TRANE EXHK009 Water Source Heat Pump Axiom User Guide
- June 26, 2024
- Trane
Table of Contents
TRANE EXHK009 Water Source Heat Pump Axiom
Copyright
This document and the information in it are the property of Trane, and may not
be used or reproduced in whole or in part without written permission. Trane
reserves the right to revise this publication at any time, and to make changes
to its content without obligation to notify any person of such revision or
change.
Trademarks
All trademarks referenced in this document are the trademarks of their
respective owners.
List of options
Factory Installed Options | Field Installed Options |
---|---|
1-inch or 2-inch Ducted Filter Rack | 2-inch or 4-inch Ducted Filter Rack |
Air-Fi® Wireless Communications | Ducted Panel |
Deluxe 24V, Symbio™ 400-B Controls | Hose Kits (or ship separate hoses and |
valves)
Factory-mounted Isolation Valve| Low, Medium and High Electric Heat
Hot Gas Reheat| Pump Module
Matte or Foil Face Insulation| Pump Module Hose Kit
MERV 8 or 13 Filters| Thermostats or Zone Sensors
Polymer or Stainless Steel IAQ Drain Pan| Waterside Economizer
Recessed Unit Mounted Disconnect Switch|
Standard or Deluxe Sound Package
Table 2. General data – models EXHK009-024
Model EXHK | 009 | 012 | 015 | 018 | 024 |
---|---|---|---|---|---|
Unit size width x depth x height (in.) | 25.5 x 46 x 17.75 | 25.5 x 46 x 17.75 | |||
25.5 x 49 x 18.75 | 25.5 x 55 x 19.75 | 25.5 x 55 x 19.75 | |||
Compressor type | Rotary | Rotary | Rotary | Rotary | Scroll |
Net weight (lbs.) | 173 | 173 | 173 | 269 | 269 |
Ship weight (lbs.) | 297 | 297 | 297 | 393 | 393 |
Filter size nominal (in.) | 16 x 19 | 16 x 19 | 17 x 20 | 18 x 23 | 19 x 23 |
Water in/out size (FPT) | 0.5 | 0.5 | 0.75 | 0.75 | 0.75 |
Condensate size (NPTI) | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 |
Blower wheel Size (in.) | 9 x 8 | 9 x 8 | 10 x 8 | 10 x 9 | 10 x 9 |
Table 3. General data – models EXHK030-070
Model EXHK | 030 | 036 | 042 | 048 | 060 | 070 |
---|---|---|---|---|---|---|
Unit size width x depth x height (in.) | 28 x 68 x 21.75 | 28 x 68 x 21.75 | ||||
29.38 x 77.75 x 22.13 | 29.38 x 77.75 x 22.13 | 29.38 x 86.75 x 22.13 | 29.38 x |
86.75 x 22.13
Compressor type| Scroll| Scroll| Scroll| Scroll| Scroll| Scroll
Net weight (lbs.)| 315| 316| 408| 386| 437| 434
Ship weight (lbs.)| 460| 461| 587| 565| 616| 613
Filter size nominal (in.)| 20 x 30| 20 x 30| 20 x 20 (qty-2)| 20 x 20 (qty-2)|
30 x 20
20 x 20
| 30 x 20
20 x 20
Water in/out size (FPT)| 1| 1| 1| 1| 1| 1
Condensate size (NPTI)| 0.75| 0.75| 0.75| 0.75| 0.75| 0.75
Blower wheel Size (in.)| 11 x 11| 11 x 11| 11 x 11| 11 x 11| 11 x 11| 11 x 11
Table 4. General data – models EXVK009-030
Model EXVK | 009 | 012 | 015 | 018 | 024 | 030 |
---|---|---|---|---|---|---|
Unit size width x depth x height (in.) | 21.5 x 21.5 x 34 | 21.5 x 21.5 x 34 | ||||
21.5 x 23 x 36 | 21.5 x 26 x 38 | 21.5 x 26 x 38 | 24 x 32.5 x 42 | |||
Compressor type | Rotary | Rotary | Rotary | Rotary | Scroll | Scroll |
Net weight (lbs.) | 152 | 152 | 188 | 222 | 236 | 282 |
