Carrier ZS27 Immersion Temperature Sensor Instructions

June 13, 2024
Carrier

Carrier ZS27 Immersion Temperature Sensor

To wire a ZS immersion temperature sensor

NOTES

  • Do not drill into the sensor’s watertight enclosure which will violate the NEMA and/or IP rating.
  • Use caulk or Teflon tape for your conduit entries to maintain the appropriate NEMA or IP rating for your application.
  • For outdoor or wet applications, conduit entry should be from the bottom of the enclosure.

PREREQUISITE The Rnet cable is wired to the controller. The shield wire and the ground wire should be inserted into the controller’s GND terminal.

  1. Turn off the controller’s power.

  2. Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation.

  3. Strip about 0.25 inch (0.6 cm) of the inner insulation from each wire.

  4. Unlatch and open the hinged door on the sensor’s enclosure.

  5. Pull the Rnet communication cable through the knockout hole.

  6. If wiring 1 cable to the sensor, cut the shield wire off at the outer jacket, then wrap the cable with tape at the outer jacket to cover the end of the shield wire.
    If wiring 2 cables in a daisy-chain configuration, twist together the shield wires, then wrap the shield wires with tape.

  7. Insert the other 4 wires into the sensor’s screw terminal connector. If wiring 2 cables, insert like-colored wires into each terminal. 

CAUTION Allow no more than 0.06 inch (1.5 mm) bare communication wire to protrude. If bare communication wire contacts the cable’s foil shield, shield wire, or a metal surface other than the terminal block, the device may not communicate correctly.

  • Close and latch the sensor’s door.
  • Turn on the controller’s power.
    NOTE Use the same polarity throughout the Rnet.

ZS outdoor air temperature sensors

ZS outdoor sensors measure temperature or temperature/humidity.

Specifications for ZS outdoor air sensors

Probe

  • Temperature sensor probe:
  • Vented polycarbonate shield, .5 in. (1.27 cm) OD 1.2 in. (3.05 cm)
  • Temperature/humidity sensor probe:
  • ABS with SS filter
  • 1.0 in. (2.5 cm) diameter
  • 2.4 in. (6.1 cm) length

To address a ZS outdoor air temperature sensor

  • Each ZS Sensor on an Rnet must have a unique address, but addresses do not have to be sequential.
  • Open the hinged cover on the sensor enclosure, and then use the DIP switches to set an address from 0 to 14. (0 is factory default.) Each DIP switch has the value shown in the figure below. Turn on as many DIP switches as you need so that their total value equals the address.

EXAMPLE DIP switches 1 and 4 above are on. Their values (1 + 8) total 9, so the sensor’s address is 9.

To mount a ZS outdoor air temperature sensor

Outside Air Temperature/Humidity sensor

  1. Determine the best location for the sensor. Mount the sensor:

    • In the shade, never in the sunlight or you will have higher than expected temperature readings by as much as +30%.
    • Away from building windows, doors, or vents.
    • At least one foot below the eave to prevent measurement of trapped heat under the eave.
    • At least four feet about ground level.
  2. Drill the mounting holes and mount as shown below with the probe pointing down. Tighten the mounting screws enough to ensure that the foam backing compresses to about 50% of its thickness to create a seal against the wall surface.

  3. Unlatch and open the hinged door on the sensor’s enclosure.

  4. Route the Rnet cable into the back of the enclosure, and then connect the wiring as described in To wire a ZS outside air sensor (page 35).

  5. Unlatch and open the hinged door on the sensor’s enclosure.
    Route the Rnet cable into the back of the enclosure, and then connect the wiring as described in To wire a ZS outside air sensor (page 35).

  6. After wiring the sensor, caulk the wiring hole.

  7. Close the enclosure door until it latches. Secure with provided cover screws.

To wire a ZS outdoor air sensor

NOTES

  • Do not drill into the sensor’s watertight enclosure which will violate the NEMA and/or IP rating.
  • Use caulk or Teflon tape for your conduit entries to maintain the appropriate NEMA or IP rating for your application.

PREREQUISITE The Rnet cable is wired to the controller. The shield wire and the ground wire should be inserted into the controller’s GND terminal.

  1. Turn off the controller’s power.
  2. Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner  insulation.
  3. Strip about 0.25 inch (0.6 cm) of the inner insulation from each wire.
  4. Unlatch and open the hinged door on the sensor’s enclosure.
  5. Pull the Rnet communication cable through the knockout hole.
  6. If wiring 1 cable to the sensor, cut the shield wire off at the outer jacket, then wrap the cable with tape at the outer jacket to cover the end of the shield wire.  If wiring 2 cables in a daisy-chain configuration, twist together the shield wires, then wrap the shield wires with tape.
  7. Insert the other 4 wires into the sensor’s screw terminal connector. If wiring 2 cables, insert like-colored wires into each terminal.
  8. Automated Logic® recommends that you use the following Rnet wiring scheme:

CAUTION Allow no more than 0.06 inch (1.5 mm) bare communication wire to protrude. If bare communication wire contacts the cable’s foil shield, shield wire, or a metal surface other than the terminal block, the device may not communicate correctly.

Close and latch the sensor’s door.
Turn on the controller’s power.

NOTE Use the same polarity throughout the Rnet.

Humidity filter maintenance

The temperature/humidity sensor has a sintered filter that protects the humidity sensor from various airborne particles. The filter can become dirty and may need periodic cleaning. Symptoms of a dirty filter are that the humidity sensor is slow to respond or consistently reports incorrect values.
To clean the filter :

  1. Gently unscrew the filter from the probe.
  2. Rinse the filter in warm soapy water, and then rinse in clean water. You can use a nylon brush if needed.
  3. Gently screw the clean filter all the way into the probe. Hand tighten only.

