YHDC SCT013G Split Core Current Transformer Owner’s Manual

July 8, 2024
YHDC

YHDC SCT013G Split Core Current Transformer

Specifications:

  • Characteristics : Safety lock buckle, easy installation, cable output
  • Electrical parameters:
    • Rated input: 5A, 10A, 15A, 20A, 25A, 30A, 50A, 60A, 100A
    • Rated output: 1V
    • Accuracy : 1%
    • Weight : 50g
    • Turns ratio: 1:2000
    • Sampling resistance : 10Ω
    • Length of cable : 100cm~105cm

Product Usage Instructions

Installation:

  1. Ensure the safety lock buckle is engaged before starting the installation process.
  2. Connect the cable output securely to the designated port on your device.
  3. Make sure the secondary is not allowed to short circuit during installation.

Electrical Connections:
When connecting the product, follow these steps:

  1. For voltage output type:
    • Connect the standard 3.5 audio plug to the corresponding port.
    • Output current should be within the specified range for optimal performance.
  2. For current output type:
    • Use the provided 3.5mm output for current output connections.
    • Avoid open circuit situations to prevent damage to the product.

Characteristic:
Safety lock buckle, easy installation, cable output

Technical index

  • Mounting type: Free hanging (In-Line)
  • Material of core: Ferrite
  • Applicable standards: GB20840-2014
  • Operating temperature: -25℃ ~ +70℃
  • Storage temperature: -30℃ ~ +90℃
  • Frequency range: 50Hz-1KHz
  • Dielectric strength: Input (bare conductor)/Output AC 3.5KV/1min 50Hz
  • Output/Housing AC 3.5KV/1min 50Hz

Electrical parameters

The following parameters are typical values. The actual values shall be subject to the actual measurement of the product

YHDC-SCT013G-Split-Core-Current-Transformer-FIG-
\(1\) YHDC-SCT013G-Split-Core-Current-
Transformer-FIG-  \(2\)

DIMENSION

YHDC-SCT013G-Split-Core-Current-Transformer-FIG-
\(3\)

FLOW CHART

YHDC-SCT013G-Split-Core-Current-Transformer-FIG-
\(4\) YHDC-SCT013G-Split-Core-Current-
Transformer-FIG-  \(5\) YHDC-SCT013G-Split-Core-
Current-Transformer-FIG-  \(6\)

FAQ

Q: Can I use the product without engaging the safety lock buckle?
A: No, it is essential to engage the safety lock buckle for safe operation of the product.

Q: What happens if the secondary is short-circuited?
A: Short-circuiting the secondary is not allowed as it may lead to product damage or malfunction.

Q: How should I handle the cable output during installation?
A: Ensure the cable output is securely connected and does not face any sharp bends or kinks to maintain proper functionality.