), the electric heater is energized, and the compressor is locked out. The system’s electric heat source is utilized for primary heating until the loop temperature rises above 60°F. Once the loop temperature rises above 60°F, the boilerless controller returns the unit to normal compressor heating operation and locks out the electric heater.
The electric heat must be field installed by the contractor.
Note: The boilerless controller has a field adjustable entering water temperature setting of 25, 35, 45, 55, and 60 degrees. The compressor operation will return to normal operation when the loop temperature rises 5 degrees above the setpoint. This electric heat option is designed for primary heat only, not to run as supplemental heat to the heating function of the heat pump.

Table 2. Refrigerant charge (EXH/EXV)

Model (60 Hz)
EXH/V009 EXH/V012 EXH/V015

Heat Pump (oz)/Kg)

Circuit 1 33.5/0.94 32.5/0.92 33.5/0.94

Circuit 2 — — —

Heat Pump w/ HGR (oz)/ Kg)

Circuit 1 Circuit 2

35.0 / 0.99

34.0 / 0.96

35.5/1.00

General Information

Table 2. Refrigerant charge (EXH/EXV) (continued)

Model (60 Hz)
EXH/V018 EXH/V024 EXH/V030 EXH/V036 EXH/V042 EXH/V048 EXH/V060 EXH/V070

Heat Pump (oz)/Kg)

Circuit 1 45.5/1.28 48.0/1.36 57.5/1.63 59.5/1.68 72.0/2.04 74.0/2.09 84.0/2.38 100.0/2.83

Circuit 2 — — — — — — — —

Heat Pump w/ HGR (oz)/ Kg)

Circuit 1 Circuit 2

47.5/1.34

50.0/1.41

60.5/1.71

62.0/1.75

76.0/2.15

78.0/2.21

89.0/2.52

105.0/2.97

Table 3. Refrigerant charge (DXH/DXV)

Model (60 Hz)
DXH/ V024
DXH/ V036
DXH/ V048
DXH/ V060
DXH/ V070

Heat Pump (oz)/Kg) Circuit 1 Circuit 2

50.0/1.41

56.5/1.60

73.0/2.06

86.5/2.45

100.0/2.83

Heat Pump w/ HGR (oz)/ Kg)
Circuit 1 Circuit 2

52.0/1.47

59.5/1.68

77.0/2.18

92.0/2.60

105.0/2.97

WSHP-SVX019A-EN

9

Pre-Installation

WARNING
Fiberglass Wool!
Exposure to glass wool fibers without all necessary PPE equipment could result in cancer, respiratory, skin or eye irritation, which could result in death or serious injury. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. You MUST wear all necessary Personal Protective Equipment (PPE) including gloves, eye protection, a NIOSH approved dust/mist respirator, long sleeves and pants when working with products containing fiberglass wool.
Precautionary Measures: · Avoid breathing fiberglass dust. · Use a NIOSH approved dust/mist respirator. · Avoid contact with the skin or eyes. Wear long-
sleeved, loose-fitting clothing, gloves, and eye protection. · Wash clothes separately from other clothing; rinse washer thoroughly. · Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respirator.
First Aid Measures: · Eye Contact – Flush eyes with water to remove
dust. If symptoms persist, seek medical attention. · Skin Contact – Wash affected areas gently with soap and warm water after handling.
Unit Inspection Checklist
Note: The packaging for these units are tested per, and compliant with, the requirements of NMFC Item 180 Certified Packaged Products.
· Unpack all components of the kit. · Check carefully for any shipping damage. If any
damage is found it must be reported immediately and a claim made against the transportation company. Important: Equipment is shipped FOB (Free on Board)
at the manufacturer. Therefore, freight claims for damages against the carrier must be initiated by the receiver.
10

· Visually inspect the components for shipping damage as soon as possible after delivery, before it is stored. Concealed damage must be reported within 15 days.
· If concealed damage is discovered, stop unpacking the shipment.
· Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
· Notify the carrier’s terminal of damage immediately by phone and by mail. Request an immediate joint inspection of the damage by the carrier and the consignee.
· Do not attempt to repair any damaged parts until the parts are inspected by the carrier’s representative.
Jobsite Inspection Checklist
Always perform the following checks before accepting a unit:
· Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
· Verify that the power supply complies with the unit nameplate specifications.
· Visually inspect the exterior of the unit, for signs of shipping damage. Do not sign the bill of lading accepting the unit(s) until inspection has been completed. Check for damage promptly after the unit(s) are unloaded. Once the bill of lading is signed at the jobsite, the unit(s) are now the property of the SOLD TO party and future freight claims MAY NOT be accepted by the freight company.
Jobsite Storage
NOTICE
Microbial Growth!
Failure to follow instructions below could result in odors and damage to the equipment and building materials. The floor or foundation must be level and the condensate drain at the proper height for proper drainage and condensate flow. Standing water and wet surfaces inside the equipment can become an amplification site for microbial growth (mold). If there is evidence of microbial growth on the interior insulation, it should be removed and replaced prior to operating the system.
This unit is intended for indoor use only. To protect the unit from damage due to the elements, and to prevent possible IAQ contaminant sources from growing, the unit should be stored indoors. If indoor storage is not possible, the following provisions for outdoor storage must be met:
WSHP-SVX019A-EN

· Place the unit(s) on a dry surface or raise above the ground to assure adequate air circulation beneath the unit.
· Cover the unit(s) with a water proof tarp to protect them from the elements.
· Make provisions for continuous venting of the covered units to prevent moisture from standing on the unit(s) surfaces. Wet interior unit insulation can become an

Pre-Installation
amplification site for microbial growth (mold) which has been determined to be a cause of odors and serious health related indoor air quality problems.
· Store units in the normal UP orientation to maintain oil in the compressor.
· Stack horizontal units no more than three units high. Do not stack the vertical unit configurations.

WSHP-SVX019A-EN

11

Unit Dimensions

Service Clearances
Per NEC requirements, 36 inches of access and working space is provided and maintained around all control boxes and electrical equipment to permit ready and safe
Figure 1. Clearances – EXH/DXH 0.75 to 6 tons

14″

14″

LEFT RETURN BACK SUPPLY

LEFT RETURN RIGHT SUPPLY

14″

14″

14″

14″

UNIT FRONT 36″
14″
RIGHT RETURN BACK SUPPLY

UNIT FRONT 36″
14″
RIGHT RETURN LEFT SUPPLY

operation and maintenance of such equipment. Local codes may require more clearance to electrical equipment. Check all code requirements prior to unit installation.

A minimum 14­inch clearance for servicing the unit is required for all EXH 0.75 to 6 tons configurations from other mechanical and electrical equipment (where shown) to enable panel removal from the unit for service/maintenance ability. The optimum clearance required is 20 inches.

Notes: ·

Return air direction (left-hand or right hand) is NOT field convertible. Units must be ordered with correct return air side.

· For horizontal models, confirm enough clearance between the condensate drain and the ceiling for pitching of the condensate line. See Figure 20, p. 37 for pitching requirements.

14″

14″

14″

14″

UNIT FRONT 36″

UNIT FRONT 36″

12

WSHP-SVX019A-EN

1″ 1″

Figure 2. Clearance ­ EXVK/DXVK 0.75 to 6 tons

24″

1″

RI GHT RETURN TOP/ BACK SUPPLY

UNI T FRONT 36″

24″

1″

UNI T FRONT 36″

LEFT RETURN TOP/ BACK SUPPLY

Unit Dimensions
A 24­inch clearance from other mechanical and electrical equipment (where shown) is recommended for most unit configurations. This will enable panel removal from the unit for service/maintenance. The 24­inch side clearance on EXVK/DXVK 0.75 to 6T models is for optimal access only. Side clearance is not a requirement as most components can be accessed from the front of the unit. A 1­inch minimum clearance between the filter rack and any obstacle is required for units in a free return application to provide proper air flow to the air- to-refrigerant coil. A 12­inch minimum clearance between the filter rack and any obstacle should be provided to properly attached ductwork. The 1­inch dimension shown in the back of the unit represents the supply duct collar for the back supply option. This clearance is needed to clear these flanges.

WSHP-SVX019A-EN

13

Unit Dimensions

Unit Dimensions
Figure 3. Left return/back supply (EXHK/DXHK)
N Dimensional data left return/back supply

TOP B M

BACK

E

D

H

D J
F 1.36 DRAIN

C NOMINAL

BB

FILTER SIZE

CC

NOMINAL FILTER SIZE LEFT SIDE
RIGHT SIDE

A L

BB AA
1.04

FRONT

HI VOLT
DISCONNECT SWITCH LOCATION

WO

K

CC

CC WCI MOUNTING

11.62

LOCATION

AA

2.56

BB LOW VOLT

WI 3.30

AA CC

Table 4. Dimensional data left return/back supply (EXHK/DXHK)

Cab

Unit

Width

Depth Height

Duct Collar

Duct Collar Location

EXHK DXHK A

B

C

D

E

F

Blower Opening

H

J

Hi Volt
K

Unit hanging location

L

M

N

Nominal Filter Size

W.I. NPTI

W.O. DRAIN NPTI NPTI

B 009, 012 ­ 25.50 46.00 17.75 13.50 3.50 2.00 10.13 9.38 15.00 23.50 19.88 23.00 16 x 19 0.50 0.50 0.75

C

015

­ 25.50 49.00 18.75 13.50 3.88 2.25 10.50 11.25 16.00 23.50 21.38 24.50 17 x 20 0.75 0.75 0.75

D 018, 024 024 25.50 55.00 19.75 13.50 3.50 2.25 11.75 11.25 17.00 23.50 24.38 27.50 18 x 23 0.75 0.75 0.75

E 030,036 036 28.00 68.00 21.75 16.50 3.63 2.13 13.88 13.50 19.00 26.00 30.88 34.00 20 x 30 1.00 1.00 0.75

F

042, 048 048

29.38 77.75 22.13 16.50 3.50

2.50

13.88 13.50 19.25 27.25 30.88 43.75

20 x 20 (x2)

1.00

1.00

0.75

G

060, 070 060,070 29.38 86.75 22.13 16.50 3.50

2.50

13.88

13.50

19.25

27.25

30.88

52.75

20 x 20, 20 x 30

1.00

1.00

0.75

Note: Dimensions represent unit hanging dimensions including base rails for hanging.

14

WSHP-SVX019A-EN

Figure 4. Left return/right supply (EXHK/DXHK)

Dimensional data left return/right supply

TOP

B

N

M

Unit Dimensions

A L

BACK
NOMINAL FILTER SIZE C
BB CC
1.36 DRAIN

NOMINAL FILTER SIZE LEFT SIDE

BB AA
1.04

CC AA

RIGHT SIDE

D H

E

FRONT

K 2.56

HI VOLT
DICONNECT SWITCH LOCATION

WO

CC WCI MOUNTING

LOCATION

BB

WI

LOW VOLT

11.62 3.30

J D
AA CC
F

Table 5. Dimensional data left return/right supply (EXHK/DXHK)

Cab

Unit

Width

Depth

Height

Duct Collar

Duct Collar Location

Blower Opening

EXHK DXHK A

B

C

D

E

F

H

J

Hi Volt
K

Unit hanging location
LMN

Nominal Filter Size

W.I. NPTI

W.O. DRAIN NPTI NPTI

B 009, 012

­

25.50 46.00 17.75 13.50 3.38 3.00 10.13 9.38 15.00 23.50 19.88 23.00 16 x 19 0.50 0.50 0.75

C

015

­ 25.50 49.00 18.75 13.50 5.88 4.00 10.50 11.25 16.00 23.50 21.38 24.50 17 x 20 0.75 0.75 0.75

D 018, 024 024 25.50 55.00 19.75 13.50 5.63 4.75 11.75 11.25 17.00 23.50 24.38 27.50 18 x 23 0.75 0.75 0.75

E 030,036 036 28.00 68.00 21.75 16.50 5.63 3.88 13.88 13.50 19.00 26.00 30.88 34.00 20 x 30 1.00 1.00 0.75

F

042, 048

048

29.38 77.75

22.13

16.50

5.63

3.75 13.88 13.50 19.25 27.25 30.88 43.75

20 x 20 (x2)

1.00

G

060, 070 060,070 29.38 86.75

22.13

16.50

5.63

3.75

13.88 13.50

19.25

27.25

30.88

52.75

20 x 20, 20 x 30

1.00

Note: Dimensions represent unit hanging dimensions including base rails for hanging.

1.00 1.00

0.75 0.75

WSHP-SVX019A-EN

15

Unit Dimensions

Figure 5. Right return/left supply (EXHK/DXHK)

TOP

B

Dimensional data right return/left supply

N

M

NOMINAL FILTER SIZE

1.56

NOMINAL FILTER SIZE

BACK

E

D

H

C
BB CC

D J

DRAIN 1.36

F

LEFT SIDE RIGHT SIDE

A L

BB AA
1.04

FRONT

HI VOLT
DISCONNECT SWITCH LOCATION

WO

K
CC

CC WCI MOUNTING

AA

LOCATION BB

WI

2.56

LOW VOLT

11.62 3.30

AA CC

Table 6. Dimensional data right return/left supply (EXHK/DXHK)

Cab

Unit

Width

Depth

Height

Duct Collar

Duct Collar Location

Blower Opening

Hi Volt

EXHK DXHK A

B

C

D

EFH J

K

Unit hanging location

L

M

N

Nominal Filter Size

W.I. NPTI

W.O. DRAIN NPTI NPTI

B 009, 012

­

25.50 46.00 17.75 13.50 5.50 2.00 10.13 9.38 15.00 23.50 19.88 23.00 16 x 19 0.50 0.50 0.75

C

015

­ 25.50 49.00 18.75 13.50 5.88 2.25 10.50 11.25 16.00 23.50 21.38 24.50 17 x 20 0.75 0.75 0.75

D 018, 024 024 25.50 55.00 19.75 13.50 5.63 2.25 11.75 11.25 17.00 23.50 24.38 27.50 18 x 23 0.75 0.75 0.75

E 030,036 036 28.00 68.00 21.75 16.50 5.63 2.13 13.88 13.50 19.00 26.00 30.88 34.00 20 x 30 1.00 1.00 0.75

F 042, 048 048 29.38 77.75 22.13 16.50 5.63 2.50 13.88 13.50 19.25 G 060, 070 060,070 29.38 86.75 22.13 16.50 5.63 2.50 13.88 13.50 19.25 Note: Dimensions represent unit hanging dimensions including base rails for hanging.

