BOURNS 1250A Series General Duty AC Surge Protective Device Installation Guide

June 11, 2024
BOURNS

1250A SeriesGeneral Duty AC Surge Protective Device
INSTALLATION INSTRUCTIONS

General Information

The Bourns® Model 1250A series is defined as a high performance surge protection solution for most commercial and industrial environments with critical operations needing protection against the harmful effects of transient surges. These surges are the result of:

  • Direct and indirect lightning strikes
  • Power company load switching
  • Upstream load switching at other facilities

This unit is intended for point-of-entry or sub-board protection and should be connected in parallel with the power system.
WARNING!
Only qualified personnel should install or service this system.
Electrical safety precautions must be followed when installing or servicing this equipment. To prevent risk of electrical shock, turn off and lock out all power sources to the unit before making electrical connections or servicing.
For proper and safe operation, neutral and ground MUST be reliably connected. Failure to operate this unit from a solidly grounded power source of the proper configuration will reduce or impede operation, and may result in unit failure.

Installation

BOURNS 1250A Series General Duty AC Surge Protective Device - DIN-
Rail

  1. When installing or replacing the SPD, it must be in a deenergized condition.
  2. Install the DIN mounting rail (35 mm, re: EN 50022).
  3. Snap-lock the SPD to the rail.
  4. Connect wiring to the indicated terminals.
  5. Ensure compliance with supplied instructions.
  6. Apply power and observe correct operation of status indicators and, if utilized, remote alarm facilities.
  7. Never Hi-Pot test any SPD. (This will cause premature failure or damage to the SPD.)

Wiring Connections

Conductor Type| |
---|---|---
Min. Cross-section| L&N terminal: #12AWG (4 mm2)
PE terminal: #10AWG (6 mm2)
Max. Cross-section| #4AWG or 25 mm2(stranded)| #2AWG or 35 mm2(solid)
Insulation Stripped Back| 0.4 in. or 10 mm

Table 1: Connection wire size

Correct Incorrect

Insulation not cut back enough
Insulation cut back too far

Fig. 2: Tightening the terminal

Before making connections to the unit, verify that the unit model number and nameplate voltage rating are appropriate for connection to the intended power source.
For best performance, the unit should be positioned so that the length of the wiring to the Surge Protective Device (SPD) unit is minimized.
Each SPD terminal is designed to accept wire sizes from #12AWG (4 mm 2 ) to

2AWG (35 mm 2 ) solid conductor or #4AWG (25 mm 2 ) stranded conductor.

Insulation should be stripped back 10 mm before terminating into tunnel terminal.
Do not use excessive force when tightening the terminal; 2 ~ 2.5 Nm (1822 lb- in) is recommended.
WARNING! Select the proper Bourns® SPD unit according to your system voltage, configuration, and the anticipated surge environment.
Prior to installing the SPD, ensure that your facility’s electric supply system is properly installed and connected in accordance with all applicable national and local codes and safety procedures.

Specifications are subject to change without notice.
Users should verify actual device performance in their specific applications.
The products described herein and this document are subject to specific legal disclaimers as set forth on the last page of this document, and at www.bourns.com/docs/legal/disclaimer.pdf.

Status Indicator & Remote Signal

Remote Signal Contact

|
Normal| Fault (Needs to be Replaced)

Table 2: Remote signal contact indication

A characteristic of all transient and surge protection devices is that they degrade in proportion to the magnitude and number of surge incidents to which they have been subjected. Status indication should be periodically monitored to determine if replacement is required. When the SPD indicator window turns RED, the remote signal contact closes between C (common) and NO (normally open). The pluggable module should be replaced as soon as possible.

Product Ratings & Limitations

Type 2CA SPD – Permanently connected SPDs for use on the load side of the main service disconnect, as described in the Standard for Safety, Surge Protective Devices (SPDs), UL-1449, Fourth Edition.
Voltage Protection Rating – To obtain the Voltage Protection Rating (VPR), in accordance with the Standard for Safety, Surge Protective Devices (SPDs), UL-1449, Fourth Edition, released 2014, as indicated on this product, the wire specified must be utilized to connect the SPD to your facility’s power grid. Connections made with unapproved conductors may result in different VPRs.
Circuit Ampacity Limitations – This product has been tested to withstand, without exposing live circuits or components on power sources, a voltage of two times (2x) the device ratings, and fault currents of up to 200 kA, as described in the Standard for Safety, Surge Protective Devices (SPDs), UL-1449, Fourth Edition, released 2014.

Product Dimensions

Single Pole![BOURNS 1250A Series General Duty AC Surge Protective Device

Troubleshooting

If any of the diagnostic indicators reveal a problem, check all connections and voltages to the unit. If all connections are made and reliable, and proper voltages are supplied to the unit, please contact www.bourns.com.
NOTE
This guide is not comprehensive. It is assumed that the user will follow established safety precautions for working in an electrical environment. For more information on safety precautions and procedures, please consult the related organizations listed below.