To format a ZS Sensor
Formatting a sensor clears its flash memory. Do either of the following to format a sensor:

  • Download the controller that the sensor is connected to.
  • Do the following:
    • Remove the wiring connector from the sensor.
    • Note the current position of the DIP switches.
    • Set all DIP switches to the ON position.
    • Reattach the wiring connector to format.
    • After approximately 3 seconds, remove the wiring connector.
    • Set the DIP switches back to their original position.
    • Reattach the wiring connector.

NOTE If you move a sensor from one controller to another controller that has a different control program, format the sensor.

Append ix: voes detected

VOC families that can be detected by our sensors are:

  • CO, CH4, LPG
  • Alcohols
  • Ketones (solvents). Examples are Acetone and Methyl Ethyl Ketone (MEK).
  • Organic Acids. Examples are Lactic acid, Acetic acid, Formic acid, Citric acid, and Oxalic acid.
  • Amines. Amines are derivatives of ammonia. See http://en.wikipedia.org/wikijCategory:Amines.
  • Aliphatic hydrocarbons. These are flammable with little or no odor. Examples are hexane, paraffin, methane, and acetylene.
  • Aromatic Hydrocarbons. These are flammable with a discernable odor. Examples are benzene, furan, pyridine, toluene, asphaltene, and picric acid.

Over 10,000 specific chemicals are listed as voes, but some of the more common chemicals are:

  • Dipropylene glycol
  • Ethanol
  • Ethyl Alcohol
  • Eucalyptol
  • Formaldehyde
  • Heptane
  • Hydrocarbons
  • lsobutane
  • lsobutene
  • lsoprene
  • Limonene
  • Methane
  • Methoxyethanol
  • Methoxyethoxyethanol
  • Methylcyclohexane
  • Methylethylketone
  • Methyl methacrylate
  • Naphthalene
  • Nonanal
  • Organic Chloramines
  • Pentane
  • Phenol
  • Pinene
  • Propane
  • Siloxanes
  • Tetrachloroethene
  • Tetrachloroethylene
  • Toluene
  • Trichloromethane
  • r (1-methylethyl)cyclopropane
  • Xylene

Many things contain these chemicals. For example, cigarette smoke contains benzene and carbon monoxide. Propane (R290/LPG) is commonly used in contemporary refrigerant blends. Most of the above chemicals can be found in cleaners, disinfectants, perfumes, polishes, plastics, glues and lubricants.

  • Below 1000 ppm = Safe
  • 1000-1500 ppm = Warning
  • Over 1500 ppm = Poor air quality

Document revision history

Important changes to this document are listed below. Minor changes such as typographical or formatting errors are not listed.

Date Topic Change description **Code***
3/1/19 Specifications for ZS zone sensors Motion sensor specifications –

Detector distance:

Changed 16.4 in. to 16.4 ft.

| X-0-MW-E
8/24/18| Rnet configuration| Added OptiPoint™ Interface and revised wording of first half of topic.| X-D
| Power requirements| Added OptiPoint™ Interface|
7/9/18| Power requirements| On the drawing, removed the power of the controller’s Rnet port.

Added first bullet under CAUTIONS.

| X-0-RS-E
---|---|---|---
| ZS zone sensors – Specifications| Changed description of Power supply spec.|
| CO2 sensor installation| Added paragraph regarding one hour after installation to|
| | attain accurate readings.|
3/6/18| Specifications for ZS zone sensors| Changed Sensing element accuracy for Humidity

from 10% to 90%: ±1.8% typical

to 20% to 80%: ±2% typical.

| X-0-AR-O
| Appendix: voes detected| New topic.| X-0-RS-E
1/8/18| What are ZS sensors? Power requirements ZS zone sensors

Specifications for ZS zone sensors

To wire and mount a ZS zone sensor

| Changed topics to show new zone sensor design.| X-D
---|---|---|---
8/10/17| What are ZS sensors?| Added product part numbers in this topic.| A-0-F-AR
7/26/17| Rnet configuration| Changed version 3.3.11 to 3.4.02 and changed

v03.05.03 to 03.05.02. Also changed version number

| X-TS-AP-F
| | on graphic to v03.05.02.|
5/31/17| Specifications for:

ZS pipe clamp-on sensor

ZS immersion sensor ZS outdoor air sensors

| Corrected specification for Sensing element.

Removed Environmental operating range specification.

| X-0-AR-E
---|---|---|---
5/10/17| Troubleshooting a ZS Pro or ZS

Pro-F

| Added Effective Setpoints Fields descriptions.| X-TS-EE-BR
1/30/17| Specifications for ZS zone sensors| Added CO2 sensor type.| X-TS-JM-F
1/19/17| Entire document| Major revisions to add a motion sensor to a ZS Pro, duct| X-D
| | sensors, pipe sensor, immersion sensor, and outdoor air|
| | sensors.|
3/8/16| Specifications| Added drift statement to Humidity specification.| X -TS-EE-F
4/27/15| Entire document| New look, no content changes.| A-D
2/27/15| CO2 sensor installation| New topic.| X-TS-RB-BR
11/11/14| Power requirements| Made corrections to wiring diagram.| X-TS-JM-0
7/22/14| Specifications| Revised the following specifications:

Sensing element accuracy Environmental operating range

**** Added following statement to Power supply specification: “The controller and the external power supply must share a common ground.”

| X-0-MW-E-SV
---|---|---|---

  • ZS Sensors
  • Rev. 2023-11-14
  • ALC Proprietary and Confidential
  • © 2023 Automated Logic Corporation All rights reserved

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Carrier User Manuals

Related Manuals