27.25 27.25

30.88 30.88

43.75 52.75

20 x 20 (x2)
20 x 20, 20 x 30

1.00 1.00

1.00 1.00

0.75 0.75

16

WSHP-SVX019A-EN

Figure 6. Right return/back supply (EXHK/DXHK)

Dimensional data right return/back supply

TOP B

N

M

NOMINAL FILTER SIZE

NOMINAL FILTER SIZE

BACK

D

E

H

BB CC
DRAIN

J D C
F 1.36

LEFT SIDE RIGHT SIDE

Unit Dimensions

A L

BB AA
1.04

FRONT

HI VOLT
DISCONNECT SWITCH LOCATION

WO

K

CC

CC WCI

MOUNTING

LOCATION

AA

BB

WI

2.56

LOW VOLT

11.62 3.30

AA CC

Table 7. Dimensional data right return/back supply (EXHK/DXHK)

Cab

Unit

Width

Depth

Height

Duct Collar

Duct Collar Location

Blower Opening

EXHK DXHK A

B

C

D EFH J

Hi Volt
K

Unit hanging location
LMN

Nominal Filter Size

W.I. NPTI

W.O. DRAIN NPTI NPTI

B 009, 012 ­ 25.50 46.00 17.75 13.50 3.25 3.00 10.13 9.38 15.00 23.50 19.88 23.00 16 x 19 0.50 0.50 0.75

C

015

­ 25.50 49.00 18.75 13.50 3.88 4.00 10.50 11.25 16.00 23.50 21.38 24.50 17 x 20 0.75 0.75 0.75

D 018, 024 024 25.50 55.00 19.75 13.50 3.50 4.75 11.75 11.25 17.00 23.50 24.38 27.50 18 x 23 0.75 0.75 0.75

E 030,036 036 28.00 68.00 21.75 16.50 3.63 3.88 13.88 13.50 19.00 26.00 30.88 34.00 20 x 30 1.00 1.00

F

042, 048

048

29.38 77.75

22.13

16.50 3.50

2.50 13.88 13.50 19.25 27.25 30.88 43.75

20 x 20 (x2)

1.00

G

060, 070 060,070 29.38 86.75

22.13

16.50

3.50

3.75

13.88

13.50

19.25

27.25

30.88

52.75

20 x 20, 20 x 30

1.00

Note: Units in a free return application will require more than a 1 in. clearance to provide proper airflow to the unit’s air-to-refrigerant coil.

1.00 1.00

0.75 0.75 0.75

WSHP-SVX019A-EN

17

Unit Dimensions
Figure 7. Left return/top supply (EXVK/DXVK)
TOP

D

F

J

NOMINAL

FILTER

D

SIZE

H

E

LEFT SIDE

FRONT

RIGHT SIDE

NOMINAL FILTER SIZE

C

HI VOLT

DISCONNECT SWITCH LOCATION
WO

K 1.75

WCI MOUNTING LOCATION
LOW VOLT

DRAIN WI

11.0 8.0 2.5

B

A

Table 8. Dimensional data left return/top supply (EXVK/DXVK)

Cab

Unit

Width

Depth

Height

Duct Collar

Duct Collar Location

EXVK DXVK A

B

C

D

E

F

G

Blower Opening

H

J

Hi Volt
K

Nominal Filter Size

W.I. NPTI

W.O. NPTI

Drain NPTI

B 009, 012

­

21.50 21.50 34.00 13.25 4.00 1.00 3.50 10.50 9.60 14.25 16 x 19 0.50 0.50 0.75

C

015

­

21.50 23.00 36.00 13.25 4.75 0.63 3.50 10.50 11.30 15.25 17 x 20 0.75 0.75 0.75

D 018, 024 024 21.50 26.00 38.00 13.25 6.25 0.63 3.50 11.80 11.30 16.25 18 x 23 0.75 0.75 0.75

E 030,036 036 24.00 32.50 42.00 16.50 7.25 0.75 3.50 13.70 13.50 18.25 20 x 30 1

1 0.75

F 042, 048 048 25.40 32.50 49.00 16.50 7.25 0.75 3.50 13.70 13.50 18.25 27 x 30 1

1 0.75

G 060, 070 060,070 25.40 32.50 55.00 16.50 7.25 0.75 3.50 13.70 13.50 18.25 30 x 33 1 Note: Units in a free return application will require more than a 1 in. clearance to provide proper airflow to the unit’s air-to-refrigerant coil.

1 0.75

18

WSHP-SVX019A-EN

Figure 8. Right return/top supply (EXVK/DXVK)

G

D

TOP J

DH E

NOMINAL FILTER SIZE

Unit Dimensions

LEFT SIDE

FRONT

RIGHT SIDE

NOMINAL FILTER SIZE

C

HI VOLT

DISCONNECT

SWITCH

LOCATION

WO

K 1.75

WCI MOUNTING LOCATION
LOW VOLT

DRAIN WI

11.0 8.0 2.5

B

A

Table 9. Dimensional data right return/top supply (EXVK/DXVK)

Cab

Unit

Width

Depth

Height

Duct Collar

Duct Collar Location

EXVK DXVK A

B

C

D

E

F

G

Blower

Opening

H

J

Hi Volt

Nominal Filter

K

Size

W.I. NPTI

W.O. NPTI

Drain NPTI

B 009, 012

­

21.50 21.50 34.00 13.25 4.00 1.00 3.50 10.50 9.60 14.25 16 x 19 0.50 0.50 0.75

C

015

­

21.50 23.00 36.00 13.25 4.75 0.63 3.50 10.50 11.30 15.25 17 x 20 0.75 0.75 0.75

D 018, 024 024 21.50 26.00 38.00 13.25 6.25 0.63 3.50 11.80 11.30 16.25 18 x 23 0.75 0.75 0.75

E 030,036 036 24.00 32.50 42.00 16.50 7.25 0.75 3.50 13.70 13.50 18.25 20 x 30 1

1 0.75

F 042, 048 048 25.40 32.50 49.00 16.50 7.25 0.75 3.50 13.70 13.50 18.25 27 x 30 1

1 0.75

G 060, 070 060,070 25.40 32.50 55.00 16.50 7.25 0.75 3.50 13.70 13.50 18.25 30 x 33 1

1 0.75

Note: Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit’s air-to-refrigerant coil.

WSHP-SVX019A-EN

19

Unit Dimensions

Figure 9. Left return/back supply (EXVK/DXVK)

Dimensional data left return/back supply

TOP B

A

E F
D J

BACK
D H

NOMINAL FILTER SIZE

NOMINAL FILTER SIZE LEFT SIDE

C

RIGHT SIDE

FRONT

HI VOLT

DISCONNECT

SWITCH

LOCATION

WO

K

DRAIN

WI

1.81

LOW VOLT

10.87 8.00
2.55

Table 10. Dimensional data left return/back supply (EXVK/DXVK)

Cab

Unit

EXVK DXVK

B 009, 012 ­

Width A
21.50

Depth B
21.50

Height C
34.00

Duct Collar
D
13.50

Duct Collar

Location

E

F

3.50 2.00

Blower Opening

Hi Volt

Nominal Filter

H

J

K

Size

10.13 9.38 14.25 16 x 19

W.I. NPTI
0.50

C

015

­

21.50 23.00 36.00 13.50 3.88 2.25 10.50 11.25 15.25 17 x 20 0.75

D 018, 024 024 21.50 26.00 38.00 13.50 3.50 2.75 11.75 11.25 16.25 18 x 23 0.75

E 030,036 036 24.00 32.50 42.00 16.50 3.63 2.13 13.88 13.50 18.25 20 x 30

1

F 042, 048 048 25.40 32.50 49.00 16.50 3.50 2.50 13.88 13.50 18.25 27 x 30

1

G 060, 070 060,070 25.40 32.50 55.00 16.50 3.50 2.50 13.88 13.50 18.25 30 x 33

1

Note: Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit’s air-to-refrigerant coil.

W.O. NPTI
0.50 0.75 0.75
1 1 1

Drain NPTI
0.75 0.75 0.75 0.75 0.75 0.75

20

WSHP-SVX019A-EN

Figure 10. Right return/back supply (EXVK/DXVK)
TOP

Dimensional data right return/back supply

NOMINAL FILTER SIZE

A

Unit Dimensions

NOMINAL FILTER SIZE

BACK

D

E

H

F

J D

B LEFT SIDE

FRONT

C RIGHT SIDE

HI VOLT

DISCONNECT SWITCH LOCATION

WO

K

DRAIN

1.81

LOW VOLT

WI

10.87 8.00
2.55

Table 11. Dimensional data right return/back supply (EXVK/DXVK)

Cab

Unit

EXVK DXVK

B 009, 012 ­

Width
A 21.50

Depth
B 21.50

Height
C 34.00

Duct Collar
D
13.50

Duct Collar

Location

E

F

3.25 1.00

Blower Opening

H

J

10.13 9.38

Hi Volt

Nominal Filter

K

Size

14.25 16 x 19

W.I. NPTI
0.50

W.O. NPTI
0.50

C

015

­

21.50 23.00 36.00 13.50 3.88 1.00 10.50 11.25 15.25 17 x 20 0.75 0.75

D 018, 024 024 21.50 26.00 38.00 13.50 3.50 1.00 11.75 11.25 16.25 18 x 23 0.75 0.75

E 030,036 036 24.00 32.50 42.00 16.50 3.63 1.00 13.88 13.50 18.25 20 x 30 1

1

F 042, 048 048 25.40 32.50 49.00 16.50 3.50 1.00 13.88 13.50 18.25 27 x 30 1

1

G 060, 070 060,070 25.40 32.50 55.00 16.50 3.50 1.00 13.88 13.50 18.25 30 x 33 1

1

Note: Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit’s air-to-refrigerant coil.

Drain NPTI
0.75 0.75 0.75 0.75 0.75 0.75

WSHP-SVX019A-EN

21

Unit Dimensions
Figure 11. Waterside economizer1 (EXHK/DXHK)
B D

B D

2″ AIR FILTER (1.38 FOR 1″)

2.38

A

2″ AIR FILTER (1.38 FOR 1″)

A

2.38

C

3.40 4.25

3.40 4.25

Table 12. Dimensional data waterside economizer (EXHK/DXHK)

Cab
B C D E F G

Unit

EXHK

009

012

015

­

018

024

030

036

042

048

060

070

DXHK

­

­

­

­

024

­

036

­

048

­

060

070

Width A
8.5

WSE Dimensions

Depth

Height

Depth W/ Piping

B

C

D

21.5

18.25 29.00

23.0

19.25 30.50

26.0

33.50

22.25

38.25

32.5

29.25 50.50

35.25 59.50

Pipe Size

A

B

NPTI 0.50 0.75 0.75
1 1 1

NPTI 0.50 0.75 0.75
1 1 1

Table 13. Waterside economizer weights and part numbers – horizontal

Unit Model
EXHK009-012 LR EXHK015 LR
EX/DXHK018-024 LR EX/DXHK030-036 LR EX/DXHK042-048 LR

Waterside Economizer
WSHPECN00016 WSHPECN00017 WSHPECN00018 WSHPECN00019 WSHPECN00020

Weight w/out H2O
27 29 35 41 50

Weight w/H2O
30 33 40 48 59

1. Waterside economizer installation requires field piping. 22

C
WSHP-SVX019A-EN

Table 13. Waterside economizer weights and part numbers – horizontal (continued)

Unit Model
EX/DXHK060-070 LR EXHK009-012 RR EXHK015 RR
EX/DXHK018-024 RR EX/DXHK030-036 RR EX/DXHK042-048 RR EX/DXHK060-070 RR

Waterside Economizer
WSHPECN00021 WSHPECN00023 WSHPECN00024 WSHPECN00025 WSHPECN00026 WSHPECN00027 WSHPECN00028

Weight w/out H2O
59 27 29 35 41 50 59

Weight w/H2O
70 30 33 40 48 59 70

Figure 12. Waterside economizer (EXVK/DXVK)

Unit Dimensions

Table 14. Dimensional data waterside economizer (EXVK/DXVK)

Unit EXVK009-012
EXVK015

Cabinet B C

A (Width)
8.5
8.5

WSE Dimensions B
(Depth)
21.5
23.0

C (Height)
18.25
19.25

WSHP-SVX019A-EN

23

Unit Dimensions

Table 14. Dimensional data waterside economizer (EXVK/DXVK) (continued)

WSE Dimensions

Unit

Cabinet

A

B

(Width)

(Depth)

EXVK018-024, DXVK024

D

8.5

26.0

EXVK030-036, DXVK036

E

8.5

32.5

EXVK042-048, DXVK048

F

8.5

32.5

EXVK/DXVK060-070

G

8.5

32.5

Figure 13. Waterside economizer (EXVK/DXVK)

C (Height)
22.25
22.25
29.25
35.25

Table 15. Dimensional data waterside economizer (EXVK/DXVK)

Pipe Size

WSE Size

Piping Location

Drain

Unit

Cabinet A

B

C

D

E

F

G

H

J

K

L

M

N

NPTI NPTI Width Depth Height Height Height Width Width Width Width Width Height

EXVK009-012

B

EXVK015

C

EXVK018-024, DXVK024

D

EXVK030-036, DXVK036

E

EXVK042-048, DXVK048

F

EXVK/DXVK060-070

G

0.50 0.50 8.5 27.5 18.25 17.75 20.75 5.0 7.88 3.5 0.63 4.25 15.75 0.75 0.75 8.5 29.0 19.25 19.75 22.75 5.0 7.88 3.5 0.63 4.25 16.75
0.75 0.75 8.5 32.0 21.75 21.75 24.75 5.0 7.88 3.5 0.63 4.25 15.75

1

1

8.5 38.5 22.75 22.75 25.75 5.0

8

3.5

0.5 4.25 19.75

1

1

8.5 38.5 22.75 22.75 25.75 5.0

8

3.5

0.5 4.25 19.75

1

1

8.5 38.5 22.75 22.75 25.75 5.0

8

3.5

0.5 4.25 19.75

24

WSHP-SVX019A-EN

Unit Dimensions

Table 16. Waterside economizer weights and part numbers – vertical

Unit Model
EXVK009-012 LR EXVK015 LR
EX/DXVK018-024 LR EX/DXVK030-036 LR EX/DXVK042-048 LR EX/DXVK060-070 LR
EXVK009-012 RR EXVK015 RR
EX/DXVK018-024 RR EX/DXVK030-036 RR EX/DXVK042-048 RR EX/DXVK060-070 RR

Waterside Economizer
WSHPECN00002 WSHPECN00003 WSHPECN00004 WSHPECN00005 WSHPECN00006 WSHPECN00007 WSHPECN00009 WSHPECN00010 WSHPECN00011 WSHPECN00012 WSHPECN00013 WSHPECN00014

Weight w/out H2O (lbs) Weight w/H2O (lbs)

27

30

29

33

35

40

41

48

51

60

60

71

27

30

29

33

35

40

41

48

51

60

60

71

Figure 14. Waterside economizer coil piping diagram

Unit Water Outlet

Unit Heat Exchanger

Unit Water Inlet

WSE Coil Outlet

WSE Coil

WSE Coil Inlet

TEE

Please match the entering water port marking with
the marking label on the valve prior
to using this diagram.

