mark 121EC Tanner MDA Luchtverwarmer Met EC Motor Instruction Manual
- June 21, 2024
- MARK
Table of Contents
mark 121EC Tanner MDA Luchtverwarmer Met EC Motor
Product Specifications:
-
Model: MDA 100, 200, 300, 400, 500
-
Dimensions: Vary based on model (refer to specific section for
detailed dimensions) -
Installation: Wall-mounted or ceiling-mounted
Includes: Anti-vibration set (optional), flow line, return line
Product Usage Instructions:
Wall-Mounted Installation:
To install the heater in a wall-mounted configuration with the anti-vibration set:
- Refer to the specific dimensions provided for your model in the manual.
- Ensure all connections are secure and follow the flow line and return line directions.
- Mount the heater using the wall bracket provided in the package.
- Check for proper alignment and stability before operation.
Ceiling-Mounted Installation
For ceiling-mounted installation with the anti-vibration set:
- Consult the detailed dimensions for ceiling-mounted configuration in the manual.
- Securely attach the heater to the ceiling bracket and follow flow line and return line instructions.
- Ensure that the unit is suitable for horizontal air distribution due to the condensate collection tray.
Frequently Asked Questions (FAQ):
Q: Is the MDA+ suitable for vertical air distribution?
A: No, the MDA+ is only suitable for horizontal air distribution due to the
condensate collection tray at the bottom of the unit.
Warning
Incorrect installation, adjustment, alteration, repair or maintenance work may
lead to material damage or injury. All work must be carried out by certified,
qualified professionals. If the appliance is not positioned in accordance with
the instructions, the warranty shall be rendered void. This appliance is not
intended for use by children or persons with a physical, sensory or mental
handicap, or who lack the required experience or expertise, unless they are
supervised or have been instructed in the use of the appliance by somebody who
is responsible for their safety.Children must be supervised to ensure that
they do not play with the appliance. The information in this document is
subject to change without notice. The most recent version of this manual is
always available at
www.markclimate.com/downloads.
Dimensions
Dimensions of the heater, wall-mounted, incl. anti-vibration set (option)
- Heater
- Wall bracket
- Anti vibration set
- Flow line
- Return line
- T Type
- G Connection
- Dimensions in mm
- Weight in kg
- Condensate connection ø 20 mm. Only for Tanner MDA+ for heating/cooling.
Dimensions of the heater, ceiling-mounted, incl. anti vibration set (option)
- Heater
- Ceiling bracket
- Anti vibration set
- Flow line
- Return line
- T Type
- Dimensions in mm
- Weight in kg
The MDA+ is only suitable for horizontal air distribution installation because of the condensate collection tray at the bottom of the unit.
Dimensions
Dimensions of the heater, ceiling mounted, incl. antivibration set (option)
- Heater
- Ceiling bracket
- Anti vibration set
- Flow line
- Return line
For dimensions and weights see 1.1.1
Condensate connection ø 20 mm. Only for Tanner MDA+ for heating/cooling.
Anti vibration set for horizontal airflow heaters (position number 21)
- T Type
- Z Order code
- Dimensions in mm
- Weight in kg
Installation
General
When connecting the heater onto the mains use an additional pipe wrench to
avoid twisting the pipe.
Max. operating pressure 14 Bar Max. water temp. 120 ºC
Connection (correct)
For correct connection, flow line B must be connected to the hot medium and
return line A to the cold medium.
- A Return line
- B Flow line
Connection (incorrrect)
Connections in upward or downward direction are not possible because of risk
of air locks
Frost protection
Because under certain circumstances (outside air colder than 5°C) there is a
risk of the heater freezing up, protection against freezing must be installed
to prevent this from happening!
Electrical diagrams
- Connection diagram for Tanner MDA(+) 230Vac.
- L = Lead
- N = Zero
- PE = Earth
- Connection diagram for Tanner MDA(+) 400Vac.
- Connection diagram for Tanner MDA(+) 1xx with EC-fan.
- Connection diagram for multiple Tanner MDA(+) 1xx with EC-fan
- Connection diagram for Tanner MDA(+) 2xx/3xx/4xx with EC-fan Anschlussplan für Tanner MDA(+)
- Connection diagram for multiple Tanner MDA(+) 2xx/3xx/4xx with EC-fan
- Connection diagram EEx 1.3.7
- A Connection diagram EEx
- B Option:Connection diagram motor 3~ position high with isolator switch.
- By changing L1 and L2 you can change the rotation direction.
Connection diagram
Connection diagram for Tanner MDA(+) 5xx 230Vac.
- L = Lead
- N = Zero
- PE = Earth
Connection diagram for Tanner MDA(+) 5xx 400Vac.
Connection diagram for Tanner MDA(+) 5xx with EC-fan.
Additional sections
Mark BV are glad to assist in the calculations and give you advise as regards planning on the basis of our wide experience.
Size
ABDFGHIKLNRSTU
- 100 390 415 443 463 690 740 690 380 440 800 516 386 439 212 120 406
- 200 520 545 573 593 920 920 820 510 570 895 666 516 573 253 151 530
- 300 670 695 723 743 1180 1240 975 665 720 940 796 666 724 300 175 680
- 400 800 835 853 873 1420 1240 1110 800 850 1075 1005 796 853 329 220 815
Additional sections
- Description
- Vertical louvres
- Downflow hood 4-sides vertical
- Downflow hood 4-sides horizontal
- Destratification hood
- Mixing box 2 sides manual control
- Mixing box for dampers
- Mixing box
- Damper section
- Filter section with filter (EU 3)
- Flexible connection
- Corner frame
- Mesh
- Weather grill ≤50% fresh air intake
- Weather grill >50%-100% fresh air intake
- Transition piece for 13
- Empty section (b=120 mm)
- Raincap incl. upstand (aluminium)
- Blanking plate Motor protection damper
- Empty section (B=240 mm) Wall bracket
- Shock absorber set for nr. 21 and 24
- Ceiling bracket vertical
- Shock absorber set for nr. 22
- Ceiling bracket set horizontal
- Induction damper
Maintenance
The regular maintenance and cleaning of the device depends only on the degree of soiling. This depends on the degree of dust in the external or ambient air.
Engine
The engine is maintenance-free. Occasionally it should be dried and made dust
free.
Heat exchanger
Clean the heat exchanger by blowing compressed air onto it. Take care of oil-
containing dust with an oil-soluble detergent. Use a steam cleaner to remove
sticky surface.
Note! Use low pressure as well as an intermediate distance to the heat
exchanger of at least 300mm.
MARK BV
BENEDEN VERLAAT 87-89 VEENDAM (NEDERLAND) POSTBUS 13, 9640 AA VEENDAM TELEFOON
+31(0)598 656600 FAX +31 (0)598 624584
info@mark.nl
www.mark.nl