Ship weight (lbs.) | 207 | 207 | 246 | 282 | 296 | 345 |
Filter size nominal (in.) | 16 X 19 | 16 X 19 | 17 X 20 | 18 X 23 | 18 X 23 | 20 X |
30
Water in/out size (FPT)| 0.5| 0.5| 0.75| 0.75| 0.75| 1
Model EXVK| 009| 012| 015| 018| 024| 030
---|---|---|---|---|---|---
Condensate size (NPTI)| 0.75| 0.75| 0.75| 0.75| 0.75| 0.75
Blower wheel Size (in.)| 9 x 8| 9 x 8| 10 x 8| 10 x 9| 10 x 9| 11 x 11
Table 5. General data – models EXVK036-070
Model EXVK | 036 | 042 | 048 | 060 | 070 |
---|---|---|---|---|---|
Unit size width x depth x height (in.) | 24 x 32.5 x 42 | 25.4 x 32.5 x 49 | 25.4 | ||
x 32.5 x 49 | 25.4 x 32.5 x 55 | 25.4 x 32.5 x 55 | |||
Compressor type | Scroll | Scroll | Scroll | Scroll | Scroll |
Net weight (lbs.) | 284 | 356 | 350 | 370 | 432 |
Ship weight (lbs.) | 347 | 421 | 415 | 439 | 501 |
Filter size nominal (in.) | 20 X 30 | 27 X 30 | 27 X 30 | 30 X 33 | 30 X 33 |
Water in/out size (FPT) | 1 | 1 | 1 | 1 | 1 |
Condensate size (NPTI) | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 |
Blower wheel Size (in.) | 11 x 11 | 11 x 11 | 11 x 11 | 11 x 11 | 11 x 11 |
Table 6. General data – models DXHK024-070
Model DXHK | 024 | 036 | 048 | 060 | 070 |
---|---|---|---|---|---|
Unit size width x depth x height (in.) | 25.5 x 55 x 19.75 | 28 x 68 x 21.75 | |||
29.38 x 77.75 x 22.13 | 29.38 x 86.75 x 22.13 | 29.38 x 86.75 x 22.13 | |||
Compressor type | Two-Stage Scroll | Two-Stage Scroll | Two-Stage Scroll | Two- | |
Stage Scroll | Two-Stage Scroll | ||||
Net weight (lbs.) | 271 | 318 | 387 | 440 | 436 |
Ship weight (lbs.) | 395 | 463 | 566 | 619 | 615 |
Filter size nominal (in.) | 18 x 23 | 20 x 30 | 20 x 20 (qty-2) | 30 x 20 |
20 x 20
| 30 x 20
20 x 20
Water in/out size (FPT)| 0.75| 1| 1| 1| 1
Condensate size (NPTI)| 0.75| 0.75| 0.75| 0.75| 0.75
Blower wheel Size (in.)| 10 x 9| 11 x 11| 11 x 11| 11 x 11| 11 x 11
Table 7. General data – models DXVK024-070
Model DXVK | 024 | 036 | 048 | 060 | 070 |
---|---|---|---|---|---|
Unit size width x depth x height (in.) | 21.5 x 26 x 38 | 24 x 32.5 x 42 | 25.4 x | ||
32.5 x 49 | 25.4 x 32.5 x 55 | 25.4 x 32.5 x 55 | |||
Compressor type | Two-Stage Scroll | Two-Stage Scroll | Two-Stage Scroll | Two- | |
Stage Scroll | Two-Stage Scroll | ||||
Net weight (lbs.) | 238 | 284 | 360 | 377 | 439 |
Ship weight (lbs.) | 298 | 347 | 425 | 446 | 508 |
Filter size nominal (in.) | 18 x 23 | 23 x 30 | 27 x 30 | 30 x 33 | 30 x 33 |
Water in/out size (FPT) | 0.75 | 1 | 1 | 1 | 1 |
Condensate size (NPTI) | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 |
Blower wheel Size (in.) | 10 x 9 | 11 x 11 | 11 x 11 | 11 x 11 | 11 x 11 |
Table 8. ANSI/AHRI/ASHRAE/ISO13256-1 WLHP, GWHP and GLHP performance – 0.75 to 6 tons
Model
|
Rated GPM
|
Rated CFM
| Water Loop Heat Pump| Ground Water Heat Pump| Ground Loop Heat
Pump
---|---|---|---|---|---
Cooling 86°F| Heating 68°F| Cooling 59°F| Heating 50°F|
Full Cool 77°F| Full Heat 32°F
Capacity Btuh|
EER
| Capacity Btuh|
COP
| Capacity Btuh|
EER
| Capacity Btuh|
COP
| Capacity Btuh|
EER
| Capacity Btuh|
COP
EXV/H009| 2.25| 285| 8700| 18.1| 10700| 6.4| 9600| 29.7| 8500| 5.2| 9000|
21.2| 6100| 3.9
EXV/H012| 3.00| 380| 11400| 17.1| 14300| 5.9| 12500| 26.1| 11500| 5.0| 11900|
19.8| 8500| 3.8
EXV/H015| 3.75| 475| 15800| 16.3| 19000| 5.3| 17100| 24.6| 15600| 4.6| 16200|
18.7| 11800| 3.7
EXV/H018| 4.50| 570| 18900| 17.5| 23000| 5.4| 21100| 29.6| 18600| 4.8| 19700|
20.8| 14400| 3.9
EXV/H024| 6.00| 760| 25300| 18.1| 32000| 5.6| 27400| 28.4| 25900| 4.8| 26200|
21.2| 19400| 3.8
EXV/H030| 7.50| 950| 30200| 17.9| 37500| 5.7| 34500| 29.3| 30100| 5.0| 31800|
21.3| 22900| 4.2
EXV/H036| 9.00| 1140| 35000| 17.8| 43600| 5.6| 39500| 28.4| 35500| 4.9| 36600|
20.8| 27200| 4.1
EXV/H042| 10.50| 1330| 42000| 17.8| 48800| 5.9| 45300| 27.7| 39300| 5.1|
43300| 20.9| 30800| 4.1
EXV/H048| 12.00| 1520| 45300| 17.5| 51800| 5.8| 48300| 26.5| 41800| 4.9|
46900| 20.3| 33900| 4.0
EXV/H060| 15.00| 1900| 60600| 17.0| 72100| 5.4| 66800| 26.2| 58700| 4.7|
62700| 19.7| 45200| 3.8
EXV/H070| 17.50| 2215| 63400| 17.6| 77000| 5.5| 67700| 25.1| 62200| 4.7|
65900| 20.1| 48800| 3.9
Table 9. ANSI/AHRI/ASHRAE/ISO13256-1 WLHP, GWHP and GLHP performance – 2 to 6 tons
Model
|
Load
|
Rated GPM
|
Rated CFM
| Water Loop Heat Pump| Ground Water Heat Pump| Ground Loop Heat
Pump
---|---|---|---|---|---|---
Cooling 86°F| Heating 68°F| Cooling 59°F| Heating 50°F|
Full Cool 77°F| Full Heat 32°F
Capacity Btuh|
EER
| Capacity Btuh|
COP
| Capacity Btuh|
EER
| Capacity Btuh|
COP
| Capacity Btuh|
EER
| Capacity Btuh|
COP
DXV/H024| Full| 6.0| 760| 25400| 18.8| 31100| 5.7| 27100| 28.1| 25000| 5.0|
25700| 21.3| 18900| 4.1
DXV/H024| Part| 6.0| 608| 18100| 19.5| 21700| 5.9| 19700| 33.1| 17900| 5.0|
19100| 27.5| 16300| 4.6
DXV/H036| Full| 9.0| 1140| 32100| 17.5| 41800| 6.0| 36700| 27.5| 33600| 5.1|
33800| 20.5| 25400| 4.2
DXV/H036| Part| 9.0| 912| 22600| 17.5| 30300| 6.6| 26300| 31.8| 24100| 5.3|
25400| 26.2| 20600| 4.7
DXV/H048| Full| 12.0| 1520| 44800| 17.3| 53700| 6.0| 49500| 26.6| 42900| 5.1|
46300| 19.8| 32300| 4.2
DXV/H048| Part| 12.0| 1216| 31900| 17.1| 38700| 6.4| 34900| 26.6| 30800| 5.2|
34600| 24.2| 26400| 4.4
DXV/H060| Full| 15.0| 1900| 54500| 18.2| 67000| 6.1| 60100| 26.5| 53800| 5.2|
56500| 20.7| 41000| 4.2
DXV/H060| Part| 15.0| 1520| 38100| 18.3| 48000| 6.7| 43100| 30.2| 37900| 5.4|
41900| 26.0| 32000| 4.5
DXV/H070| Full| 17.5| 2215| 61800| 16.0| 81400| 5.5| 67000| 22.5| 67300| 4.8|
65100| 18.5| 51700| 4.0
DXV/H070| Part| 17.5| 1772| 44600| 17.4| 55700| 5.9| 48100| 26.4| 46100| 4.9|
48100| 23.6| 41000| 4.3
Note : Performance data EXVK 0.5 Ton or 0.75 Ton Rated in accordance with ANSI/AHRI/ASHRAE/ISO13256-1. Certified conditions are 80.6°F DB/66.2°F WB EAT in cooling and 68°F DB/59°F WB EAT in heating. Entering liquid temperature in cooling is 86°F for Water Loop, 77°F for Ground Loop (full load), 68°F for Ground Loop (part load), and 59°F for Ground Water. Entering liquid temperature in heating is 68°F for Water Loop, 32°F for Ground Loop (full load), 41°F for Ground Loop (part load), and 50°F for Ground Water.
