Qlima WDH 235 PTC Inverter Monoblock Instruction Manual

June 20, 2024
Qlima

Qlima Logo WDH 235 PTCQlima WDH 235 PTC Inverter Monoblock GARANTE 2YEARS
OPERATING MANUAL

IMPORTANT COMPONENTS

  1. Air inlet
  2. Louvre
  3. Front panel
  4. Control panel (depending on model)
  5. Wall hanging mounts
  6. Back panel
  7. Vent
  8. Drainage pipe

WHAT’S INCLUDED

  1. Air conditoner
  2. Wall template
  3. Plastic ducting sheet (x2)
  4. Wall plugs
  5. Vent cover (x2) (chain, indoor ring and outdoor cover)
  6. Remote control
  7. Screws
  8. Wall bracket
  9. Fixed Plate
  10. 4×10 topping screw
  11. Sealing strip

Qlima WDH 235 PTC Inverter Monoblock - INCLUDED

  1. READ THE DIRECTIONS FOR USE FIRST.
  2. IN CASE OF ANY DOUBT, CONTACT YOUR DEALER.

Qlima WDH 235 PTC Inverter Monoblock - INCLUDED 1

TOOLS REQUIRED

  1. Spirit level
  2. Drill
  3. Tape measure
  4. 180 mm Core drill
  5. 8 mm Masondry drill bit
  6. Sharp knife
  7. 20 mm Masondry drill bitt
  8. Pencil

Dear Sir, Madam,
Congratulations on the purchase of your air conditioner. You have acquired a high quality product that will provide you with many years of pleasure, on condition that you use it responsibly. Reading these instructions for use before operating your air conditioner will optimise its life span. We wish you comfort with your air conditioner.
Yours sincerely,
PVG Holding B.V.
Customer service department

SAFETY INSTRUCTIONS

Read this user manual carefully before using the appliance and keep it for future reference. Install this device only when it complies with local/national legislation, ordinances and standards. This product is intended to be used as an air conditioner in residential houses and is only suitable for use in dry locations, in normal household conditions, indoors in living room, kitchen and garage.
IMPORTANT

  • Never use the device with a damaged power cord, plug, cabinet or control panel. Never trap the power cord or allow it to come into contact with sharp edges.
  • The installation must be completely in accordance with local regulations, ordinances and standards.
  • The device is suitable exclusively for use in dry places, indoors.
  • Check the mains voltage. This device is suitable exclusively for earthed sockets – connection voltage 220-240 Volt/ 50 Hz.
  • The device MUST always have an earthed connection. You may absolutely not connect the device if the power supply is not earthed.
  • The plug must always be easily accessible when the device is connected.
  • Read these instructions carefully and follow the directions.

Before connecting the device, check that:

  • The connection voltage corresponds to that on the type plate.
  • The socket and power supply are suitable for the device.
  • The plug on the cable fits the socket.
  • The device is on a stable and flat surface. Have the electrical installation checked by a recognised expert if you are not sure that everything is in order.
  • The airconditioner is a safe device, manufactured in accordance with CE safety stand- ards. Nevertheless, as with every electrical device, exercise caution when using it.
  • Never cover the air inlets and outlets.
  • Empty the water reservoir through the water drain before moving it.
  • Never allow the device to come into con- tact with chemicals.
  • Do not insert objects into the openings of the device.
  • Never allow the device to come into con- tact with water. Do not spray the device with water or submerge it as this may cause a short circuit.
  • Always take the plug out of the socket before cleaning or replacing the device or a part of the device.
  • NEVER connect the device with the aid of an extension cable. If a suitable, earthed socket is not available, have one fitted by a recognised electrician.
  • Always consider the safety of children in the vicinity of this device, as with every electrical device.
  • Always have any repairs – beyond regular maintenance – carried out by a recognised service engineer. Failure to do so may lead to invalidation of the guarantee.
  • Always take the plug out of the socket when the device is not in use.
  • If the power cable is damaged it must be replaced by the manufacturer, its customer service department or persons with comparable qualifications in order to prevent danger.
  • This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
  • Children should be supervised to ensure that they do not play with the appliance.
  • This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.
  • Children shall not play with the appliance.
  • Cleaning and user maintenance shall not be made by children without supervision.

ATTENTION!