Port A
3 Way Valve

Port B

Port AB Entering Water

WSHP-SVX019A-EN

25

Weights

Table 17. Unit weights DXH 2 to 6 tons (Approximate)

DXH

Shipping Weight with pallet (lbs)

Unit Weight without pallet (lbs)

024

393

269

036

458

313

048

560

381

060

613

434

070

613

434

Table 18. Unit weights DXVK 2 to 6 tons (Approximate)

DXV

Shipping Weight with pallet (lbs)

Unit Weight without pallet (lbs)

024

296

236

036

342

279

048

419

354

060

440

371

070

506

437

Table 19. Unit weights EXVK 0.75 to 6 tons (Approximate)

EXV (60 Hz)

Shipping Weight with pallet (lbs)

Unit Weight without pallet (lbs)

009

207

152

012

207

152

015

246

188

018

282

222

024

296

236

030

343

280

036

344

281

042

394

329

048

410

374

060

436

394

070

501

432

Table 20. Unit weights EXH 0.75 to 6 tons (Approximate)

EXH (60 Hz)

Shipping Weight with pallet (lbs)

Unit Weight without pallet (lbs)

009

297

173

012

297

173

Table 20. Unit weights EXH 0.75 to 6 tons (Approximate) (continued)

EXH (60 Hz)

Shipping Weight with pallet (lbs)

Unit Weight without pallet (lbs)

015

297

173

018

393

269

024

393

269

030

458

313

036

458

313

042

560

381

048

560

381

060

613

434

070

613

434

Weight Distribution for Hanging the DXH and EXH Model
WARNING
Improper Unit Lift!
Failure to properly lift unit in a LEVEL position could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. Test lift unit approximately 24 inches (61 cm) to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level.
Approximate weight distribution for proper hanging of the unit is indicated by weight distribution in the figure below.
Tolerance on the weights determined are ±15%.
Figure 15. Weight distribution DXH 2 to 6 tons; EXH 0.75 to 6 tons

26

WSHP-SVX019A-EN

A2L Information

A2L Work Procedures WARNING
Risk of Fire — Flammable Refrigerant!
Failure to follow instructions below could result in death or serious injury, and equipment damage.
· To be repaired only by trained service personnel.
· Do not puncture refrigerant tubing.
· Dispose of properly in accordance with federal or local regulations.
WARNING
Refrigerant under High Pressure!
Failure to follow instructions below could result in an explosion which could result in death or serious injury or equipment damage. System contains refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.
The units described in this manual use R-454B refrigerant. Use ONLY R-454B rated service equipment or components with these units. For specific handling concerns with R-454B, contact your local Trane representative.
Installation, repair, removal, or disposal should be performed by trained service personnel.
At all times, Trane’s maintenance and service guidelines shall be followed. If in doubt, contact Trane technical support for assistance.
Servicing
Prior to initiating work on equipment, check the area with an appropriate refrigerant detector. Ensure the service personnel are properly trained regarding work in potentially toxic or flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with all applicable refrigerants, i.e. non-sparking, adequately
WSHP-SVX019A-EN

sealed, or intrinsically safe. Be aware that the refrigerant does not contain an odor.
If any hot work is to be conducted on the refrigerating equipment or any associated parts, appropriate fire extinguishing equipment shall be available on hand. A dry powder or CO2 fire extinguisher should be located adjacent to the charging area.
At all times, Trane’s maintenance and service guidelines shall be followed. In in doubt, contact Trane technical support for assistance.
All maintenance staff and others working in the local area shall be instructed on the nature of the work being carried out. Work in confined spaces shall be avoided.
Ignition Source Mitigation
Do not use any sources of ignition when working on the refrigeration system.
Keep all ignition sources, including cigarette smoking, away from the site of installation, repair, removal or disposal, during which refrigerant can potentially be released to the surrounding space.
Survey the area around the equipment before initiating work to ensure no flammable hazards or ignition risks are present.
“No Smoking” signs shall be displayed.
Do not use devices that can be a source of ignition to accelerate defrosting of components. Use only defrost and cleaning procedures recommended by Trane. Do not pierce or burn.
Ventilation
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere. If present, check that the ventilation system, including outlets, are operating adequately and are not obstructed.
Refrigerating Equipment
Refrigerant piping or components should not be installed in locations where substances which may corrode them are present.
Check that equipment hazard markings are visible and legible. Replace them if they are not.
For equipment using secondary fluids, like water or glycol, check that refrigerant is not present in the secondary fluid loop before conducting any hot work.
Electrical Devices
Do not apply power to the circuit if a fault exists which compromises safety. If the fault cannot be corrected immediately, but it is necessary to continue operation, an
27

A2L Information
adequate temporary solution shall be used. This shall be reported to the owner of the equipment, so all parties are advised.
Initial safety checks shall include:
· Cabling is not subject to wear, corrosion, excessive pressure, vibration, sharp edges, or any other adverse environmental effects. Account for the effects of aging or continual vibration from sources such as compressors or fans.
· Capacitors are discharged. This shall be done in a safe manner to avoid possibility of sparking.
· No live electrical components and wiring are exposed while charging, recovering, or purging the system.
· Verify continuity of earth bonding.
· Replace electrical components with Trane replacement parts, or those meeting the same ratings and qualified for flame arrest protection, UL LZGH2 category.
Leak Detection
Never use an open flame to detect leaks. A halide torch should not be used. Use only approved leak detection methods per this instruction manual.
The following leak detection methods are deemed acceptable for all refrigerant systems.
Electronic leak detectors may be used to detect refrigerant leaks but, in the case of flammable refrigerants, the sensitivity may not be adequate, or may need recalibration. (Detection equipment shall be calibrated in a refrigerant- free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL gas (25% maximum) is confirmed.
Leak detection fluids are also suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
Examples of leak detection fluids are:
· Bubble method
· Fluorescent method agents
If a leak is suspected, all naked flames shall be removed/ extinguished.
If a refrigerant leak is found which requires brazing, all refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak.
Refrigerant Removal and Evacuation
When breaking into the refrigerant circuit to make repairs ­ or for any other purpose ­ conventional procedures shall be used. However, for flammable refrigerants it is important that best practice be followed, since flammability is a consideration.
The following procedure shall be adhered to:
28

1. Safely remove refrigerant following local and national regulations.
2. Evacuate.
3. Purge the circuit with inert gas.
4. Evacuate (optional for A2L).
5. Continuously flush or purge with inert gas when using flame to open circuit.
6. Open the circuit.
Prior to refrigerant removal, open all appropriate valves, including solenoid and electronic expansion valves (EXVs). Use control settings, where available. When not available, manually open all electronically controlled valves using acceptable service procedures.
The recovery equipment shall be in good working order with instructions available. Equipment shall be suitable for the recovery of the flammable refrigerant. For specific handling concerns, contact the manufacturer. Ensure all hose connections are checked for tightness to avoid refrigerant leaks.
The refrigerant shall be recovered into the correct recovery cylinders if venting is not allowed by local and national codes. Do not mix refrigerants in recovery unit and especially not in cylinders.
Refrigerant recovery unit should be purged with an inert gas after each use or before using with a different refrigerant Class ­ for example, A2L to A1.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The compressor body shall not be heated by an open flame or other ignition sources to accelerate this process. When oil is drained from a system, it shall be carried out safely.
The system shall be purged with oxygen-free nitrogen to render the appliance safe for flammable refrigerants. This process might need to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant systems.
The system shall be vented down to atmospheric pressure to enable work to take place.
The outlet for the vacuum pump shall not be close to any potential ignition sources, and ventilation shall be available.
Refrigerant Charging
In addition to conventional charging procedures, the following requirements shall be followed.
· Ensure that contamination of different refrigerants does not occur when using charging equipment.
· Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
· Cylinders shall be kept in an appropriate position according to the instructions.
WSHP-SVX019A-EN

· Ensure that the refrigerating system is earthed prior to charging the system with refrigerant.
· Label the system when charging is complete (if not already).
· Extreme care shall be taken not to overfill the refrigerating system.
Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leaktested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
Prior to refrigerant charging, open all appropriate valves, including solenoid and electronic expansion valves (EXVs). Use control settings, where available. When not available, manually open all electronically controlled valves using acceptable service procedures.
Decommissioning
Before carrying out the decommissioning procedure, it is essential that the trained service personnel is completely familiar with the equipment and all its details. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant. It is essential that electrical power is available before the task is commenced.
1. Become familiar with the equipment and its operation.
2. Isolate system electrically.
3. Before attempting the procedure, ensure that:
a. Mechanical handling equipment is available, if required, for handling refrigerant cylinders.
b. All personal protective equipment is available and being used correctly.
c. The recovery process is supervised at all times by a competent person.
d. Recovery equipment and cylinders conform to the appropriate standards.
4. Pump down refrigerant system, if possible.
5. If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
6. Make sure that cylinder is situated on the scales before recovery takes place.
7. Start the recovery machine and operate in accordance with instructions.
8. Do not overfill cylinders (no more than 80% volume liquid charge).
9. Do not exceed the maximum working pressure of the cylinder, even temporarily.
10. When the cylinders have been filled correctly and the process completed, make sure that the cylinders and
WSHP-SVX019A-EN

A2L Information
the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
11. Recovered refrigerant shall not be charged into another refrigerating system unless it has been cleaned and checked. When equipment has been decommissioned, attach a signed label which includes the date of decommissioning.
12. When equipment has been decommissioned, attach a signed label which includes the date of decommissioning.
A2L Application Considerations
This product is listed to UL standard 60335-2-40, Household and Similar Electrical Appliances ­ Safety ­ Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers, which defines safe design and use strategies for equipment using A2L refrigerants. This standard limits the refrigerant concentration in a space in the event of a refrigerant leak. To meet the requirements, the UL standard defines minimum room area, refrigerant charge limit, minimum circulation airflow and/or ventilation airflow requirements, and limits the use of ignition sources in ductwork and spaces. The standard may require a unit refrigerant leak detection system.
For equipment with R-454B and charge amounts less than or equal to 3.91 lbs per circuit, this UL standard does not prescribe a room area limit and does not require a refrigerant leak detection system or any circulation airflow or ventilation airflow mitigation strategies. However, ignition sources in ductwork must be evaluated.
Depending on the application, a specific requirement of ANSI/ASHRAE Standard 15, Safety Standard for Refrigeration Systems, could be more stringent than UL 60335-2-40 requirements. See Refrigeration Systems and Machinery Rooms Application Considerations for Compliance with ASHRAE® Standard 15-2022 Application Engineering Manual (APP-APM001*-EN) for more information.
Ignition Sources in Ductwork
Do not install open flames in the ductwork. Hot surfaces exceeding 700°C (1290°F) should not be installed in the ductwork unless the average airflow velocity is not less than 1.0 ms (200 ftmin) across the heater and proof of airflow is verified before system is energized.
Electric heaters can exceed the surface temperature limit if airflow distribution is poor, or insufficient airflow is provided over the heater.
Surface temperatures of most gas heaters do not exceed the surface temperature limits due to ANSI construction requirements.
Ignition Sources in Unit
This UL-listed unit does not contain any ignition sources. All potential ignition sources, (including factory or field
29

A2L Information

installed accessory electric heaters, gas heaters, relays, and contactors) were evaluated during product UL listing.
Minimum Room Area Limits (Refrigerant charge greater than 3.91 lb per circuit)
Equipment with R­454B charge amounts greater than 3.91 lb per circuit may require additional circulation or ventilation airflow mitigation strategies. In this case, two minimum room area (Amin) thresholds:
· The first threshold defines when equipment serving a single room is required to provide circulation airflow, either continuous or activated by a leak detection

system. A ducted system requires circulation airflow unless the smallest room it serves is larger than the adjusted Amin threshold. This product contains a leak detection system if a circuit charge is greater than 3.91 lbs. As a result, no further leak detection system evaluation is required.
· The second threshold defines when additional ventilation airflow is required. If the room area, A or TA, is below the adjusted Amin or TAmin threshold, additional ventilation is required to remove refrigerant in the event of a leak. Refer to UL 60335-2-40 Clause GG.8 and ANSIASHRAE Standard 15 Section 7 for natural and mechanical ventilation requirements.

Table 21. Minimum room area — vertical
Models

Minimum Room Area (m2) 0.6 meters height

Minimum Room Area (ft2) 1.9 feet height

EXVK009

11.2

EXVK012

10.9

EXVK015

11.3

EXVK018

15.2

EXVK024

16.0

EXVK030

19.3

EXVK036

19.8

EXVK042

24.3

EXVK048

24.9

EXVK060

28.4

EXVK070

33.5

DXVK024

16.6

DXVK036

19.0

DXVK048

24.6

DXVK060

29.4

DXVK070

33.5

120.3 116.8 122.0 163.2 171.8 207.9 213.1 261.2 268.0 305.8 360.8 178.7 204.5 264.6 316.1 360.8

Table 22. Minimum room area — horizontal
Models
EXHK009 EXHK012 EXHK015 EXHK018 EXHK024 EXHK030 EXHK036 EXHK042 EXHK048

Minimum Room Area (m2) 2.2 meters height 3.0 3.0 3.1 4.1 4.4 5.3 5.4 6.6 6.8

Minimum Room Area (ft2) 7.2 feet height 32.8 31.9 33.3 44.5 46.9 56.7 58.1 71.2 73.1

30

WSHP-SVX019A-EN

A2L Information

Table 22. Minimum room area — horizontal (continued)

Models

Minimum Room Area (m2) 2.2 meters height

EXHK060

7.7

EXHK070

9.1

DXHK024

4.5

DXHK036

5.2

DXHK048

6.7

DXHK060

8.0

DXHK070

9.1

Minimum Room Area (ft2) 7.2 feet height 83.4 98.4 48.7 55.8 72.2 86.2 98.4

Minimum Room Area (Amin) Adjustments
Use equation below to adjust the minimum room area, as applicable, based on the unit’s installation height, altitude, and occupancy level it serves.

Amin.adj = Nameplate Amin x Altitude Adj x Height Adj x Focc

Table 23. Altitude adjustment factor

Altitude (ft)
Amin Adjustment

Sea Level to 2000
1

2001 to 4000
1.05

4001 to 6000
1.11

6001 to 8000
1.17

Multiply the altitude adjustment factor in the table below by Amin listed on the unit nameplate

8001 to 10000
1.24

10001 to 12000
1.32

12001 to 14000
1.41

14001 to 15000
1.51

Over 15000 1.57

In addition, Amin can be adjusted if the unit is installed in a room at a height that is higher than the minimum height shown on the unit. To adjust Amin, multiply by the ratio of the unit minimum installation height (in meters) / actual installation height (in meters). Use 0.6 m in the ratio for unit minimum installation heights less than or equal to 0.6 m.
For institutional occupancies, ASHRAE Standard 15 applies an additional adjustment factor Focc to the amount of a charge allowed in a space. To calculate the adjusted Amin for institutional occupancies, multiply the Amin on the nameplate by two.
EXAMPLE 1: 20 Ton Packaged Rooftop Multi-Zone VAV System Serving an Institutional Occupancy Space
The packaged unit serves 7600 ft2 of a nursing home located at an attitude of 4000 ft. The unit has two equally charged 10 ton refrigeration circuits. Each circuit has 12 lbs of refrigerant with a minimum room area requirement of 180 ft2 with a 2.2 m release height.
TAmin.adj = 180 ft2 x 1.05 x 2 = 378 ft2
No additional ventilation is required.
EXAMPLE 2: 10 Ton Split System Serving a Single Commercial Occupancy Space
The split system serves a 1500 ft2 manufacturing space at 5000 ft altitude. The final installed charge of the single circuit 10 ton unit is 20 lb. The unit has an open return with a release height of 1 m and ducted supply air. The unit Amin is 660 ft2.
WSHP-SVX019A-EN

Amin.adj = 660 ft2 x 1.11 = 733 ft2
No additional ventilation is required.
Determining Room Area (A or TA)
The room area (A) is the room area enclosed by the projection to the floor of the walls, partitions, and doors of the space that the equipment serves. For ducted systems, total room area (TA) of all rooms connected by ducts, may be used instead of A.
Rooms connected by drop ceilings only are not considered a single room.
Rooms on the same floor of the building, and connected by an open passageway, can be considered part of the same room if the passageway is a permanent opening, extends to the floor and is intended for people to walk through.
Adjacent rooms on the same floor of the building and connected by permanent openings in the walls and/or doors between rooms (including gaps between the wall and the floor), can be considered part of the same room if the openings meet the following criteria.
· The opening is permanent and cannot be closed.
· Openings extending to the floor, such as door gaps, need to be at least 20mm above the floor covering surface.
· Natural ventilations opening areas must meet the requirements of ANSIASHRAE Standard 15-2022, Section 7.2.3.2.
31

A2L Information
Rooms that are connected by a mechanical ventilation system can be considered a single room area if the mechanical ventilation system meets the requirements of ANSIASHRAE Standard 15-2022, Section 7.6.4.
Leak Detection System (Refrigerant charge greater than 3.91 lb per circuit)
The leak detection system consists of one or more refrigerant detection sensors. When the system detects a leak, the following mitigation actions will be initiated until refrigerant has not been detected for at least 5 minutes:
· Energize the supply fan(s) to deliver a required minimum amount of circulation airflow.
· Disable compressor operation.

· Provide an output signal to fully open all zoning dampers, such as VAV boxes.
· Provide an output to energize additional mechanical ventilation (if needed).
· Units without airflow proving will disable electric heat sources.
Building fire and smoke systems may override this function.
If the refrigerant sensor has a fault, is at the end of its life, or is disconnected, the unit will initiate the mitigation actions. Mitigation actions may be verified by disconnecting the sensor.
The refrigerant sensors do not need service. Use only Trane-approved sensors when replacement is required.

32

WSHP-SVX019A-EN

Installation

WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
General Installation Checks
The checklist below is a summary of the steps required to successfully install a commercial unit. This checklist is intended to acquaint the installing personnel with what is required in the installation process. It does not replace the detailed instructions that are in the applicable sections of this manual.
1. Remove packaging and inspect the unit. Check the unit for shipping damage and material shortage; file a freight claim and notify appropriate sales representation.
The EXH/V 0.75 to 6 tons and DXH/V 2 to 6 tons have been anchored to the skid with (4) angle brackets. Remove these brackets before lifting unit into place.
2. Verify the correct model, options and voltage from the unit nameplate.
3. Pull out all field attached parts (i.e. filter rack, duct collar, filter and mounting screws) from the unit packaging for field mounting.
4. Verify the installation location of the unit provides the required clearance for proper operation.
5. Remove refrigeration access panel and inspect the unit. Be certain the refrigerant tubing has clearance from adjacent parts.
6. Fabricate and install duct work
7. Install and connect a condensate drain line and trap to the drain connection.

Main Electrical WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.
1. Verify the power supply complies with the unit nameplate specifications.
2. Inspect all control panel components; tighten any loose connections.
3. Connect properly sized and protected power supply wiring to a field- supplied/installed disconnect switch and to the main compressor contactor/power block 1K1 for DXH/V 2 to 6 tons and EXH/V 0.75 to 6 ton units.
4. Install proper grounding wires to an earth ground. Note: All field- installed wiring must comply with NEC and
applicable local codes.
Electric Heat Requirements
1. Verify that the power supply complies with the electric heater specifications on the unit and heater nameplate.
2. Inspect the heater junction box and control panel; tighten any loose connections.
3. Check electric heat circuits for continuity.
Low Voltage Wiring (AC) Requirements
1. Install the zone sensor or thermostat.
2. Connect properly sized control wiring to the proper termination points between the zone thermostat or sensor and the unit control panel.
Filter Installation
Each unit ships with 1 in. (25.4 mm) standard, 2 in. (50.8 mm) standard, 2 in. MERV 8 or 2 in. MERV 13 filter. The quantity of filters is determined by unit size. The EXH and DXH units require field installation of the 1 in. or 2 in. filters rack. All sheet metal bracket, filter and hardware are in a box located on the side of the unit within the unit packaging. All vertical units ship with the filter rack and filters factory installed. Note: Do not operate the unit without filters.

WSHP-SVX019A-EN

33

Installation
Supply-Air Ductwork
Horizontal DXH and EXH units require duct flanges to be field installed. The duct flange ships in a box on the side of the unit. Install the flange with (8) 3/8 in. (213 mm) factory supplied screws.
Install the 1 in. (25.4 mm) supply-air duct flange to the vertical and horizontal equipment with the (8) 5/16 in. (7.94 mm) factory-supplied head screws. The duct collar assembly for each unit is shipped with the unit in the same box where the IOM manual is located.
When attaching the field ductwork to the unit, provide a watertight flexible connector at the unit to prevent operating sounds from transmitting through the ductwork (See the figure below).
Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence and to reduce static pressure.
Figure 16. Flexible supply-air connector (field provided)

Figure 17. Flexible return-air connector (field provided)
SUPPLY-AIR

RETURN AIR

Filt er Flange ( Fact ory Provided)

Ret urn-Air Boot ( Field Provided)

Su p p ly – Air Boot ( Field Supplied)
1- inch Duct Collar ( Fact ory Provided)
Return-Air Ductwork
Install the 1/2 in. (25.4 mm/50.8 mm) adjustable filter rack to the horizontal equipment only with the use of (4) 5/16 in. (7.94 mm) factory supplied head screws. The vertical equipment factory ships with the filter rack and filter(s) installed. When attaching the field ductwork to the unit, provide a watertight flexible connector at the unit to prevent operating sounds from transmitting through the ductwork. Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence and to reduce static pressure.

Ducted Panel
The return-air arrangement may be easily converted from a free return-air system, to a ducted return-air system with the addition of a return-air side panel. By replacing the filter racks with the return-air panel, a complete seal from the duct to the unit is possible. The 1.5 duct flange facilitates ease of field connection to the duct system. This accessory is typically used when the return-air filter is placed in a builtin ceiling grille, or placed within a field provided filter rack assembly.
Install the return-air duct panel to the return-air opening with the six screws provided for the filter rack assembly.

34

WSHP-SVX019A-EN

Figure 18. Return-air duct panel

Installation

Unit Side 1″

3 3/4″

Unit Top A
B

Duct Panel with 1 1/2″-Flange

Table 24. Ducted panel – return air
Unit Size EXVK009-012
EXVK015 EXVK018-024, DXVK024 EXVK030-036, DXVK036 EXVK042-048, DXVK048 EXVK060-070, DXVK060-070
EXHK009-012 EXHK015
EXHK018-024, DXHK024 EXHK030-036, DXHK036 EXHK042-048, DXHK048 EXHK060-070, DXHK060-070

A (in.) 18.50 20.00 23.00 29.50 29.50 29.50 18.50 20.00 23.00 29.50 38.88 47.88

B (in.) 16.50 17.50 18.50 20.50 27.25 33.25 16.50 17.50 18.50 20.50 19.75 19.75

Duct Collar Part Number WSHPPND00002 WSHPPND00003 WSHPPND00004 WSHPPND00005 WSHPPND00006 WSHPPND00007 WSHPPND00011 WSHPPND00012 WSHPPND00013 WSHPPND00014 WSHPPND00015 WSHPPND00016

WSHP-SVX019A-EN

35

Installation
Ducted Filter Rack

When filter access is needed at the unit in a ducted return, a ducted filter rack is available. Vertical unit filter racks are available in right or left access configurations. Horizontal units are available in top, bottom or side access configurations.

Table 25. Ducted filter opening size – 0.75 to 6 tons

Unit Size

A (in.)

EXHK 009-012

19.00

EXHK 015

20.50

EXHK 018-024, DXHK 024

23.50

EXHK 030-036, DXHK 036

30.00

EXHK 042-048, DXHK 048

40.50

EXHK 060-070, DXHK 060-070

50.50

EXVK 009-012

19.00

EXVK 015

20.50

EXVK 018-024, DXVK 024

23.50

EXVK 030-036, DXVK 036

30.00

EXVK 042-048, DXVK 048

30.00

EXVK 060-070, DXVK 060-070

30.00

Note: All dimensions in inches. All dimensions are for accessory 2 or 4-inch filter rack.

B (in.) 16.25 17.25 18.25 20.25 21.00 21.00 16.25 17.25 18.25 20.25 27.00 32.75

C (in.) 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

Sound Attenuation Pad
For sound-sensitive installations, a vibration pad (field provided) should be placed beneath the horizontal or vertical equipment. For the horizontal unit, the pad should be approximately twice the size of the unit foot print. For the vertical unit, the pad should be 0.5 in. (12.7 mm) thick and equal to the overall unit foot print.
Hanging the Horizontal Unit
WARNING
Proper Structural Support Required!
Failure to ensure proper structural ceiling support could result in unit falling from its location which could result in death or serious injury. Ceiling structure must be strong enough to support the weight of the unit and any accessories. If unsure, check with a structural engineer.

1. Install the hanging isolators (located in the control box from factory) into the six hanging brackets.
2. Use a lift with a large supporting surface or a wooden structure supporting the base of the unit (hanging rails) when the unit is lifted for installation.
3. Secure the equipment to a joist, concrete, etc. with the use of 3/8 in. (9.7 mm) field provided (all-thread) rod. Each rod should contain field provided nuts and washers to complete the hanging installation.
4. All plumbing to the unit should conform per national and local codes and is the responsibility of the contractor. The 0.5 to 6 ton horizontals and EX/DXHK models do not need to be sloped. EXHK and DXHK 0.75 to 6 ton models must be installed level. The 0.5 to 5 ton horizontal models do not need to be sloped and must be installed level.
Note: Rods must be perpendicular to the mounting holes in the base rail of the horizontal unit.

