Sid Harvey ADB-1 Adjustable Delay on Break Timer Owner’s Manual
- June 22, 2024
- Sid Harvey
Table of Contents
ADB-1 Adjustable Delay on Break Timer
Owner’s Manual
TIME DELAYS
Adjustable Delay on Break Timer
Adjusts from 6 seconds to 8 minutes. Spinproof knob. Works with 24, 120 or 240
VACcontrol circuits. Supports up to 1.0 Amps.
Twowire hookup for easy installation. Solid statewith quick disconnect
terminals. Mounts withone self-tapping screw.
Conformal coatedcircuitry protects against moisture and shock.UR recognized
for USA and Canada. Works withanticipator type thermostats.
HOW IT WORKS:
Immediately upon applicationof power, the Delay on Break timer enablescircuit
operation. Once power is interrupted, thecircuit opens for the time set on
the dial. After thetime period elapses, the circuit closes, allowingthe
protected motor or compressor to start. Fortypical HVAC applications, the
operation of thetimer is transparent and will go unnoticed.
CATALOG NO. | DESCRIPTION | UOM | ORDER MULTIPLE |
---|---|---|---|
ADB-1 | Adjustable Delay on Break | EA | 1 |
ADB-2 | Adjustable Delay on Break w/Wire Leads | EA | 1 |
Adjustable Delay on Make Timer
Ideal for random starting of multiple units. Adjusts from 6 seconds to 8
minutes. Spin proof knob. Works with 24, 120 or 240 VAC control circuits.
Supports up to 1.0 Amps. Two wire hookup for easy installation. Solid state
with quick-disconnect terminals. Mounts with one self-tapping screw. Conformal
coated circuitry protects against moisture and shock. UR recognized for US and
Canada. Works with anticipator type thermostats. HOW IT WORKS: These timers
delay circuit closure upon application of power. Only after the set time
period elapses and power remains ON will the circuit close, allowing the
protected motor or compressor to start. For typical HVAC installations, timers
are adjusted to random times to prevent power circuit overloads, thus are
often called random start timers.
CATALOG NO. | DESCRIPTION | UOM | ORDER MULTIPLE |
---|---|---|---|
ADB-1 | Adjustable Delay on Make | EA | 1 |
ADB-2 | Adjustable Delay on Make w/Wire Leads | EA | 1 |
MONITORS
Digital Three Phase Line Voltage Monitor
Offers continuous protection against voltage anomalies which can damage
compressors, motors and other sensitive electrically operated devices.
PROTECTION: Loss of Phase, Phase Reversal, Voltage Imbalance, Low Voltage,
High Voltage
DISPLAY: Large custom LCD display indicates all operating conditions at a
glance. Three large sets of digits provide easy system troubleshooting.
VOLTMETER: Three independent voltmeters read both line and contactor load
(backside) voltages.
MONITORED VOLTAGE: 160 to 600 Volts 50-60 Hz.
POWER SUPPLY: Power for the WPC-500 is automatically derived from any active
phase.
System operation is not dependent on the control voltage or a specific phase
for power.
CONTROL VOLTAGE: 19-277 VAC. Anticipator load is provided for operation with
24 volt electronic and mechanical thermostats.
OPERATING VOLTAGE SET POINT: 175 to 650 VAC.
Digitally adjustable in one volt increments.
VOLTAGE TRIP POINT: Adjustable in 1% increments between 6% and 18% of selected
operating voltage.
Restart voltage set point (hysterisis) fixed at cutout voltage + 3%.
VOLTAGE SYMMETRY: Adjustable imbalance trip point from 2% to 25% of selected
operating voltage.
RESPONSE TIMES: Phase Loss/Reversal: 100 mS max.
Imbalance: Adjustable Response Timer
Over or Under Voltage: Adjustable Response Timer LOCKOUT DELAY TIMER: Fully
adjustable 0 to 720 Seconds (0 to 12 minutes). Digital display shows re-
maining time and user set points.
SEQUENTIAL START TIMER: 0 to 30 seconds in one second increments.
RESPONSE TIMER: 0.1 to 20 Seconds. Digital display shows remaining time and
user set points.
MEMORY: Up to 25 past fault conditions are stored for later retrieval and
analysis. The faults may be displayed or cleared by the front panel buttons.
CATALOG NO. | DESCRIPTION | EA | ORDER MULTIPLE |
---|---|---|---|
DTP-3 | Digital 3-Phase Motor Protector | UOM | 1 |
Digital Single Phase Line Voltage Monitor
Automatic voltage monitor and control system. Continuously measures incoming
line voltage, allowing detection of any voltage outside the tolerances that
you set. If these limits are exceeded, the response timer begins counting.
You may also set response time – a short time for a quick response or a long
time to avoid nuisance tripping. If the voltage remains outside the tolerance
after the time has elapsed, the DSP-1 will turn off its output relay and
protect your device. While output is off, an additional delay timer activates
to avoid rapid restarts. FEATURES:
Digital voltmeter displays instantaneous line voltage;
Automatic voltage tester adjusts from 90 to 300 volts;
Adjustable response timer (0.1 to 10 sec.) prevents nuisance tripping;
Adjustable delay timer (1 to 720 sec.) prevents rapid restarts;
Digital display makes for easy viewing and operation
SPECIFICATIONS:
Voltmeter: 70 to 325 Volts
Voltage Set Point: 90 to 300 Volts
Tolerance Limits: 6 to 18%
Response Timer: 0.1 to 10 seconds
Delay Timer: 1 to 720 seconds
Output Relay: 10 Amps, 250 VAC resistive, single-pole/double-throw
Control Input: 18 to 250 VAC with anticipator load for 24 volt thermostats
CATALOG NO. | DESCRIPTION | UOM | ORDER MULTIPLE |
---|---|---|---|
DSP-1 | Digital Single Phase Motor Protector | EA | 1 |
NOTE: Item numbers in RED indicate Made in the U.S.A.