  • Never seal the room – where this device will be used – completely airtight. This will prevent under pressure in this room. Under pressure can disrupt the safe operation of geysers, ventilation systems, ovens, etc.
  • Failing to follow the instructions may lead to nullification of the guarantee on this device.

Specific information regarding appliances with R290 / R32 refrigerant gas.

  • Thoroughly read all of the warnings.
  • When defrosting and cleaning the appli- ance, do not use any tools other than those recommended by the manufacturing company.
  • The appliance must be placed in an area without any continuously sources of ignition (for example: open flames, gas or electrical appliances in operation).
  • Do not puncture and do not burn.
  • This appliance contains Y g (see rating label back of unit) of R290 / R32 refrigerant gas.
  • R290 / R32 is a refrigerant gas that com- plies with the European directives on the environment. Do not puncture any part of the refrigerant circuit. Be aware the refrigerants may not contain an odour.
  • If the appliance is installed, operated or stored in a nonventilated area, the room must be designed to prevent to the accumulation of refrigerant leaks resulting in a risk of fire or explosion due to ignition of the refrigerant caused by electric heaters, stoves, or other sources of ignition.
  • The appliance must be stored in such a way as to prevent mechanical failure.
  • Individuals who operate or work on the refrigerant circuit must have the appropriate certification issued by an accredited organization that ensures competence in handling refrigerants according to a specific evaluation recognized by associations in the industry.
  • Repairs must be performed based on the recommendation from the manufacturing company.

Maintenance and repairs that require the assistance of other qualified personnel must be performed under the supervision of an individual specified in the use of flammable refrigerants. Appliances shall be installed, operated and stored in a room with a floor area larger than 15 m 2 . The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
Explanation of symbols displayed on the unit(For the unit adopts R32/R290 Refrigerant only):
WARNING:
This symbol shows that this appliance used a flammable refrigerant. If the refrigerant is leaked and exposed to an external ignition source, there is a risk of fire.
CAUTION:
This symbol shows that the user manual should be read carefully.
CAUTION:
This symbol shows that the installation manual should be read carefully.
CAUTION:
This symbol shows that the technical manual should be read carefully.
INSTRUCTIONS FOR REPAIRING APPLIANCES CONTAINING R290 / R32

GENERAL INSTRUCTIONS

This instruction manual is intended for use by individuals possessing adequate backgrounds of electrical, electronic, refrigerant and mechanical experience.
1.1 Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system.
1.2 Work procedure
Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed.
1.3 General work area
All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided.
The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.
1.4 Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. nonsparking, adequately sealed or intrinsically safe.
1.5 Presence of fire extinguisher
lf any hotwork is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO 2 fire extinguisher adjacent to the charging area.
1.6 No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of
fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to
the surrounding space. Prior to worktaking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking” signs shall be displayed.
1.7 Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it extemally into the atmosphere.
1.8 Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. lf in doubt consult the manufacturer’s
technical department for assistance. The following checks shall be applied to installations using flammable refrigerants: – the charge size is in accordance with the room size within which the refrigerant containing parts are installed;

  • the ventilation machinery and outlets are operating adequately and are not obstructed;
  • if an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant;
  • marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;
  • refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.

1. 9 Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. lf a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. lf the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. lnitial safety checks shall include:

  • that capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
  • that there no live electrical components and wiring are exposed while charging, recovering or purging the system;
  • that there is continuity of earth bonding.

REPAIRS TO SEALED COMPONENTS

2.1 During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. lf it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
2.2 Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number
of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres.
Replacement parts shall be in accordance with the manufacturer’s specifications.
NOTE The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. lntrinsically safe components do not have to be isolated prior to working on them.

REPAIR TO INTRINSICALLY SAFE COMPONENTS

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted tor the equipment in use. lntrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.

CABLING

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continua! vibration from sources
such as compressors or fans.

DETECTION OF FLAMMABLE REFRIGERANTS

Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame} shall not be used.

LEAK DETECTION METHODS

The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need recalibration. (Detection equipment shall be calibrated in a refrigerant- free area.)
Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum} is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipework.
lf a leak is suspected, all open flames shall be removed/extinguished.
lf a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves} in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.

REMOVAL AND EVACUATION

When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to: remove refrigerant; purge the circuit with inert gas; evacuate; purge again with inert gas; open the circuit by cutting or brazing. The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system.
When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipework are to take place. Ensure that the outlet tor the vacuum pump is not close to any ignition sources and !here is ventilation available.

CHARGING PROCEDURES

In addition to conventional charging procedures, the following requirements shall be followed. Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them. Cylinders shall be kept upright. Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. Label the system when charging is complete (if not already). Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.

DECOMMISSIONING

Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. lt is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. lt is essential that 4 GB electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) lsolate system electrically.
c) Before attempting the procedure ensure that: mechanical handling equipment is available, if required, for handling refrigerant cylinders;
d) All personal protective equipment is available and being used correctly; the recovery process is supervised at all times by a competent person;
e) recovery equipment and cylinders conform to the appropriate standards.
f) Pump down refrigerant system, if possible. g) lf a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. h) Make sure that cylinder is situated on the scales before recovery takes place.
i) Start the recovery machine and operate in accordance with manufacturer’s instructions.
j) Do not overfill cylinders. (No more than 80 % volume liquid charge).
k) Do not exceed the maximum working pressure of the cylinder, even temporarily.
l) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off. m) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.

LABELLING

Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

RECOVERY

When removing refrigerant from a system, either for servicing or decommissioning, il is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge are available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that il is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. lf compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric healing to the compressor body shall be employed to accelerate this process. When oil is drained from a system, il shall be carried out safely.

INSTALLATION

Corresponding images can be found on pages 254-255.

  1. This unit must be installed on an external wall, as it vents directly out of its rear. a
    • Only install the unit on a flat, solid and reliable wall. Ensure that there are no cables, pipes, steel bars or other obstructions behind the wall.
    • Leave at least 10 cm of space to the left, right and base of the machine. At least 20cm of space must be left above the unit to help air flow smoothly.

  2. Paste the supplied installation template paper in position on the wall, ensuring that the reference line is level using a spirit level. b

  3. The hole for the drainage pipe must be drilled using a 20mm Drill bit. Ensure the hole is at a downward angle (min 5 degrees) so that the water will drain correctly. c

  4. Use a 180mm core drill to drill the two holes for the units ventillation, ensuring that the holes are at a downward angle (min 5 degrees) and aligned with the template. d
    • Use the template to mark the position of the screws for the hanging rail, using a spirit level to ensure it is straight and level.
    • Drill the marked holes using a suitable 8mm drill bit and insert wall plugs.
    Line the hanging rail with the holes, and fix the rail into position using the supplied screws.
    • Ensure that the hanging rail is securely fastened onto the wall, and that there is no risk of the unit tipping or falling.

  5. Roll the plastic vent sheets into a tube and feed them from the inside into the holes previously made. Ensure the tubes sit flush to the interior wall. e
    • Go outside and trim off the excess vent tube using a sharp knife, keeping the edge as neat as possible.
    • The machine performs best when it is installed on awall with a thickness not exceeding 240mm.

  6. Insert the indoor fixing ring from the vent cover onto the indoor side of the air vent. Then fold the external vent cover in half. Attach the chains to each side of the vent cover, before sliding the cover outside through the vent hole.

  7. Expand the external cover, before tightly fixing the chains by hooking onto the indoor fixing ring. This will hold the external cover firmly in position.
    Repeat for the second vent.

  8. Once the chains are fitted and secure, any excess chain should be removed by cutting the chain.

  9. Paste the sealing strip in the accessories along the edge of the back for whole circle of the machine, cut off the excessive length if needed.
    NOTE:
    1. The sealing strip should be pasted along the edge of the machine. i
    2. Please peel the striping layer on the sealing strip gradually while pasting.
    3. Paste from the bottom of the machine first.
    4. The position of the corner should be pasted as shown in j
    5. Improper pasting may cause extra noise.

  10. Lift the unit onto the wall, align the hanging holes with the hooks on the hanging rail and gently rest the unit into place. At the same time, slide the drain pipe through the drainage hole. If the wireless controller (Available separately) has been purchased, it should then be installed, and connected.
    NOTE: The end of the external water pipe must be placed in an open space or drain. Avoid damage or constriction to the drainage pipe to ensure the unit drains.

OPERATION

CONTROL PANEL

  1. Digital display
  2. Cooling
  3. Air supply
  4. Dry
  5. Heating
  6. PTC
  7. Speed
  8. Increase/Decrease
  9. Timer
  10. Speed
  11. Mode
  12. Power

REMOTE CONTROL
The air conditioner can be controlled with the remote control. Two AAA- batteries are required.
NOTE: Further details of the functions can be found on the following page.

POWER Press the POWER button to turn the machine on or off.
MODE Press the MODE button to switch between cooling, heating, fan and dry

modes.
FAN| Press the FAN button to change between high, medium and low fan speeds

LED

| Press the LED button to open or close the LED light on unit, it can be a choice for sleep condition.
▲| Press the UP button to increase the desired temperature or timer duration
▼| Press the DOWN button to decrease the desired temperature or timer duration
PTC| Press it to turn PTC on or off. When PTC turned on, the display indicates lights up on remote control at the same time; when PTC turned off,  goes out on display and remote control at the same time. (only activated in heating mode)
SILENT| Press it for silent mode. When silent mode turned on, the display indicates “SL” and the lights doesn’t dim out. When silent mode turned off, the lights goes out. In Silent mode, noise will be SILENT lower, fan works in low speed, frequency is low.
SWING| Press to turn the swing function on and off (Can only be activated from the remote)
TIMER| Press the TIMER button to set the timer.

FUNCTIONS

POWER Press “POWER” to turn the unit On or Off
Press to change between the 4 different modes. The display will show the

symbol for the mode currently selected.
| Cooling mode defaults to 22°C and will cool the air while sending warm air outside. The desired temperature can be adjusted using the increase and decrease button between 16°C and 30°C. The fan speed can also be adjusted using the speed button.

| Dry mode will extract moisture from the air, which will be drained outside using the installed drain pipe. The fan speed cannot be adjusted in dry mode.
| In fan mode the appliance will recirculate the air within the room, and will not cool, heat or dehumidify. The fan speed can be adjusted using the Speed button.
| Heating mode defaults to 24°C and will heat the air while sending cool air outside. The desired temperature can be adjusted using the increase and decrease button between 16°C and 30°C. The fan speed can also be adjusted using the speed button.

SL
SILENT

| SL
SILENT| Silent mode can be activated from APP or the remote control, It can also be activated by pressing “”+”” on unit control panel at the same time. It will only operate in cooling modes, the fan speed will change to low and noise will be lower.
| | Press to change the fan speed between Low, Medium and High. The fan speed cannot be adjusted in Dry or Silent modes.
| The air conditioner contains a 24 hour timer, which can be used to either set a delayed start, or a set period of operation. The timers cannot be combined, although the app can be used to program periods of operation.
SHUTDOWN TIMER: While the unit is running press the timer button, the display will flash “0” 5 times. After the 5th flash, use the up and down buttons to adjust the duration in 1 hout increments between 1 to 24 hours. When the timer has elapsed, the unit will shutdown automatically.
DELAYED START TIMER: With the unit in standby, press the timer button, the display will flash “0” 5 times. After the 5th flash, use the up and down buttons to adjust the duration in 1 hout increments between 1 and 24 hours. After the timer has elapsed, the unit will start up in the same mode with the same settings as when it was turned off.
INCREASE AND DECREASE| Used within cooling and heating modes to adjust the desired room temperature. Also used while setting the timer to adjust the duration.
SWING MODE| After machine turns on, press the “SWING” button, louver will swing continuously up and down; by pressing the button again the move- ment will stop and the louver remain in that position. Swing mode can only be adjusted from the remote, and will initially be turned on by default.
COMPRESSOR PROTECTION| There is a 3 minutes delay on power on. In order to protect the life of the compressor and electronic components please do not switch on the unit for at least 5 minutes after you turned the unit off.

PTC ELECTRIC HEATING FUNCTION
The unit has an additional PTC electric heating element. When the weather conditions outside are bad, you can press the PTC button on the remote control to turn on the electric heating function to increase the heat. The heat power of the
PTC is equal to 800W.
PTC TURN ON

  1. Only in the heating mode, press the PTC button on the remote control to send the turn-on command to the unit. At this time, the remote control and the unit display lights up at the same time.

  2. After the unit receives the remote control command, the system will carry out self-testing, PTC will work when the following points are satisfied at the same time:
    a. Unit is in heating mode.
    b. Tw<25°C (outdoor temperature keeps lower than 25°C for 10 seconds ).
    c. Ts-Tr≥5°C (The Set temperature is more than 5 degrees higher than the Room temperature).
    d. Room temperature Tr≤18°C.
    e. Coil Temperature of evaporator Te ≤48°C.
    f. Compressor is keep working for 3minutes.

  3. PTC will stop working when the system self- testing detects one of the following points:
    a. Outdoor temperature keeps higher than 28°C for 10 seconds
    b. The room temperature is greater than the setpoint;
    c. Room temperature Tr ≥23°C.
    d. Compressor stop working.
    e. The ventilation stops or the fan is faulty.
    f. 4-way valve get disconnected.
    g. Coil Temperature of evaporator Te ≥54°C or sensor error.
    h. Unit didn’t work in heating mode.
    i. Unit is in defrost function.
    PTC TURN OFF
    Presses the PTC button again or change to other mode to turn off PTC function, the lights on remote control and the unit display will be off at the same time.
    NOTE:
    • The unit will work without PTC function as a default until the “PTC” button on remote control is pressed.
    • If unit is turn off, the PTC setting will be cleared, it need to be set again.

WIFI SETUP AND SMART FEATURES
WIFI SETUP
BEFORE YOU START

  • Ensure your router provides a standard 2.4ghz connection.

  • If your router is dual band ensure that both networks have different network names (SSID). The provider of your router / Internet service provider will be able to provide advice specific to your router.

  • Place the air conditioner as close as possible to the router during setup.

  • Once the app has been installed on your phone, turn off the data connection, and ensure your phone is connected to your router via wifi.
    DOWNLOAD THE APP TO YOUR PHONE

  • Download the ”SMART LIFE” app, from your chosen app store, using the QR codes below, or by searching for the app in your chosen store.

https://smartapp.tuya.com/smartlife

CONNECTION METHODS AVAILABLE FOR SETUP

  • The air conditioner has 2 different setup modes: Bluetooth Connection and Wifi connection (Quick Connection and AP (Access Point)). The Bluetooth and Quick Connection is a quick and simple way to set the unit up. The AP connection uses a direct local wifi connection between your phone and the air conditioner to upload the network details.
  • Before starting the setup, with the air conditioner plugged in, but turned off, press and hold the Speed button for 3 seconds (until you hear a bleep) to enter the wifi connection mode.
  • Please ensure your device is in the correct wifi connection mode for the connection type you are attempting, the flashing of the wifi light on your air conditioner will indicate this.
Connection Type Frequency of Flashes Frequency of Flashes
Bluetooth connection
Quick Connection Flashes twice per second
AP (Access Point) Flashes once per three seconds

CHANGING BETWEEN CONNECTION TYPES
To change the unit between the two wifi connection modes, hold the Speed button for 3 seconds.

REGISTER THE APP

Qlima WDH 235 PTC Inverter Monoblock -REGISTER THE APP

SETTING UP YOUR HOME WITHIN THE APP
SMART LIFE is designed so it can work with a large number of compatible smart devices within your home. It can also be set up to work with multiple devices within different houses As such during the setup process, the app requires that differen t areas are created and named to allow easy management of all your devices. When new devices are added, they are assigned to one of the rooms you have created.
CREATING ROOMS

Qlima WDH 235 PTC Inverter Monoblock -CREATING ROOMS

CONNECTING USING QUICK CONNECTION
Before initiating the connection, make sure the unit is in standby mode, with the WIFI light flashing twice per second. If not follow the instructions for changing the connection mode. Also ensure your phone is connected to the wifi network. (We advise turning mobile data off during setup)

Qlima WDH 235 PTC Inverter Monoblock - CONNECTION

CONNECTING USING AP MODE (ALTERNATIVE METHOD)
Before initiating the connection, make sure the unit is in standby mode, with the wifi light flashing once per second. If not follow the instructions for changing the wifi connection mode. Also ensure your phone is connected to the wifi network. (We advise turning mobile data off during setup)

Qlima WDH 235 PTC Inverter Monoblock - METHOD

CONTROLLING YOUR DEVICE THROUGH THE APP

THE HOME SCREEN

Qlima WDH 235 PTC Inverter Monoblock - APP

DEVICE SCREEN

Qlima WDH 235 PTC Inverter Monoblock - DEVICE SCREEN

DEVICE SCREEN
The device screen is the main control screen for the air conditioner, providing access to the controls to amend the functions and settings
Back: Returns to the Home Screen
Current Room
Temperature: Displays the current room temperature
MODE:
Change the operating mode of the air conditioner between Cooling, Heating, Dehumidify and Fan
SPEED:
Use to change the Fan speed between Low, Medium and High. Note this cannot be changed in dehumidify mode.
Desired Temperature DOWN Button: Use to lower the desired temperature.