  • Underwriters Laboratories (UL)
  • American National Standards Association (ANSI)
  • Institute of Electrical and Electronics Engineers (IEEE).
  • National Fire Protection Association (NFPA)
  • National Electrical Mfgrs. Association (NEMA)
  • International Electrotechnical Commission (IEC)

Product Dimensions (continued)

Two PolesBOURNS 1250A Series General Duty AC Surge Protective Device - Two
PolesThree PolesBOURNS
1250A Series General Duty AC Surge Protective Device - Three
PolesFour PolesBOURNS
1250A Series General Duty AC Surge Protective Device - Four
Poles

Power Distribution and SPD Connection

BOURNS 1250A Series General Duty AC Surge Protective Device - SPD
Connection

Legal Disclaimer Notice

This legal disclaimer applies to purchasers and users of Bourns ® products manufactured by or on behalf of Bourns, Inc. and its affiliates (collectively, “Bourns”).
Unless otherwise expressly indicated in writing, Bourns ® products and data sheets relating thereto are subject to change without notice. Users should check for and obtain the latest relevant information and verify that such information is current and complete before placing orders for Bourns ® products.
The characteristics and parameters of a Bourns® product set forth in its data sheet are based on laboratory conditions, and statements regarding the suitability of products for certain types of applications are based on Bourns’ knowledge of typical requirements in generic applications. The characteristics and parameters of a Bourns® product in a user application may vary from the data sheet characteristics and parameters due to (i) the combination of the Bourns® product with other components in the user’s application, or (ii) the environment of the user application itself. The characteristics and parameters of a Bourns product also can and do vary in different applications and actual performance may vary over time. Users should always verify the actual performance of the Bourns® product in their specific devices and applications, and make their own independent judgments regarding the amount of additional test margin to design into their device or application to compensate for differences between laboratory and real world conditions.
Unless Bourns has explicitly designated an individual Bourns® product as meeting the requirements of a particular industry standard (e.g., ISO/TS 16949) or a particular qualification (e.g., UL listed or recognized), Bourns is not responsible for any failure of an individual Bourns ® product to meet the requirements of such industry standard or particular qualification. Users of Bourns® products are responsible for ensuring compliance with safety- related requirements and standards applicable to their devices or applications.
Bourns® products are not recommended, authorized or intended for use in nuclear, lifesaving, life-critical or life-sustaining applications, nor in any other applications where failure or malfunction may result in personal injury, death, or severe property or environmental damage. Unless expressly and specifically approved in writing by two authorized Bourns representatives on a case-by-case basis, use of any Bourns ® products in such unauthorized applications might not be safe and thus is at the user’s sole risk. Life- critical applications include devices identified by the U.S. Food and Drug Administration as Class III devices and generally equivalent classifications outside of the United States.
Bourns expressly identifies those Bourns® standard products that are suitable for use in automotive applications on such products’ data sheets in the section entitled “Applications.” Unless expressly and specifically approved in writing by two authorized Bourns representatives on a case-by-case basis, use of any other Bourns® standard products in an automotive application might not be safe and thus is not recommended, authorized or intended and is at the user’s sole risk. If Bourns expressly identifies a sub-category of automotive application in the data sheet for its standard products (such as infotainment or lighting), such identification means that Bourns has reviewed its standard product and has determined that if such Bourns standard product is considered for potential use in automotive applications, it should only be used in such sub-category of automotive applications. Any reference to Bourns® standard product in the data sheet as compliant with the AEC-Q standard or “automotive grade” does not by itself mean that Bourns® has approved such product for use in an automotive application.
Bourns ® standard products are not tested to comply with United States Federal Aviation Administration standards generally or any other generally equivalent governmental organization standard applicable to products designed or manufactured for use in aircraft or space applications. Bourns expressly identifies Bourns ® standard products that are suitable for use in aircraft or space applications on such products’ data sheets in the section entitled “Applications.” Unless expressly and specifically approved in writing by two authorized Bourns representatives on a case-by-case basis, use of any other Bourns standard product in an aircraft or space application might not be safe and thus is not recommended, authorized or intended and is at the user’s sole risk.
The use and level of testing applicable to Bourns ® custom products shall be negotiated on a case-by-case basis by Bourns and the user for which such Bourns ® custom products are specially designed. Absent a written agreement between Bourns and the user regarding the use and level of such testing, the above provisions applicable to Bourns ® standard products shall also apply to such Bourns ® custom products.
Users shall not sell, transfer, export or re-export any Bourns ® products or technology for use in activities which involve the design, development, production, use or stockpiling of nuclear, chemical or biological weapons or missiles, nor shall they use Bourns ® products or technology in any facility which engages in activities relating to such devices. The foregoing restrictions apply to all uses and applications that violate national or international prohibitions, including embargos or international regulations. Further, Bourns ® products and Bourns technology and technical data may not under any circumstance be exported or re-exported to countries subject to international sanctions or embargoes. Bourns ® products may not, without prior authorization from Bourns and/or the U.S. Government, be resold, transferred, or re-exported to any party not eligible to receive U.S. commodities, software, and technical data.
To the maximum extent permitted by applicable law, Bourns disclaims (i) any and all liability for special, punitive, consequential, incidental or indirect damages or lost revenues or lost profits, and (ii) any and all implied warranties, including implied warranties
of fitness for particular purpose, non-infringement and merchantability.

For your convenience, copies of this Legal Disclaimer Notice with German, Spanish, Japanese, Traditional Chinese and Simplified Chinese bilingual versions are available at:
Web Page: http://www.bourns.com/legal/disclaimers-terms-and- policies
PDF: http://www.bourns.com/docs/Legal/disclaimer.pdf
C1753 05/17/18R

*RoHS Directive 2015/863, Mar 31, 2015 and Annex.
Actual product may differ from image shown.
Specifications are subject to change without notice.
Users should verify actual device performance in their specific applications.
The products described herein and this document are subject to specific legal disclaimers as set forth on the last page of this document, and at www.bourns.com/docs/legal/disclaimer.pdf.
Asia-Pacific: Tel: +886-2 2562-4117 • Email: asiacus@bourns.com
EMEA: Tel: +36 88 885 877 • Email: eurocus@bourns.com
The Americas: Tel: +1-951 781-5500 • Email: americus@bourns.com
www.bourns.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals