Hazard warning!
Warning of hazards from electricity!
General safety precautions
Failure to observe these operating instructions presents hazards!
These instructions contain important information on the safe use of this product. Particular attention is drawn to potential hazards. Failure to observe this information may lead to death or serious injuries.
- Read instructions carefully.
- Follow safety advice.
- Keep instructions within easy reach.
– Working with electrical current may produce haz-ardous situations. Touching live parts can result in electrical shock, burns or death.
– Work on mains voltage must only be performed by qualified, skilled personnel.
– National wiring regulations and electrical oper-ating conditions must be observed (e.g. DE: VDE 0100, AT: ÖVE-ÖNORM E8001-1, CH: SEV 1000).
– Only use genuine replacement parts.
– Repairs must only be carried out by companies qualified to do so
System description
Proper use
– DALI2 relay that enables the switching of connected loads.
– Suitable for installation in a concealed box with a minimum depth of 60 mm.
Operating principle
– REL5A DALI2 that enables the switching of connected loads that cannot be
integrated into the DALI bus independently, such as non-dimmable lights.
– REL5A DALI2 can be addressed by the application controller and switches the
connected consumers with ON or dim telegrams >0.
– REL5A DALI2 follow the signals from the application controller (APC) /
control unit via DALI.
– REL5A DALI2 is powered by 230V.
Package contents
– 1 relay module
– 1 safety data sheet
– 1 quick-start guide
Product dimensions
Product components
A Connection of supply voltage and relay output
B DALI-2 input
Electrical connection
Wiring diagrams
The mains supply lead is a multiple-core cable:
L = Phase (usually black, brown or grey)
N = Neutral conductor (usually blue)
DA+ = connection to the DALI BUS (brown)
DA- = connection to the DALI BUS (brown)
OUT = Phase output
Installation
Hazard from electrical power.
Touching live parts can result in electrical shock, burns or death.
- Switch OFF power and interrupt power supply.
- Using a voltage tester, check to make sure that the power supply is disconnected.
- Make sure power supply remains interrupted.
Risk of damage to property!
Mixing up connection leads may produce a short circuit.
- Identify connection leads.
- Connect the leads correctly.
Preparing for installation
-
Check all components for damage. Do not use the floodlight if it is damaged.
-
Familiarise yourself with the fitting situation and the relevant documentation.
-
Select an appropriate site to install the product.
– Vibration-free.
– Not in explosive atmospheres.
– Not on normally flammable surfaces. -
Put together the tools and material needed:
– Screwdriver.
Installation procedure
-
Make sure the power supply is switched OFF.
-
Connect mains power supply lead as shown in the wiring diagram.
-
„4. Electrical connection“
-
Fit the relay module into the box.
-
Fit a cover onto the box.
-
Switch ON power supply.
Cleaning and maintenance
The tool requires no maintenance.
Hazard from electrical power.
Contact between water and live parts can result in electric shock, burns or
death.
• Only clean tool in a dry state.
Disposal
Electrical and electronic equipment, accessories and packaging must be recycled in an environmen-tally compatible manner.
Do not dispose of electrical and electronic equipment as domestic waste.
EU countries only:
Under the current European Directive on Waste Electrical and Electronic Equipment and its implementation in national law, electrical and electronic equipment no longer suitable for use must be collected separately and recycled in an environmentally compatible manner.
Conformity
STEINEL GmbH hereby declares that the REL5A DALI2 radio equipment type conforms to Directive 2014/53/EU. The full wording of the EU Declaration of Conformity is available for downloading from the following Internet address: www.steinel.de
Manufacturer’s Warranty
Manufacturer’s warranty of STEINEL GmbH, Diesel strasse 80-84, DE-33442 Herzebrock-Clar- holz, Germany
All STEINEL products meet the highest quality standards. For this reason, we, the manufacturer, are pleased to provide you, the customer, with a warranty under the following terms and conditions:
The warranty covers the absence of deficiencies which are proven to be the result of a material defect or fault in manufacturing and which are re- ported to us immediately after detection and within the warranty period. The warranty shall cover all STEINEL Professional products sold and used in Germany.
Our warranty cover for consumers
The provisions below apply to consumers. A consumer is any natural person who,
on entering into the purchase transaction, neither acts in exercising their
commercial nor their self-employed activity.
You can opt for warranty cover in the form of repair or replacement which will be provided free of charge (if applicable, in the form of a successor model of the same or higher quality) or in the form of a credit note.
In the case of sensors, floodlights, outdoor and indoor lights, the warranty period for the STEINEL Professional product you have purchased is 5 years in each case from the date on which the product was purchased
We shall bear the shipping costs but not the trans- port risks involved in return shipment.
Our warranty cover for entrepreneurs
The provisions below apply to entrepreneurs. Entre- preneur is a natural or
legal person or partnership with legal personality who or which, on entering
into the purchase transaction, acts in exercising their or its commercial or
self-employed activity. We have the option of providing warranty cover by
rectifying deficiencies free of charge, replacing a product free of charge (if
applicable, in the form of a successor model of the same or higher quality) or
by issuing a credit note.
In the case of sensors, floodlights, outdoor and indoor lights, the warranty
period for the STEINEL Professional product you have purchased is 5 years in
each case from the date on which the product was purchased.
Within the scope of warranty cover, we shall not bear your expenses accruing from subsequent fulfillment nor shall we bear your expenses for removing the defective product and installing a replacement product.
Statutory rights accruing from defects, gratuitousness
The warranty cover described here shall be applicable in addition to the
statutory rights of warranty including special consumer protection provisions
and shall not restrict or replace them. Exercising your statutory rights in
the event of defects is gratuitous.
Exemptions from the warranty
All replaceable lamps are expressly excluded from this warranty.
– In addition to this, the warranty shall not cover:
– any wear resulting from use or any other natural wear of product parts or
any deficiencies in the STEINEL Professional product that are attributable to
wear caused by use or other natural wear,
– any improper or non-intended use of the product or any failure to observe
the operating instructions,
– any unauthorised additions, alterations or other modifications to the
product or any deficiencies attributable to the use of accessory,
– supplementary or replacement parts which are not genuine STEINEL parts,
– any maintenance or care of products that is not carried out in accordance
with the operating instructions,
– any attachment or installation that is not in accordance with STEINEL’s
installation instructions,
– any damage or loss occurring in transit.
Application of German law
The warranty shall be governed by German law excluding the United Nations Convention concerning the International Sale of Goods (CISG).
Making claims
If you wish to make a warranty claim, please send your product complete and carriage paid with the original receipt of purchase, which must show the date of purchase and product designation, either to your retailer or directly to us at STEINEL (UK) Ltd. – 25 Manasty Road, Axis Park, Orton Southgate, GB- Peterborough Cambs PE2 6UP United Kingdom. For this reason, we recommend that you keep your receipt of purchase in a safe place until the warranty period expires.
Technical specifications
– Dimensions (H x W x D): 45 x 45.5 x 20.3 mm
– Power supply: 100-240 V~, 50/60 Hz
– Power consumption stand by: 0.5 W
Output, relay
– Switching voltage AC: 100-240 V, 50/60 Hz
– Resistive load: max. 4.3 A
– Capacitive load: max. 1.3 A
– Inductive load: max. 4.3 A
Switching capacity:
– Incandescent / halogen lamp load: 1,000 W
– LED/ECG – load
300 W (max. 50 pcs, C < 176 μF)
– Mounting:
into installation box, junction box
– Max.housing temperature: 50°C
– IP rating: IP 20
– Ambient temperature: -25°C to +50°C
– Factory setting: contact closed
Troubleshooting
Unit without power.
– Fuse not switched ON or faulty.
• Switch ON fuse.
• Change faulty fuse.
– Break in wiring.
• Check wiring with voltage tester.
– Short circuit in mains power supply lead.
• Check connections.
– Any mains switch OFF
• Switch ON mains switch.