ON / OFF Button:
Use to turn the unit on or off.

Edit Name: Use to change the name of the air conditioner.
Desired Room
Temperature: Displays the desired room temperature
Current Mode: Shows the mode the air conditioner is currently in.
SWING:
Use to turn the oscillating swing function on and off.
SCHEDULE:
Use to add a set a scheduled operation.
A number of these can be combined to specify automatic operation
TIMER:
Use to add an off timer while the unit is running, or an on timer while the unit is turned off

Desired Temperature
UP Button : Use to increase the desired temperature.

  • Due to continuous development of the app, the layout and available features may be subject to change.
    SMART SCENES
    Smart Scenes is a powerful tool providing the option to customise the operation of the air conditioner based both on conditions within the room and outside influences. This gives the user the option of specifying much more intelligent  actions. These are split into two categories Scene and Automation.
    SCENE
    Scene allows for a one touch button to be added to the Home screen. The button can be used to change a number of settings in one go, and can change all the settings within the unit. A number of scenes can easily be setup, allowing the user to easily change between a number of preset configurations.
    Below is an example of how to set up a scene:Qlima WDH 235 PTC Inverter
Monoblock - SCENE

AUTOMATION
Automation allows an automatic action to be set up for the device. This can be triggered by the Time, indoor temperature, humidity of the room, weather conditions, and a range of other influences.Qlima WDH 235 PTC Inverter
Monoblock - AUTOMATIONQlima WDH 235 PTC Inverter
Monoblock - PROFILE TAB

PROFILE TAB
The profile tab gives you the option to edit both your detail, and use the added features of the unit.
CHANGING THE NAME OF YOUR DEVICE
When in any of the device screens further settings for the device can be accessed, by pressing on the three dots in the top right hand corner. The top option within this allows you to change the name of the device to something relevant to  the use of the product, such as “Living Room Air Conditioner”. Within the menu, you also have the option of setting up a pattern lock or change your password.
DEVICE SHARING
This allows you to share access to the controls of your air conditioner with friends and family.
INTEGRATION
This allows the unit to be integrated with your favourite home automation hardware such as Google Home and the Amazon Echo.

MAINTENANCE

WARNING!
Switch off the unit and remove the electrical plug from the mains before cleaning the appliance or filter, or before replacing the filters. Clean the housing with a soft, damp cloth. Never use aggressive chemicals, petrol, detergents or other  cleansing solutions.

TROUBLE SHOOTING

Do not repair or disassemble the air conditioning. Unqualified repair will invalidate the warranty and may lead to failure, causing injuries and property damage. Only use it as directed in this user manual and only perform operations advised here.

Problem Reasons Solution

The air conditioner does not work.

| There is no electricity.| Check the unit is plugged in, and the socket is working normally.
The ambient temperature is too low or too high,| Only use to use the machine with a room temperature between 7 and 35°C.
In cooling mode, the room temperature is lower than the desired temperature; in heating mode, the room temperature is higher than the desired temperature.| Adjust the desired room temperature.
In dehumidification (dry) mode, the ambient temperature is low.| Ensure that the room  is above 17°C for dry mode.
Doors or windows are open; there are a lot of people; or in cooling mode, there are other sources of heat (e.g. fridges).| Close doors and windows; increase air conditioning power.
The cooling or heating effect is poor.

| Doors or windows are open; there are a lot of people; or in cooling mode, there are other sources of heat (e.g. fridges).| Close doors and windows; increase air conditioning power.
The filters screen is dirty.| Clean or replace the filter screen.
The air inlet or outlet is blocked| Clear obstructions; make sure the unit is installed as per the instructions.
The air conditioner is leaking.| The unit is not straight.| Use a spirit level to check the unit is horizontal, if not remove from the wall and straighten.
 | The drain pipe is blocked.| Check the drain pipe to ensure it is not blocked or constricted.
Compressor does not work.| Overheat protection operational.| Wait for 3 minutes until the temperature is lowered, and then restart the machine.
The remote control does not work.| The distance between the machine and the remote control is too far.| Let the remote control get close to the air conditioner, and make that the remote control ure
The remote control is not aligned with the direction of the remote- control receiver.| directly faces to the direction of the remote-control receiver.
Batteries are dead.| Replace batteries.