*Table 10. Electrical data – 0.75 to 6 tons, EX009-070**
Model No.| Unit Volts| Blower Motor HP| Minimum Circuit
Ampacity| Maximum Overcurrent Protective Device
---|---|---|---|---
EXV/H009| 208-230/60/1| 1/3| 6/6| 15/15
EXV/H009| 265/60/1| 1/3| 5| 15
EXV/H012| 208-230/60/1| 1/3| 9/9| 15/15
EXV/H012| 265/60/1| 1/3| 6| 15
EXV/H015| 208-230/60/1| 1/3| 16/16| 25/25
EXV/H015| 265/60/1| 1/3| 9| 15
EXV/H018| 208-230/60/1| 1/2| 21/21| 30/30
Model No.| Unit Volts| Blower Motor HP| Minimum Circuit
Ampacity| Maximum Overcurrent Protective Device
---|---|---|---|---
EXV/H018| 265/60/1| 1/2| 11| 15
EXV/H024| 208-230/60/1| 1/2| 17/17| 25/25
EXV/H024| 265/60/1| 1/2| 15| 20
EXV/H024| 208-230/60/3| 1/2| 12/12| 15/15
EXV/H024| 460/60/3| 1/2| 6| 15
EXV/H030| 208-230/60/1| 3/4| 18/18| 30/30
EXV/H030| 265/60/1| 3/4| 16| 25
EXV/H030| 208-230/60/3| 3/4| 14/14| 20/20
EXV/H030| 460/60/3| 3/4| 7| 15
EXV/H036| 208-230/60/1| 3/4| 20/20| 30/30
EXV/H036| 265/60/1| 3/4| 18| 25
EXV/H036| 208-230/60/3| 3/4| 19/19| 30/30
EXV/H036| 460/60/3| 1| 8| 15
EXV/H042| 208-230/60/1| 3/4| 22/22| 35/35
EXV/H042| 208-230/60/3| 3/4| 18/18| 30/30
EXV/H042| 460/60/3| 1| 9| 15
EXV/H048| 208-230/60/1| 1| 27/27| 40/40
EXV/H048| 208-230/60/3| 1| 20/20| 30/30
EXV/H048| 460/60/3| 1| 9| 15
EXV/H060| 208-230/60/1| 1| 32/32| 50/50
EXV/H060| 208-230/60/3| 1| 25/25| 40/40
EXV/H060| 460/60/3| 1| 12| 15
EXV/H070| 208-230/60/1| 1| 36/36| 50/50
EXV/H070| 208-230/60/3| 1| 26/26| 40/40
EXV/H070| 460/60/3| 1| 12| 15
*Table 11. Electrical data – 2 to 6 tons, DX024-070**
Model No.| Unit Volts| Blower Motor HP| Minimum Circuit
Ampacity| Maximum Overcurrent Protective Device
---|---|---|---|---
DXV/H024| 208-230/60/1| 1/2| 15/15| 25/25
DXV/H024| 265/60/1| 1/2| 12| 15
DXV/H024| 208-230/60/3| 1/2| 10/10| 15/15
DXV/H024| 460/60/3| 1/2| 6| 15
DXV/H036| 208-230/60/1| 3/4| 21/21| 35/35
DXV/H036| 265/60/1| 3/4| 15| 25
DXV/H036| 208-230/60/3| 3/4| 13/13| 20/20
DXV/H036| 460/60/3| 1| 7| 15
DXV/H048| 208-230/60/1| 1| 26/26| 40/40
DXV/H048| 208-230/60/3| 1| 18/18| 25/25
DXV/H048| 460/60/3| 1| 11| 15
DXV/H060| 208-230/60/1| 1| 30/30| 45/45
DXV/H060| 208-230/60/3| 1| 24/24| 35/35
DXV/H060| 460/60/3| 1| 12| 15
DXV/H070| 208-230/60/1| 1| 38/38| 60/60
DXV/H070| 208-230/60/3| 1| 24/24| 35/35
DXV/H070| 460/60/3| 1| 12| 15
Figure 1. Clearances – EXHK/DXHK 0.75 to 6 tons
A minimum 14-inch clearance for servicing the unit is required for all EXH 0.75 to 6-ton configurations from other mechanical and electrical equipment (where shown) to enable panel removal from the unit for service/maintenance ability. The optimum clearance required is 20 inches.
Figure 2. Clearances – EXVK/DXVK 0.75 to 6 tons
A 24-inch clearance from other mechanical and electrical equipment (where shown) is recommended for most unit configurations. This will enable panel removal from the unit for service/maintenance. The 24-inch side clearance on EXVK/DXVK 0.75-6T models is for optimal access only. Side clearance is not a requirement as most components can be accessed from the front of the unit. A 1-inch minimum clearance between the filter rack and any obstacle is required for units in a free return application to provide proper airflow to the air- to-refrigerant coil. A 12-inch minimum clearance between the filter rack and any obstacle should be provided to properly attached ductwork.The 1-inch dimension shown in the back of the unit represents the supply duct collar for the back supply option. This clearance is needed to clear these flanges.
Trane – by Trane Technologies (NYSE: TT), a global climate innovator – creates comfortable, energy-efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.