To hang the horizontal configuration (see the figure below):

36

WSHP-SVX019A-EN

Figure 19. Hanging the unit

Installation
Supply Pipe Connections
Figure 21. Supply/return pipe connections

Condensate Drain Connection
Figure 20. Negative pressure system
CLEAN OUT ( CAPPED and SEALED)
Install proper trapping to the equipment. The unit drain connection is 0.75 in. NPT for all DXH, DXV, and EXH/V 0.75 to 6 ton models. When designing the condensate trap for the water-source system, it is important to consider the unit draw through design requiring negative pressure trapping. In a properly trapped system, when condensate forms during normal operation, the water level in the trap rises until there is a constant flow. It is imperative to maintain water in the trap and not allow the trap to dry out during heating season. Keeping trap primed at all times will enable the water to flow properly. See the figure above for appropriate dimensions required in a negative pressure system.
WSHP-SVX019A-EN

WATER- OUT
WATER- I N
AUTOMATI C BALANCI NG HOSE KI T

RETURN TO LOOP
SUPPLY FROM CENTRAL PUMP

Connect the supply and return hoses to the water-inlet (from supply) and water-outlet (to return) of the unit. For vibration isolation, it is recommended that flexible steelbraided hoses be installed instead of hard piping the equipment to the main loop system. Figure above shows connection of a Hays Mesurflo® balancing hose kit to the water-in and water-out of a vertical unit. Note: Above figure example incorporates the Hays
Mesurflo® balancing hose kit and a 2-position isolation valve into the system design. An isolation valve is often used in variable speed pumping applications and is designed to stop water flow to the unit during non operation times. This allows the loop water pumps to run only when a requirement for pumping is needed for greater energy efficiency of the overall system design.
Cleaning and Flushing the Water Loop
After the piping system is complete, the flexible hose connectors should be doubled back to complete the water circuit external to the unit (avoiding trash settle-out in the condenser). An extra pipe may be necessary to connect the hose kits.
1. Water circulation system should be filled with clean water using the water make up connections.
Note: Air vents should be open during filling.
2. With the air vents closed, start the circulating pump and then crack the air vents to bleed off the trapped air to confirm circulation through all components of the system.
Note: Make up water must be available to the system to replace the volume formerly occupied by the air that is bled off.
3. With the air vented and the water circulating, the entire system should be checked for leaks and repaired as required.
4. Operate the supplementary heat system (boiler) making checks per manufacturer’s instructions. During this operation, visual checks should be made for leaks
37

Installation
that may have occurred due to increased heat. Repair as required.
5. Open the system at the lowest point for the initial blow down (making sure the make up water is equal to the water being dumped). Continue blow down until the water leaving the drain runs clear, but not less than 2 hours.
6. Shut down pumps and supplementary heat system. Reconnect the hoses placing the water-to-refrigerant heat exchanger in the water circulating system.
Note: Vents should be open when the pumps and supplementary heat system are shut down.
Field Installed Power Wiring
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
NOTICE
Use Copper Conductors Only!
Failure to use copper conductors could result in equipment damage as the equipment was not designed or qualified to accept other types of conductors.
Verify that the power supply available is compatible with the unit’s nameplate. Use only copper conductors to connect the power supply to the unit.
Main Unit Power Wiring
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

A field supplied disconnect switch must be installed at or near the unit in accordance with the National Electric Code (NEC latest edition). Location of the applicable electric service entrance for HIGH (line voltage) may be found in the Dimensions section of this manual. The high-voltage connection is made at the 1K1 contactor or 1TB power block inside the unit control box (See the figure below). Refer to the customer connection diagram that is shipped with the unit for specific termination points. Provide proper grounding for the unit in accordance with the local and national codes.
Figure 22. Power wiring example
Control Power Transformer
The 24 V control power transformers are to be used only with the accessories called out in this manual. A 50 VA transformer is externally fused. Transformers rated greater than 50 VA are equipped with circuit breakers. If a circuit breaker trips, turn OFF all power to the unit before attempting to reset it.
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.
The transformer is located in the control panel.

38

WSHP-SVX019A-EN

Thermostat Location
Figure 23. Thermostat/sensor location

Installation
Location of the thermostat or zone sensor is an important element of effective room control. Areas where the thermostat or zone sensor should not be located include: · Behind doors or corners · Near hot or cold air ducts · Near radiant heat (heat emitted from appliances or the
sun) · Near concealed pipes or chimneys · On outside walls or other non conditioned surfaces · In airflows from adjacent zones or other units

Thermostats and Zone Sensors

Table 26. Thermostat selection for use with the Deluxe controller

Thermostat

Part Number

Description

X13511535010

1 Heat/1 Cool, non-programmable commercial thermostat for conventional air conditioners and heat pumps that are configured without auxiliary heat
· 1 H/1 C

X13511536010

3 Heat/2 Cool, non-programmable commercial thermostat for conventional air conditioners and heat pumps that are configured with or without auxiliary heat.
· 3 H/2 C

X13511537010

3 Heat/2 Cool, programmable commercial thermostat for conventional (rooftop) air conditioners and heat pumps that are configured with or without auxiliary heat.
· 3 H/2 C

X13511538010

3Heat/2 Cool, programmable touch screen thermostat for conventional air conditioners and heat pump systems. The thermostat will provide the human interface, zone temperature sensing both local and optional remote temperature sensing, and set point scheduling on a daily/ weekly basis. This thermostat can also display humidity with a control signal for dehumidification with a local humidity sensor or optional remote humidity sensor.
· 3 H/2 C

WSHP-SVX019A-EN

39

Installation

Table 26. Thermostat selection for use with the Deluxe controller (continued)

Thermostat

Part Number Pivot — BAYSTAT814A-W.

Description
Pivot Smart Thermostat is a Wi-Fi/ethernet thermostat for commercial applications. It has a very simple interface for occupants to adjust the thermostat. Cooling and heating control of multiple systems is made even easier and faster when connected to the Pivot App. Supports 2 stage heat pump with auxiliary heat.

XL824 – TCONT824AS52DB.

The XL824 Smart thermostat is a Wi-Fi/ethernet thermostat for Residential applications such as single family homes, condominiums and apartments. Supports 2 stage heat pump with auxiliary heat. The XL824 can be connected to the Nexia Home App and other home automation systems.

Table 27. Zone sensor selection for use with SymbioTM 400-B controller

Sensor

Part Number X13790886010

Description
Wired temperature sensor with an LCD display
· Allows an occupant to control the temperature setpoint, request timed override of system operation, and provides a COMM module to service technicians. Symbio 400-B Compatible

X13651467020 X13511529010

Communication Module · Sold in packs of 12 · Provides local RJ22 connection to Trane® service tools for easy, low cost
maintenance.
Zone Sensor · Symbio 400-B compatible · External setpoint adjustment wheel

X13511527010

Zone Sensor · Symbio 400-B compatible · External setpoint adjustment wheel · ON and CANCEL buttons

40

WSHP-SVX019A-EN

Table 27. Zone sensor selection for use with SymbioTM 400-B controller (continued)

Sensor

Part Number X1379084501

Description
Zone Sensor · Symbio 400-B compatible · External setpoint adjustment wheel · ON and CANCEL buttons · Fan switch AUTO-OFF

X1379044401

Temperature and relative humidity sensor · Symbio 400-B compatible

Installation

Awake

X13790993001 X13790992001

Commercial Touch Screen Programmable Zone Sensor

· Supports Standby, Occupied, and Unoccupied

· 7 day, 5+2 day, and 5+1+1 day

· Cannot be used with BAS as sensor ties up BACnet link. For use with factoryprogrammed Symbio 400-B.

Notes: ·

Adjusting the rotary switch on Symbio 400-B may be required to correspond address configuration in the sensor. See the installation manual for more information.

· Additional configuration is needed in the field to use the Programmable zone sensors (to put BAS points in service on Symbio 400-B).

Residential Touch Screen Programmable Zone Sensor

· Supports Awake, Away, Home, and Sleep

· 7 day, 5+2 day, and 5+1+1 day

· Cannot be used with BAS as sensor ties up BACnet link. For use with factoryprogrammed Symbio 400-B.

Notes: ·

Adjusting the rotary switch on Symbio 400-B may be required to correspond address configuration in the sensor. See the installation manual for more information.

· Additional configuration is needed in the field to use the Programmable zone sensors (to put BAS points in service on Symbio 400-B).

WSHP-SVX019A-EN

41

Installation

Table 28. Wireless zone sensor selection for use with SymbioTM 400-B controller

Sensor

Part Number X13790955010

Description
Trane Air-Fi® WCS-SD (display) · Symbio 400-B Compatible · Easy-to-use interface for clear and simple monitoring and control

X13790956010

Trane Air-Fi WCS-SB (base) · Symbio 400-B Compatible · Simplicity · Eliminates local temperature control when higher control level is required.

X13790973030

Wireless communications sensor accessory–2% relative humidity (RH) sensor module (WCS-SH) The optional RH sensor module plugs in to any WCS model, further simplifying installation by eliminating the needed for additional wiring.

Controls Using 24 Vac
Before installing any wire, refer to the electrical access locations in the Unit Dimensions and Weights sections of this manual.
The AC control wiring between the controls and the unit termination point must not exceed 3 Ohms/conductor for the length of the run.

NOTICE
Component Failure!
Resistance in excess of 3 ohms per conductor could result in component failure due to insufficient AC voltage supply.
Do not exceed three (3) ohms per conductor for the length of the run.

Check all loads and conductors for grounds, shorts, and mis-wiring. Use copper conductors unless otherwise specified. Do not run the AC low-voltage wiring in the same conduit with the high voltage power wiring.

Table 29. 24V AC conductors

Distance from unit to control

Recommended wire size

000-460 ft

18 gauge

461-732 ft

16 gauge

733-1000 ft

14 gauge

Low-voltage connection diagrams for deluxe 24 V control packages for these thermostats mounted on 0.75 to 6 ton equipment sizes are shown in the figures below.
Figure 24. Low voltage wire connection

42

WSHP-SVX019A-EN

Figure 25. Low voltage single wire connection

Figure 27. Deluxe controls

Installation

Make connection for a single-wire by inserting a single wire after stripping off the coating.
Figure 26. Low voltage stranded wire connection

Figure 28. TP1 connection type

Follow the steps to connect the stranded wire:
1. Release the spring with a dedicated screwdriver (blade width 2.5 mm)
2. Insert the stripped cable as far as it gets inserted.
3. Complete the connection by removing the screwdriver.

WSHP-SVX019A-EN

43

Installation
Figure 29. Deluxe controls with WSE or DX two-stage

Figure 32. Deluxe controls general alarm and compressor disable

TP2 1 – (Y2)Compressor/Cool stage 2 Figure 30. TP2 connection type
Figure 31. Deluxe controls humidistat connections between wires H1 and H2 in control box
44

Deluxe board (1U1) connections
AL1, AL2 – Alarm Contact output
CD1, CD2 – Compressor Disable input (24Vac)
For installation, operation and programming see SymbioTM 400­B/500 Programmable Controllers Water Source Heat Pump (WSHP) Installation, Operation, and Maintenance guide (BAS-SVX092*-EN)..
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
WSHP-SVX019A-EN

External Smoke Detection Wiring to Unit
Deluxe Controller
To inhibit operation of the compressor and fan for a safety shutdown, it is necessary to break the wire (21X) from the 24 Volt transformer to the 1TB1 terminal block. This can be done with the dry contacts of a relay. When that connection is opened, it terminates voltage to both the deluxe controller and the thermostat, which stops/prevents all control function to the fan and compressor.
SymbioTM 400-B Controller
To inhibit operation of the compressor and fan for a safety shutdown, it is necessary to break the wire (21A) from the 24 Volt transformer to the Symbio 400-B (1U1). This can be done with the dry contacts of a relay. When that connection is opened, it terminates the power voltage to the controller, which stops/prevents all control function including the fan and compressor.
Airflow Adjustment
WARNING
Rotating Components!
Failure to disconnect power before servicing could result in rotating components cutting and slashing technician which could result in death or serious injury. During installation, testing, servicing and troubleshooting of this product it may be necessary to work with live and exposed rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks.
Units with Deluxe 24V controls
The ECM is programmed for constant torque and delivers airflow similar to a PSC motor while operating at a higher efficiency.

Figure 33. ECM control box

Installation

Figure 34. ECM control board

1. Potentiometer will be used to adjust the PWM output
2. Seven segment display
Using a screwdriver, the potentiometer is used to adjust the PWM output from 20% to 100% PWM. Increasing the PWM increases the motor speed. When setting the airflow for air balancing, the high-speed terminal (GH) must have 24 Vac signal. This confirms the PWM output is adjusted for the full load airflow.
The display shows the commanded motor speed percentage. If running on low speed (GL), the low-speed value is displayed. If running in GH the high-speed value is displayed. If both GH and GL input signals are present, the PWM output value is the GH value. Note: ECM control board is only on units with Deluxe 24V
controls. Tracer® TU is used to adjust fan speed on units with SymbioTM 400-B controls.

WSHP-SVX019A-EN

45

Installation
Waterside Economizer Installation
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
Waterside Economizer Installation for Horizontal 0.75 to 6 Ton Units
The following steps were sequenced to aid in the installation and pairing of a water side economizer to a 0.75 to 6 ton horizontal water source heat pump.
1. Remove the filter bracket from the unit. It is secured by four screws: three on top (circled) and two on the bottom (not shown). Do not discard the filter brackets.
Figure 35. Step 1

fasteners (total of four for each bracket). The engagement hole locations and L-Bracket can be seen in the Figure 36, p. 46 . Figure 36. Step 2
3. Attach the filter bracket to the waterside economizer using the five screws removed earlier. Install the air filter.
4. Install the braided hose connecting point A (leaving the WSE) to point B (entering the WSHP). Connect the supply water to point D and the return water to point C.
Figure 37. Step 4

2. Mount the waterside economizer to the unit. It is secured to the unit using the three engagement holes used for the filter bracket on the top. Secure the sides of the economizer using the two L-Brackets on each side by lining up the engagement holes for the
46

5. Locate the entering water sensor that is located behind the unit’s control box, and wire tie it to the water SUPPLY side of the piping. The sensor must be mounted before the two-position valve. Attaching the sensor anywhere else will cause the WSE to not operate correctly. Bundle up any excess sensor wire and wire tie the bundle neatly.
6. Locate the WSE valve wires (35B (COM), 36B (OPEN), 37B (CLOSE)) behind control box, and connect to the valve actuator. Bundle up any excess wire and wire tie the bundle neatly. Direction of rotation is reversible with switch.
7. Insulate the economizing piping package and the associated hoses via field pipe insulation. Insulating the
WSHP-SVX019A-EN

piping will prevent condensation from forming on the pipe and dripping on the floor.

Notes: ·

Trane does not provide insulation on the economizing piping package. The insulation must be field provided and field installed.

· Trane does not provide condensate overflow protection of the waterside economizer. This must be field provided and installed.

8. Field pipe the drain lines of the waterside economizer and water-source heat pump. Both the WSE and unit condensate drains must be separately trapped for proper handling of condensation (see Figure 38, p. 47 ). Both Vertical and Horizontal units will be piped similar to each other. The drain connection is located on the bottom side of the economizing coil.

Figure 38. Step 8

H

J

L

H
L J

NEGATIVE PRESSURE TRAPPING
H=1″ (25.4 mm) FOR EVERY 1″ (25.4 mm) OF MAXIMUM NEGATIVE STATIC PRESSURE +1″ (25.4 mm).
J= HALF OF H.
L=H+J+ PIPE DIAMETER +INSULATION.

Installation

Table 30. Economizer part numbers

Supply-Air Arrangement

Unit

Part Number

Left Supply Right Supply

EXVK009-012
EXVK015
EXVK018-024, DXVK024
EXVK030-036, DXVK036
EXVK042-048, DXVK048
EXVK060-070, DXVK060-070
EXVK009-012
EXVK015
EXVK018-024, DXVK024
EXVK030-036, DXVK036
EXVK042-048, DXVK048
EXVK060-070, DXVK060-070

WSHPECN00016 WSHPECN00017 WSHPECN00018 WSHPECN00019 WSHPECN00020 WSHPECN00021 WSHPECN00023 WSHPECN00024 WSHPECN00025 WSHPECN00026 WSHPECN00027 WSHPECN00028

Waterside Economizer Installation for Vertical Units
The following steps were sequenced to aid in the installation and pairing of a water side economizer to a EXV and DXV water source heat pump.
1. Remove the filter bracket from the unit. It is secured by five screws: three on top (circled) and two on the bottom (not shown). Do not discard the filter brackets.

WSHP-SVX019A-EN

47

Installation
Figure 39. Step 1

Figure 41. Step 3

2. Mount the waterside economizer to the unit. It is secured to the unit using the five engagement holes that were used for the filter brackets: three on top and two on the bottom.
Figure 40. Step 2

4. Install the braided hose connecting point A (leaving the WSE) to point B (entering the WSHP). Connect the supply water to point D and the return water to point C.
Figure 42. Step 4

3. Attach the filter brackets to the waterside economizer using five screws. Install the air filter.
48

5. Locate the entering water sensor that is located behind the unit’s control box, and wire tie it to the water SUPPLY side of the piping. The sensor must be mounted before the two-position valve. Attaching the sensor anywhere else will cause the WSE to not operate correctly. Bundle up any excess sensor wire and wire tie the bundle neatly.
6. Locate the WSE valve wires (35B (COM), 36B (OPEN), 37B (CLOSE)) behind control box, and connect to the valve actuator. Bundle up any excess wire and wire tie the bundle neatly. Direction of rotation is reversible with switch.
7. Insulate the economizing piping package and the associated hoses via field pipe insulation. Insulating the
WSHP-SVX019A-EN

piping will prevent condensation from forming on the pipe and dripping on the floor.

Notes: ·

Trane does not provide insulation on the economizing piping package. This insulation must be field provided and field installed.

· Trane does not provide condensate overflow protection of the waterside economizer. This must be field provided and installed.

8. Field pipe the drain lines of the waterside economizer and water-source heat pump together prior to installing a condensate trap for proper trapping of condensation (see Figure 38, p. 47). The vertical units will be piped similar to the horizontal units.

Figure 43. Step 8

Installation

Table 31. Economizer part numbers

Supply-Air Arrangement

Unit

Part Number

Left Supply Right Supply

EXVK009-012
EXVK015
EXVK018-024, DXVK024
EXVK030-036, DXVK036
EXVK042-048, DXVK048
EXVK060-070, DXVK060-070
EXVK009-012
EXVK015
EXVK018-024, DXVK024
EXVK030-036, DXVK036
EXVK042-048, DXVK048
EXVK060-070, DXVK060-070

WSHPECN00002 WSHPECN00003 WSHPECN00004 WSHPECN00005 WSHPECN00006 WSHPECN00007 WSHPECN00009 WSHPECN00010 WSHPECN00011 WSHPECN00012 WSHPECN00013 WSHPECN00014

WSHP-SVX019A-EN

49

Waterside Economizer Start-Up Sequence

1. Set the thermostat to the highest position.
2. Set the thermostat system switch to COOL with the fan control to AUTO. The compressor should NOT run.
3. Reduce the thermostat setting until the compressor, reversing valve, solenoid valve, and loop pump are energized. Adjust water flow utilizing pressure/ temperature plugs and comparing to tables contained in specification sheet data. Water leaving the heat exchanger should be warmer than the entering water temperature (approximately 9 to 12ºF); blower operation should be smooth; compressor and blower amps should be within data plate ratings; the suction line should be cool with no frost observed in the refrigerant circuit.
4. Check the cooling refrigerant pressures against values in “,”.
Note: If cooling mode is activated, and the entering water temperature of the heat pump falls below 55ºF, the 2-position, water side economizing valve will become energized (open) and compressor operation will halt allowing for free cooling in the space.
5. Turn the thermostat system switch to the OFF position. Unit should stop running and the reversing valve should de-energize.

6. Leave unit off for approximately FIVE minutes to allow for pressure equalization.
7. Turn the thermostat to the lowest setting.
8. Set the thermostat system switch to the HEAT position.
9. Adjust the temperature setting upward until the unit is energized. Warm air should blow from the register. A water temperature decrease of approximately 5 to 9°F leaving the heat exchanger should be noted. The blower and compressor operation should be smooth with no frost observed in the refrigeration circuit.
10. Check the heating refrigerant pressures against values in “,”.
Note: For units with boilerless electric heat option: In heating mode, if the entering water temperature of the heat pump falls below 45ºF, the electric heater will be energized, and compressor operation will halt. Once the entering water temperature rises above 50ºF, the boilerless controls returns the unit.
11. Set the thermostat to maintain the desired space temperature.
12. Instruct the owner on system operation.

Table 32. Waterside economizing three-way valve specifications (DXHK/DXVK units)

Unit Size

Valve Conn. Size

Valve Pres. Rating

DXHK/DXVK 024

3/4 FPT

600 psi

DXHK/DXVK 036-070

1 FPT

600 psi

Valve Close-off pressure 200 psi
200 psi

Valve Temp. Range

Actuator

0ºF to 212ºF -18ºC to 121ºC
0ºF to 212ºF -18ºC to 121ºC

Non-spring return type 24 Vac +/- 20%
135 second stroke time 24 Cv at full port
Non-spring return type 24 Vac +/- 20%
135 second stroke time 30 Cv at full port

Note: The valve body is constructed from forged brass with nickel plating, with the ball and stem constructed of stainless steel. For other information pertaining to the economizing water valve, see the valve’s data plate.

Table 33. Waterside economizing three-way valve specifications (EXHK/EXVK units)

Unit Size

Valve Conn. Size

Valve Pres. Rating

Valve Close-off pressure

Valve Temp. Range

EXHK 009-015

1/2 FPT

600 psi

200 psi

0°F to 250°F -18°C to 121°C

EXHK 018-036 EXVK 009-024

3/4 FPT

600 psi

200 psi

0°F to 250°F -18°C to 121°C

Actuator
Non-spring return type 24 Vac +/- 20%
135 second stroke time 10 Cv at full port
Non-spring return type 24 Vac +/- 20%
135 second stroke time 24 Cv at full port

50

WSHP-SVX019A-EN

Waterside Economizer Start-Up Sequence

Table 33. Waterside economizing three-way valve specifications (EXHK/EXVK units) (continued)

Unit Size

Valve Conn. Size

Valve Pres. Rating

EXHK 042-070 EXVK 030-070

1 FPT

600 psi

Valve Close-off pressure
200 psi

Valve Temp. Range

Actuator

0°F to 250°F -18°C to 121°C

Non-spring return type 24 Vac +/- 20%
135 second stroke time 30 Cv at full port

Note: The valve body is constructed from forged brass with nickel plating, with the ball and stem constructed of stainless steel. For other information pertaining to the economizing water valve, see the valve’s data plate.

WSHP-SVX019A-EN

51

Electrical Data

Table 34. Electrical data – 0.75 to 6 tons, EX*009-070

Model No.

Unit Volts

Total Unit FLA

Comp RLA

Comp LRA

Blower Motor Blower Motor

FLA

HP

Minimum Circuit
Ampacity

EXV/H009

208-230/60/1

4.8

4.2

27.0

0.6

EXV/H009

265/60/1

3.3

2.8

22.0

0.5

EXV/H012

208-230/60/1

6.8

5.8

27.0

1.0

EXV/H012

265/60/1

4.7

3.9

32.0

0.8

EXV/H015

208-230/60/1

12.8

11.8

33.0

1.0

EXV/H015

265/60/1

6.9

6.1

37.0

0.8

EXV/H018

208-230/60/1

16.3

14.8

35.0

1.5

EXV/H018

265/60/1

8.6

7.3

40.0

1.3

EXV/H024

208-230/60/1

13.3

11.4

64.4

1.9

EXV/H024

265/60/1

12.0

10.3

60.5

1.7

EXV/H024

208-230/60/3

9.6

7.7

59.9

1.9

EXV/H024

460/60/3

4.8

3.8

32.4

1.0

EXV/H030

208-230/60/1

14.5

12.7

75.6

1.8

EXV/H030

265/60/1

13.1

11.5

84.0

1.6

EXV/H030

208-230/60/3

11.4

9.6

67.7

1.8

EXV/H030

460/60/3

5.4

4.5

38.1

0.9

EXV/H036

208-230/60/1

16.1

13.5

82.5

2.6

EXV/H036

265/60/1

14.4

12.2

83.0

2.2

EXV/H036

208-230/60/3

15.4

12.8

97.5

2.6

EXV/H036

460/60/3

6.4

5.1

44.3

1.3

EXV/H042

208-230/60/1

17.4

14.7

109.0

2.7

EXV/H042

208-230/60/3

14.9

12.2

102.8

2.7

EXV/H042

460/60/3

7.2

5.8

50.0

1.4

EXV/H048

208-230/60/1

21.7

18.6

123.0

3.1

EXV/H048

208-230/60/3

15.9

12.8

102.8

3.1

EXV/H048

460/60/3

7.4

5.8

50.0

1.6

EXV/H060

208-230/60/1

26.6

21.8

143.0

4.8

EXV/H060

208-230/60/3

20.8

16.0

156.4

4.8

EXV/H060

460/60/3

10.1

7.7

69.0

2.4

EXV/H070

208-230/60/1

29.7

23.7

157.0

6.0

EXV/H070

208-230/60/3

22.0

16.0

156.4

6.0

EXV/H070

460/60/3

10.1

7.1

69.0

3.0

1/3

6/6

1/3

5

1/3

9/9

1/3

6

1/3

16/16

1/3

9

1/2

21/21

1/2

11

1/2

17/17

1/2

15

1/2

12/12

1/2

6

3/4

18/18

3/4

16

3/4

14/14

3/4

7

3/4

20/20

3/4

18

3/4

19/19

1

8

3/4

22/22

3/4

18/18

1

9

1

27/27

1

20/20

1

9

1

32/32

1

25/25

1

12

1

36/36

1

26/26

1

12

Maximum Overcurrent Protective
Device 15/15
15 15/15
15 25/25
15 30/30
15 25/25
20 15/15
15 30/30
25 20/20
15 30/30
25 30/30
15 35/35 30/30
15 40/40 30/30
15 50/50 40/40
15 50/50 40/40
15

52

WSHP-SVX019A-EN

Electrical Data

Table 35. Electrical data – 2 to 6 tons, DX*024-070

Model No.

Unit Volts

Total Unit FLA

Comp RLA

Comp LRA

Blower Motor Blower Motor

FLA

HP

Minimum Circuit
Ampacity

DXV/H024

208-230/60/1

12.2

10.3

62.0

1.9

DXV/H024

265/60/1

9.5

7.8

52.0

1.7

DXV/H024

208-230/60/3

8.2

6.3

56.0

1.9

DXV/H024

460/60/3

4.8

3.8

29.0

1.0

DXV/H036

208-230/60/1

17.1

14.6

82.0

2.5

DXV/H036

265/60/1

12.4

10.2

60.0

2.2

DXV/H036

208-230/60/3

10.4

7.9

66.0

2.5

DXV/H036

460/60/3

5.6

4.3

28.0

1.3

DXV/H048

208-230/60/1

21.3

18.2

106.0

3.1

DXV/H048

208-230/60/3

14.6

11.5

114.0

3.1

DXV/H048

460/60/3

8.9

7.4

56.0

1.5

DXV/H060

208-230/60/1

24.9

20.1

141.0

4.8

DXV/H060

208-230/60/3

19.5

14.7

113.4

4.8

DXV/H060

460/60/3

9.4

7.0

54.8

2.4

DXV/H070

208-230/60/1

31.3

25.2

147.3

6.1

DXV/H070

208-230/60/3

19.9

13.8

161.0

6.1

DXV/H070

460/60/3

10.0

6.9

58.0

3.1

1/2

15/15

1/2

12

1/2

10/10

1/2

6

3/4

21/21

3/4

15

3/4

13/13

1

7

1

26/26

1

18/18

1

11

1

30/30

1

24/24

1

12

1

38/38

1

24/24

1

12

Maximum Overcurrent Protective
Device 25/25
15 15/15
15 35/35
25 20/20
15 40/40 25/25
15 45/45 35/35
15 60/60 35/35
15

Table 36. EXV/H and DXV/H electric duct heater data (0.75 to 6 tons)

MODEL

EH Size

Volts

kW

Amps

EXV/H009

Medium

208-230/60/1

2.0/2.5

9.8/10.9

EXV/H009

Medium

265/60/1

2.3

8.6

EXV/H012

Medium

208-230/60/1

2.0/2.5

9.8/10.9

EXV/H012

Medium

265/60/1

2.3

8.6

EXV/H015

Medium

208-230/60/1

2.0/2.5

9.8/10.9

EXV/H015

Medium

265/60/1

2.3

8.6

EXV/H018

Medium

208-230/60/1

3.3/4.0

15.7/17.4

EXV/H018

Medium

265/60/1

3.7

13.8

EXV/H024

Medium

208-230/60/1

3.3/4.0

15.7/17.4

EXV/H024

Medium

265/60/1

3.7

13.8

EXV/H024

Medium

208-230/60/3

3.3/4.0

9.1/10.1

EXV/H024

Medium

460/60/3

3.7

4.6

EXV/H030

Medium

208-230/60/1

4.1/5.0

19.7/21.7

EXV/H030

Medium

265/60/1

4.6

17.3

EXV/H030

Medium

208-230/60/3

4.1/5.0

11.4/12.6

EXV/H030

Medium

460/60/3

4.6

5.8

EXV/H036

Low

208-230/60/1

4.9/6.0

23.6/26.1

EXV/H036 EXV/H036

Medium High

208-230/60/1 208-230/60/1

8.2/10.0 12.3/15.0

39.3/43.5 59.0/65.2

EXV/H036

Low

265/60/1

5.5

20.7

EH MOP 15 15 15 15 15 15 25 20 25 20 15 15 30 25 20 15 35 60 90 30

WSHP-SVX019A-EN

53

Electrical Data

Table 36. EXV/H and DXV/H electric duct heater data (0.75 to 6 tons) (continued)

MODEL

EH Size

Volts

kW

EXV/H036

Medium

265/60/1

9.2

EXV/H036

High

265/60/1

13.7

Amps 34.5 51.8

EH MOP 50 70

EXV/H036

Low

208-230/60/3

4.9/6.0

13.6/15.1

20

EXV/H036

Medium

208-230/60/3

8.2/10.0

22.7/25.1

35

EXV/H036

High

208-230/60/3

12.3/15.0

34.1/37.7

50

EXV/H036

Low

460/60/3

5.5

6.9

15

EXV/H036

Medium

460/60/3

9.2

11.5

20

EXV/H036

High

460/60/3

13.8

17.3

25

EXV/H036

High

575/60/3

13.7

13.8

35

EXV/H042

Low

208-230/60/1

4.9/6.0

23.6/26.1

35

EXV/H042

Medium

208-230/60/1

8.2/10.0

39.3/43.5

60

EXV/H042

High

208-230/60/1

12.3/15.0

59.0/65.2

90

EXV/H042

Low

208-230/60/3

4.9/6.0

13.6/15.1

20

EXV/H042

Medium

208-230/60/3

8.2/10.0

22.7/25.1

35

EXV/H042

High

208-230/60/3

12.3/15.0

34.1/37.7

50

EXV/H042

Low

460/60/3

5.5

6.9

15

EXV/H042

Medium

460/60/3

9.2

11.5

20

EXV/H042

High

460/60/3

13.8

17.3

25

EXV/H042

High

575/60/3

13.7

13.8

35

EXV/H048

Low

208-230/60/1

4.9/6.0

23.6/26.1

35

EXV/H048

Medium

208-230/60/1

8.2/10.0

39.3/43.5

60

EXV/H048

High

208-230/60/1

12.3/15.0

59.0/65.2

90

EXV/H048

Low

208-230/60/3

4.9/6.0

13.6/15.1

20

EXV/H048

Medium

208-230/60/3

8.2/10.0

22.7/25.1

35

EXV/H048

High

208-230/60/3

12.3/15.0

34.1/37.7

50

EXV/H048

Low

460/60/3

5.5

6.9

15

EXV/H048

Medium

460/60/3

9.2

11.5

20

EXV/H048

High

460/60/3

13.8

17.3

25

EXV/H048

High

575/60/3

13.7

13.8

35

EXV/H060

Low

208-230/60/1

4.9/6.0

23.6/26.1

35

EXV/H060

Medium

208-230/60/1

8.2/10.0

39.3/43.5

60

EXV/H060

High

208-230/60/1

12.3/15.0

59.0/65.2

90

EXV/H060

Low

208-230/60/3

4.9/6.0

13.6/15.1

20

EXV/H060

Medium

208-230/60/3

8.2/10.0

22.7/25.1

35

EXV/H060

High

208-230/60/3

12.3/15.0

34.1/37.7

50

EXV/H060

Low

460/60/3

5.5

6.9

15

EXV/H060

Medium

460/60/3

9.2

11.5

20

EXV/H060

High

460/60/3

13.8

17.3

25

EXV/H060

High

575/60/3

13.7

13.8

35

EXV/H070

Low

208-230/60/1

4.9/6.0

23.6/26.1

35

EXV/H070

Medium

208-230/60/1

8.2/10.0

39.3/43.5

60

54

WSHP-SVX019A-EN

Table 36. EXV/H and DXV/H electric duct heater data (0.75 to 6 tons) (continued)

MODEL EXV/H070

EH Size High

Volts 208-230/60/1

kW 12.3/15.0

Amps 59.0/65.2

EH MOP 90

EXV/H070

Low

208-230/60/3

4.9/6.0

13.6/15.1

20

EXV/H070

Medium

208-230/60/3

8.2/10.0

22.7/25.1

35

EXV/H070

High

208-230/60/3

12.3/15.0

34.1/37.7

50

EXV/H070

Low

460/60/3

5.5

6.9

15

EXV/H070

Medium

460/60/3

9.2

11.5

20

EXV/H070

High

460/60/3

13.8

17.3

25

EXV/H070

High

575/60/3

13.7

13.8

35

DXV/H024

Medium

208-230/60/1

3.3/4.0

15.7/17.4

25

DXV/H024

Medium

265/60/1

3.7

13.8

20

DXV/H024

Medium

208-230/60/3

3.3/4.0

9.1/10.1

15

DXV/H024

Medium

460/60/3

3.7

4.6

15

DXV/H036

Low

208-230/60/1

4.9/6.0

23.6/26.1

35

DXV/H036

Medium

208-230/60/1

8.2/10.0

39.3/43.5

60

DXV/H036

High

208-230/60/1

12.3/15.0

59.0/65.2

90

DXV/H036

Low

265/60/1

5.5

20.7

30

DXV/H036

Medium

265/60/1

9.2

34.5

50

DXV/H036

High

265/60/1

13.7

51.8

70

DXV/H036

Low

208-230/60/3

4.9/6.0

13.6/15.1

20

DXV/H036

Medium

208-230/60/3

8.2/10.0

22.7/25.1

35

DXV/H036

High

208-230/60/3

12.3/15.0

34.1/37.7

50

DXV/H036

Low

460/60/3

5.5

6.9

15

DXV/H036

Medium

460/60/3

9.2

11.5

20

DXV/H036

High

460/60/3

13.8

17.3

25

DXV/H036

High

575/60/3

13.7

13.8

35

DXV/H048

Low

208-230/60/1

4.9/6.0

23.6/26.1

35

DXV/H048

Medium

208-230/60/1

8.2/10.0

39.3/43.5

60

DXV/H048

High

208-230/60/1

12.3/15.0

59.0/65.2

90

DXV/H048

Low

208-230/60/3

4.9/6.0

13.6/15.1

20

DXV/H048

Medium

208-230/60/3

8.2/10.0

22.7/25.1

35

DXV/H048

High

208-230/60/3

12.3/15.0

34.1/37.7

50

DXV/H048

Low

460/60/3

5.5

6.9

15

DXV/H048

Medium

460/60/3

9.2

11.5

20

DXV/H048

High

460/60/3

13.8

17.3

25

DXV/H048

High

575/60/3

13.7

13.8

35

DXV/H060

Low

208-230/60/1

4.9/6.0

23.6/26.1

35

DXV/H060

Medium

208-230/60/1

8.2/10.0

39.3/43.5

60

DXV/H060

High

208-230/60/1

12.3/15.0

59.0/65.2

90

DXV/H060

Low

208-230/60/3

4.9/6.0

13.6/15.1

20

DXV/H060

Medium

208-230/60/3

8.2/10.0

22.7/25.1

35

DXV/H060

High

208-230/60/3

12.3/15.0

34.1/37.7

50

WSHP-SVX019A-EN

Electrical Data
55

Electrical Data

Table 36. EXV/H and DXV/H electric duct heater data (0.75 to 6 tons) (continued)

MODEL

EH Size

Volts

kW

DXV/H060

Low

460/60/3

5.5

Amps 6.9

EH MOP 15

DXV/H060

Medium

460/60/3

9.2

11.5

20

DXV/H060

High

460/60/3

13.8

17.3

25

DXV/H060

High

575/60/3

13.7

13.8

35

DXV/H070

Low

208-230/60/1

4.9/6.0

23.6/26.1

35

DXV/H070

Medium

208-230/60/1

8.2/10.0

39.3/43.5

60

DXV/H070

High

208-230/60/1

12.3/15.0

59.0/65.2

90

DXV/H070

Low

208-230/60/3

4.9/6.0

13.6/15.1

20

DXV/H070

Medium

208-230/60/3

8.2/10.0

22.7/25.1

35

DXV/H070

High

208-230/60/3

12.3/15.0

34.1/37.7

50

DXV/H070

Low

460/60/3

5.5

6.9

15

DXV/H070

Medium

460/60/3

9.2

11.5

20

DXV/H070

High

460/60/3

13.8

17.3

25

DXV/H070

High

575/60/3

13.7

13.8

35

Note: Electric heat performance table with heat rise data can be found in Installation Instructions (WSHPSVN011*-EN).

Table 37. Electrical data – minimum and maximum

Digit 8

Rated Voltage

Hz

4

460

60

7

265

60

A

208-230

60

B

208-230

60

Ph

Minimum Utilization Voltage

3

414

1

239

1

197

3

187

Maximum Utilization Voltage 506 292 253 253

56

WSHP-SVX019A-EN

Pre-Start Checklist
Before energizing the unit, the following system devices must be checked:
· Is the high voltage power supply correct and in accordance with the nameplate ratings?
· Is phasing of the unit correct per compressor rotation (scroll compressor only)?
· Is the field wiring and circuit protection the correct size?
· Is the low voltage control circuit wiring correct per the unit wiring diagram?
· Is the piping system clean/complete and correct? (A recommendation of all system flushing of debris from the water-to-refrigerant heat exchanger, along with air purging from the water-to-refrigerant heat exchanger be done in accordance with the Closed-Loop/Ground Source Heat Pump Systems Installation Guide).
· Is vibration isolation provided? (i.e. unit isolation pad, hose kits)
· Is unit serviceable? (See clearance specifications in Unit Dimensions and Weights).

· Are the low/high-side pressure temperature caps secure and in place?
· Are all the unit access panels secure and in place?
· Is the thermostat in the OFF position?
· Is the water flow established and circulating through all the units?
· Is the duct work correctly sized, run, taped, insulated and weather proofed with proper unit arrangement?
· Is the condensate line properly sized, run, trapped, pitched and primed?
· Is the zone sensor correctly wired and in a good location?
· Does the indoor blower turn freely without rubbing?
· Has all work been done in accordance with applicable local and national codes?
· Has heat transfer fluid been added in the proper mix to prevent freezing in closed system application?

WSHP-SVX019A-EN

57

Start-Up

Initial Unit Start-Up
Note: Start-up with the heat pump thermostat is included below:
1. Set the thermostat to the highest position.
2. Set the thermostat system switch to COOL with the fan control to AUTO. The compressor should NOT run.
3. Reduce the thermostat setting until the compressor, reversing valve, solenoid valve, and loop pump are energized. Adjust water flow utilizing pressure/ temperature plugs and comparing to tables contained in specification sheet data.
4. Water leaving the heat exchanger should be warmer than the entering water temperature (approximately 912ºF); blower operation should be smooth; compressor and blower amps should be within data plate ratings; the suction line should be cool with no frost observed in the refrigerant circuit.
5. Check the cooling refrigerant pressures against values in “,”.
6. Turn the thermostat system switch to the OFF position. Unit should stop running and the reversing valve should de-energize.
7. Leave unit off for approximately FIVE minutes to allow for pressure equalization.
8. Turn the thermostat to the lowest setting.
9. Set the thermostat system switch to the HEAT position.
10. Adjust the temperature setting upward until the unit is energized. Warm air should blow from the register. A water temperature decrease of approximately 5-9ºF leaving the heat exchanger should be noted. The blower and compressor operation should be smooth with no frost observed in the refrigeration circuit.
11. Check the heating refrigerant pressures against values in “,”.
12. Set the thermostat to maintain the desired space temperature.
13. Instruct the owner on system operation.

Table 38. Checklist

MODE

Heat

Cool

Entering fluid temperature

___F

___F

Leaving fluid temperature

___F

___F

Temperature differential

___F

___F

Return-air temperature DB/WB

___F

___F

Table 38. Checklist (continued)

MODE
Supply-air temperature DB/WB

Heat ___F

Temperature differential
Water coil heat exchanger (Water Pressure IN)

___F ____PSIG

Water coil heat exchanger (Water Pressure OUT)

____PSIG

Pressure Differential COMPRESSOR Amps

_____PSIG

Volts
Discharge line temperature (after 10 minutes)

___F

Cool F F ____PSIG ____PSIG __PSIG
F

Start-Up Checklist and Log
Installing Contractor: Use this checklist to thoroughly check-out the system and units before and during start-up. (This form need not be returned to the factory unless requested during technical service support).
Job Name:
Model Number:
Date:
Serial Number:
To minimize troubleshooting and costly system failures, complete the following checks and data entries before the system is put into full operation.
Operating Pressures
There are many variables (airflow, air temperatures) in an air conditioning system that will affect operating refrigerant pressures and temperatures. The charts below shows approximate conditions and is based on air flow at the rated SCFM, entering air at 80.6°F (DB), 66.2°F (WB) in cooling, 68°F (DB) in heating. (+)Heating data with 35°F EWT is based on the use of an anti-freeze solution having a freezing point 20°F lower than the minimum expected entering temperature.

58

WSHP-SVX019A-EN

Table 39. Operating pressures in cooling/heating for DX* units

Model

Entering Water Temp
Entering Water
Temp (°F)

DXV/H024

32

DXV/H024

32

DXV/H024

45

DXV/H024

45

DXV/H024

55

DXV/H024

55

DXV/H024

68

DXV/H024

68

DXV/H024

75

DXV/H024

75

DXV/H024

86

DXV/H024

86

DXV/H024

95

DXV/H024

95

DXV/H036

32

DXV/H036

32

DXV/H036

45

DXV/H036

45

DXV/H036

55

DXV/H036

55

DXV/H036

68

DXV/H036

68

DXV/H036

75

DXV/H036

75

DXV/H036

86

DXV/H036

86

DXV/H036

95

DXV/H036

95

DXV/H048

32

DXV/H048

32

DXV/H048

45

DXV/H048

45

DXV/H048

55

DXV/H048

55

DXV/H048

68

DXV/H048

68

DXV/H048

75

DXV/H048

75

Water Flow (GPM)
4.80 6.00 4.80 6.00 4.80 6.00 4.80 6.00 4.80 6.00 4.80 6.00 4.80 6.00 7.20 9.00 7.20 9.00 7.20 9.00 7.20 9.00 7.20 9.00 7.20 9.00 7.20 9.00 9.60 12.00 9.60 12.00 9.60 12.00 9.60 12.00 9.60 12.00

Operating Data Cooling

Heating

Suction Discharge Water Air Temp Suction Discharge Water Air Temp

Pressure Pressure Temp Drop (°F Pressure Pressure Temp Rise (°F

(psig) (pgig) Rise (°F) DB)

(psig) (psig) Drop (°F) DB)

— — 102-124 101-123 104-127 104-127 106-130 106-130 110-135 110-135 113-138 113-138 114-140 114-140 — — 112-137 112-137 113-138 113-138 114-140 114-140 116-142 116-142 118-145 118-144 120-146 120-146 — — 105-129 105-128 108-131 107-131 110-134 110-134 114-139 114-139

— — 153-187 147-180 180-220 174-212 219-267 212-259 240-293 233-285 280-342 273-333 316-386 308-376 — — 151-185 146-178 178-217 172-210 216-264 210-257 237-290 231-282 275-337 269-329 310-379 304-371 — — 164-201 159-194 191-234 186-227 232-283 226-276 253-309 247-301

— — 12-14 9-12 12-14 9-11 11-14 9-11 11-14 9-11 12-14 9-11 11-14 9-11 — — 11-13 8-10 10-13 8-10 10-12 8-10 10-12 8-10 10-12 8-10 10-12 8-9 — — 11-13 9-11 11-13 8-10 10-13 8-10 10-13 8-10

— — 24-29 24-29 23-28 23-28 22-27 22-27 22-27 22-27 22-27 22-27 21-26 21-26 — — 22-27 22-27 22-27 22-27 21-26 21-26 21-26 21-26 21-25 21-25 20-25 20-25 — — 22-27 23-28 22-27 22-27 21-26 21-26 21-26 21-26

66-80 67-82 83-101 85-104 99-120 102-124 113-138 117-143 126-154 130-159 148-181 154-188
— — 69-85 71-86 87-106 89-109 103-126 106-129 124-151 128-156 138-169 143-174 163-199 169-207 — — 61-74 62-76 75-92 77-94 90-110 93-113 108-132 111-136 120-147 124-152

253-309 255-311 277-338 279-341 292-357 295-361 318-389 322-394 330-404 335-409 349-427 354-433
— — 235-288 237-289 263-322 265-324 279-340 281-343 301-368 304-372 312-381 315-385 327-400 329-402 — — 233-285 235-287 251-307 253-309 265-324 267-327 281-344 284-347 292-357 295-360

6-7 5-6 7-9 6-7 8-10 7-8 10-12 8-10 11-13 9-11 12-15 10-12 — — 5-6 4-5 6-8 5-6 7-9 6-7 9-11 7-9 9-12 8-9 11-13 9-10 — — 5-6 4-5 6-7 5-6 7-8 6-7 8-10 7-8 9-11 7-9

20-24 20-24 25-30 26-31 28-35 29-36 33-40 34-41 36-44 37-45 40-49 41-50
— — 18-22 18-22 22-27 23-28 25-31 26-32 29-36 30-37 31-38 32-39 34-42 35-42 — — 17-21 18-22 21-26 22-27 24-30 25-31 28-35 29-36 31-38 31-38

WSHP-SVX019A-EN

Start-Up
59

Start-Up

Table 39. Operating pressures in cooling/heating for DX* units (continued)

Model

Entering Water Temp
Entering Water
Temp (°F)

DXV/H048

86

DXV/H048

86

DXV/H048

95

DXV/H048

95

DXV/H060

32

DXV/H060

32

DXV/H060

45

DXV/H060

45

DXV/H060

55

DXV/H060

55

DXV/H060

68

DXV/H060

68

DXV/H060

75

DXV/H060

75

DXV/H060

86

DXV/H060

86

DXV/H060

95

DXV/H060

95

DXV/H070

32

DXV/H070

32

DXV/H070

45

DXV/H070

45

DXV/H070

55

DXV/H070

55

DXV/H070

68

DXV/H070

68

DXV/H070

75

DXV/H070

75

DXV/H070

86

DXV/H070

86

DXV/H070

95

DXV/H070

95

Water Flow (GPM)
9.60 12.00 9.60 12.00 12.00 15.00 12.00 15.00 12.00 15.00 12.00 15.00 12.00 15.00 12.00 15.00 12.00 15.00 14.00 17.50 14.00 17.50 14.00 17.50 14.00 17.50 14.00 17.50 14.00 17.50 14.00 17.50

Operating Data Cooling

Heating

Suction Discharge Water Air Temp Suction Discharge Water Air Temp

Pressure Pressure Temp Drop (°F Pressure Pressure Temp Rise (°F

(psig) (pgig) Rise (°F) DB)

(psig) (psig) Drop (°F) DB)

117-143 116-142 118-144 118-144
— — 111-136 111-136 113-138 113-138 114-140 114-140 117-144 117-143 120-146 120-146 121-148 121-148 — — 102-125 102-125 103-126 103-126 105-129 105-128 111-136 111-136 114-139 114-139 115-141 115-141

293-358 286-349 329-402 322-394
— — 161-197 157-191 189-231 183-224 229-280 223-273 248-303 242-296 286-349 280-342 322-393 315-385 — — 151-185 146-179 178-217 173-211 217-265 211-258 240-294 235-287 277-339 271-331 313-382 306-374

10-12 8-10 10-12 8-10
— — 10-13 8-10 10-13 8-10 10-12 8-10 10-12 8-10 10-12 8-10 10-12 8-9 — — 10-12 8-10 10-12 8-10 10-12 8-10 10-12 8-10 10-12 8-10 10-12 8-10

21-25 21-25 20-25 20-25
— — 22-27 22-27 21-26 21-26 21-25 21-25 21-25 21-25 20-25 20-25 20-24 20-24 — — 21-26 21-26 21-26 21-26 20-25 20-25 21-25 21-25 20-25 20-25 20-24 20-24

143-174 148-181
— — 65-80 67-82 80-98 83-101 96-118 99-121 116-142 120-147 130-159 134-164 154-188 159-194 — — 66-81 68-83 82-100 84-103 98-120 101-123 113-138 116-142 126-154 130-159 149-182 154-188 — —

308-376 311-380
— — 234-286 236-288 253-309 254-311 266-325 268-328 286-350 289-353 296-362 299-366 313-382 316-386 — — 249-304 251-306 270-330 272-333 285-348 287-351 302-369 305-373 313-382 316-386 330-403 333-407 — —

10-13 8-10
— — 5-6 4-5 6-7 5-6 7-9 6-7 8-10 7-8 9-11 7-9 10-13 8-10 — — 6-7 5-6 6-8 5-6 8-9 6-8 9-11 7-9 9-12 8-10 11-13 9-11 — —

34-42 35-43
— — 17-21 18-22 21-26 22-27 24-30 25-30 28-35 29-35 30-37 31-38 34-41 34-42 — — 19-23 19-24 23-29 24-29 27-33 27-33 30-37 31-37 32-40 33-40 36-44 37-45 — —

60

WSHP-SVX019A-EN

Table 40. Operating pressures in cooling/heating for EX* units

Model

Entering Water Temp
Entering Water
Temp (°F)

EXV/H009

32

EXV/H009

32

EXV/H009

45

EXV/H009

45

EXV/H009

55

EXV/H009

55

EXV/H009

68

EXV/H009

68

EXV/H009

75

EXV/H009

75

EXV/H009

86

EXV/H009

86

EXV/H009

95

EXV/H009

95

EXV/H012

32

EXV/H012

32

EXV/H012

45

EXV/H012

45

EXV/H012

55

EXV/H012

55

EXV/H012

68

EXV/H012

68

EXV/H012

75

EXV/H012

75

EXV/H012

86

EXV/H012

86

EXV/H012

95

EXV/H012

95

EXV/H015

32

EXV/H015

32

EXV/H015

45

EXV/H015

45

EXV/H015

55

EXV/H015

55

EXV/H015

68

EXV/H015

68

EXV/H015

75

EXV/H015

75

Water Flow (GPM)
1.80 2.25 1.80 2.25 1.80 2.25 1.80 2.25 1.80 2.25 1.80 2.25 1.80 2.25 2.40 3.00 2.40 3.00 2.40 3.00 2.40 3.00 2.40 3.00 2.40 3.00 2.40 3.00 3.00 3.75 3.00 3.75 3.00 3.75 3.00 3.75 3.00 3.75

Operating Data Cooling

Heating

Suction Discharge Water Air Temp Suction Discharge Water Air Temp

Pressure Pressure Temp Rise Drop (°F Pressure Pressure Temp Rise (°F

(psig)

(pgig)

(°F)

DB)

(psig)

(psig) Drop (°F) DB)

— — 108-132 108-131 109-134 109-134 112-137 112-137 118-144 117-144 122-149 122-149 124-152 124-151 — — 105-128 105-128 107-131 107-131 110-134 110-134 116-141 115-141 121-148 121-147 123-150 122-150 — — 102-125 102-125 104-127 104-127 106-130 106-130 110-134 110-134

— — 147-180 142-173 176-216 170-208 215-263 210-256 237-289 230-282 276-338 270-330 310-379 304-371 — — 152-186 146-179 182-222 176-216 220-269 215-263 239-293 233-285 276-338 270-330 309-378 303-370 — — 157-192 152-185 187-228 181-221 225-275 219-268 246-300 239-292

— — 11-13 9-11 11-13 9-11 11-13 8-10 11-13 8-10 10-13 8-10 10-12 8-10 — — 11-13 9-11 11-13 9-11 10-13 8-10 11-13 8-10 10-13 8-10 10-12 8-10 — — 12-14 9-12 12-14 9-11 12-14 9-11 12-14 9-11

— — 23-28 23-28 23-28 23-28 22-27 22-27 22-27 22-27 21-26 21-26 21-25 21-25 — — 23-28 23-28 22-27 22-27 22-26 22-26 22-26 22-26 21-26 21-26 20-25 21-25 — — 24-29 24-29 23-29 23-29 23-28 23-28 23-28 23-28

67-82 69-84 86-105 88-108 102-125 105-129 121-148 125-153 135-165 139-170 158-193 164-201
— — 68-83 69-85 88-107 90-110 104-128 107-131 121-148 125-153 135-165 139-170 158-193 164-200 — — 64-79 66-81 82-100 85-103 98-120 101-123 115-141 119-145 128-157 133-162

225-274 226-276 243-297 245-299 256-313 258-316 273-334 276-337 284-347 287-351 300-367 304-372
— — 233-285 234-286 251-307 253-310 266-325 269-328 284-347 287-351 296-361 300-366 316-386 320-392 — — 241-294 242-296 262-320 264-323 278-340 281-344 294-359 298-364 307-375 311-380

5-6 4-5 6-8 5-6 7-9 6-7 9-11 7-9 10-12 8-10 11-14 9-11 — — 5-6 4-5 6-8 5-6 7-9 6-7 9-11 7-9 10-12 8-10 12-14 10-12 — — 6-7 5-6 7-8 6-7 8-10 7-8 9-11 8-9 10-13 8-10

17-20 17-21 22-27 22-27 25-31 26-31 30-36 30-37 32-39 33-40 35-43 36-44
— — 17-21 18-22 23-28 23-28 26-32 27-33 31-38 32-39 33-41 34-42 37-46 38-47 — — 20-24 20-25 25-30 25-31 28-34 29-35 32-39 33-40 35-43 36-44

WSHP-SVX019A-EN

Start-Up
61

Start-Up

Table 40. Operating pressures in cooling/heating for EX* units (continued)

Model

Entering Water Temp
Entering Water
Temp (°F)

EXV/H015

86

EXV/H015

86

EXV/H015

95

EXV/H015

95

EXV/H018

32

EXV/H018

32

EXV/H018

45

EXV/H018

45

EXV/H018

55

EXV/H018

55

EXV/H018

68

EXV/H018

68

EXV/H018

75

EXV/H018

75

EXV/H018

86

EXV/H018

86

EXV/H018

95

EXV/H018

95

EXV/H024

32

EXV/H024

32

EXV/H024

45

EXV/H024

45

EXV/H024

55

EXV/H024

55

EXV/H024

68

EXV/H024

68

EXV/H024

75

EXV/H024

75

EXV/H024

86

EXV/H024

86

EXV/H024

95

EXV/H024

95

EXV/H030

32

EXV/H030

32

EXV/H030

45

EXV/H030

45

EXV/H030

55

EXV/H030

55

Water Flow (GPM)
3.00 3.75 3.00 3.75 3.60 4.50 3.60 4.50 3.60 4.50 3.60 4.50 3.60 4.50 3.60 4.50 3.60 4.50 4.80 6.00 4.80 6.00 4.80 6.00 4.80 6.00 4.80 6.00 4.80 6.00 4.80 6.00 6.00 7.50 6.00 7.50 6.00 7.50

Operating Data Cooling

Heating

Suction Discharge Water Air Temp Suction Discharge Water Air Temp

Pressure Pressure Temp Rise Drop (°F Pressure Pressure Temp Rise (°F

(psig)

(pgig)

(°F)

DB)

(psig)

(psig) Drop (°F) DB)

113-139 113-138 115-141 115-140
— — 105-128 105-128 106-130 106-130 108-132 108-132 111-136 111-136 114-139 114-139 115-141 115-140 — — 102-125 102-124 103-126 103-126 105-128 105-128 108-133 108-132 111-136 111-136 112-137 112-137 — — 109-133 108-132 110-134 110-134

283-346 277-338 316-386 309-378
— — 150-184 144-177 177-216 170-208 214-262 208-254 234-286 227-278 271-332 264-323 304-372 297-363 — — 152-185 146-179 178-218 172-210 217-265 210-257 238-291 231-283 277-339 270-330 312-382 305-372 — — 154-188 148-181 180-220 174-213

11-14 9-11 11-14 9-11 — — 12-15 10-12 12-14 9-12 12-14 9-11 12-14 9-11 11-14 9-11 11-14 9-11 — — 12-14 9-12 12-14 9-11 11-14 9-11 12-14 9-11 11-14 9-11 11-14 9-11 — — 12-15 10-12 12-14 9-12

22-27 22-27 21-26 21-26
— — 24-29 24-29 23-28 23-29 22-27 22-27 22-27 22-27 21-26 21-26 20-25 20-25 — — 23-29 24-29 23-28 23-28 22-27 22-27 22-27 22-27 21-26 21-26 20-25 20-25 — — 24-29 24-30 24-29 24-29

151-184 156-191
— — 62-76 64-7

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Trane User Manuals

Related Manuals