If problems not listed in the table occur or recommended solutions do not work, please contact the service centre.

ERROR CODES

Fault Code| Fault Description| Fault Code| Fault Description
---|---|---|---
F1| Compressor IPM error| FE| EE error(outdoor)
F2| PFC/IPM error| PA| Return air sensor temperature abnormal protection
F3| Compressor start error| P1| Over-heat protection on top of compressor
F4| Compressor running out of step| PE| Abnormal refrigerant circulation
F5| Location detection loop failure| PH| Exhaust temperature protection
FA| Phase current overcurrent protection| PC| Coil tube overload protection (outdoor)
P2| Dc bus voltage Undervoltage protection| E3| DC fan Feedback failure (indoor)
E4| Communication error (indoor and outdoor)| P6| Coil tube overload protection (indoor)
F6| PCB communication error| P7| Defrost protection on coil tube (indoor)
P3| AC Input voltage protection| E2| Sensor error on indoor coil tube
P4| AC over-current protection| E1| Temperature sensor error (indoor)
P5| AC undervoltage protection| P8| Zero-crossing fault detection (indoor)
F7| Coil sensor error (outdoor)| EE| EE error (indoor)
F8| Sensor on suction pipe error| E5| Water-splash motor error
E0| Sensor on discharge pipe error| E8| Fan feedback fault
E6| Temperature sensor error (outdoor)| FL| Water-full protection
E7| Fan motor error (outdoor)| Eb| Fluoride deficiency protection
EA| Reversing fault of four-way valve|  |

GUARANTEE CONDITIONS

The air conditioner is supplied with a 24-month guarantee, commencing on the date of purchase. All material and manufacturing defects will be repaired or replaced free of charge within this period. The following rules apply:

  1. We expressly refuse all further damage claims, including claims for collateral damage.
  2. Repairs to or replacement of components within the guarantee period will not result in an extension of the guarantee.
  3. The guarantee is invalidated if any modifications have been made, non genuine parts are fitted or repairs are carried out by third parties.
  4. Components subject to normal wear, such as the filter, are not covered by the guarantee.
  5. The guarantee is valid only when you present the original, dated purchase invoice and if no modifications have been made to the product nor to the purchase invoice.
  6. The guarantee is invalid for damage caused by neglect or by actions that deviate from those in this instruction booklet.
  7. Transportation costs and the risks involved during the transportation of the air conditioner or air conditioner components shall always be for the account of the purchaser.
  8. Damage caused by not using suitable filters is not covered by the guarantee.

To prevent unnecessary expense, we recommend that you always first carefully consult the instructions for use. Take the air conditioner to your dealer for repairs if these instructions do not provide a solution.
Do not dispose of electrical appliances as unsorted municipal waste, use separate collection facilities. Contact your local government for information regarding the collection systems available. If electrical appliances are disposed of in landfills or dumps, hazardous substances can leak into the groundwater and get into the food chain, damaging your health and well-being. When replacing old appliances with new once, the retailer is legally obligated to take back your old appliance for disposal at least for free of charge. Do not throw batteries into the fire, where they can explode or release dangerous liquids. If you replace or destroy the remote control, remove the batteries and throw them away in accordance with the applicable regulations because they are harmful to the environment.
Environmental information: This equipment contains fluorinated greenhouse gases covered by the Kyoto Protocol. It should only be serviced or dismantled by professional trained personnel.
This equipment contains R290 / R32 refrigerant in the amount as stated in the table above. Do not vent R290 / R32 into atmosphere: R290 / R32, is a fluorinated greenhouse gas with a Global Warming Potential (GWP) = 3.Qlima
WDH 235 PTC Inverter Monoblock - PROFILE TAB 1Qlima WDH 235 PTC Inverter Monoblock - PROFILE TAB
2Qlima WDH 235 PTC Inverter Monoblock - PROFILE
TAB 3

Distributed in Europe by PVG Holding B.V.

If you need information or if you have a problem, please visit the our website (www.qlima.com) or contact our sales support (you find its phone number on www.qlima.com)

Qlima LogoPVG Holding BV – Kanaalstraat 12 C – 5347 KM
Oss – the Netherlands
P.O. Box 96 – 5340 AB Oss – the Netherlands

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals