SmartGen ATA821 Bus Tie Adaptor for Dual Power Switch User Manual
- June 4, 2024
- SmartGen
Table of Contents
ATA821
BUS TIE ADAPTOR FOR DUAL POWER SWITCH
USER MANUAL
SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.
Chinese trademark
English trademark
SmartGen — make your generator smart
SmartGen Technology Co., Ltd.
No.28 Jinsuo Road, Zhengzhou, Henan Province, China
Tel: +86-371-67988888/67981888/67992951
+86-371-67981000(overseas)
Fax: +86-371-67992952
Email: sales@smartgen.cn
Web: www.smartgen.com.cn
www.smartgen.cn
All rights reserved. No part of this publication may be reproduced in any
material form (including photocopying or storing in any medium by electronic
means or other) without the written permission of the copyright holder.
Applications for the copyright holder’s written permission to reproduce any
part of this publication should be addressed to SmartGen Technology at the
address above. Any reference to trademarked product names used within this
publication is owned by their respective companies.
SmartGen Technology reserves the right to change the contents of this document
without prior notice.
Table 1 Software Version
Date | Version | Note |
---|---|---|
30-12-19 | 1 | Original Release. |
20-01-20 | 1.1 | Upgrade. |
25-02-21 | 1.3 | Add illustration for optional terminals. |
OVERVIEW
ATA821 Bus Tie Adapter for Dual Power Switch is a kind of adapter which makes convenience for connection between HAT821 dual power bus tie ATS controller and smart breaker, reducing a lot of field wiring work for users, not only labor saving, time saving but also reliable.
PERFORMANCE AND CHARACTERISTICS
- Suitable for 3Ph 4W AC system;
- Two integrated 400V/50Hz/10A circuits of air breaker, which are individually used to connect two circuits of AC power;
- All-in-one integrated adaptor, which can simultaneously connect S1 breaker, S2 breaker and bus tie breaker;
- Suitable for HAT821 dual power bus tie ATS controller;
- Cold rolled plate closure;
- With screw installation method, adapter is fixed by 4 screws.
SPECIFICATION
Table 2 Performance Parameters
Item | Description |
---|---|
Rated Working Voltage | AC 400V 50/60Hz |
Max Working Current | 10A |
Air Breaker | 400V~ 50Hz 10A |
Case Dimensions | 144.4mmx252mmx75.3mm |
Working Conditions | Temperature: (-25~+70)°C Humidity: (20~93)%RH |
Storage Condition | Temperature: (-30~+80)°C |
Insulation Strength | Apply AC1.5kV voltage between high voltage terminal and |
low voltage terminal and the leakage current is not more than 3mA within 1min.
Weight| 1.6kg
PANEL DESCRIPTION
PANEL ILLUSTRATION
Panel illustration is as Fig. 1.
Two circuits of air breaker, connect separately with S1/S2 AC power.
Connector M1, M2, M3 need to connect to the side of HAT821 controller.
Connector S1-A, S1-B need to connect to the side of S1 breaker.
Connector S2-A, S2-B need to connect to the side of S2 breaker.
Connector STIE-A, STIE-B need to connect to the side of bus tie breaker.
Fig. 1 Panel Instruction
CONNECTOR ILLUSTRATION
The pin numbers of connector terminals are as Fig. 2.
Fig. 2 Pin Numbers of Connector Terminals
Terminal Wirings of connector is as Table 3.
Table 3 Connector Wiring Illustration
Connector
No.| Pin
No.| Wire
No.| Wire Harness No.| Connector
No.| Pin
No.| Wire
No.| Wire Harness
No.
---|---|---|---|---|---|---|---
M1| 1| M-18| WH821-M-20-RM| S1-A| 1| 01-32| WH821-Q1-3ORM
2| M-19| 2| Q1-28
3| M-15| 3| Q1-27
4| M-20| 4| Q1-35
5| NC| 5| Q1-1
6| M-17| 6| NC
7| M-21| 7| Q1-33
8| M-22| 8| 01-30
9| M-16| 9| Q1-2
M2| 1| M-4| 10| Q1-24
| | |
2| M-14| 11| Q1-36
3| M-1| 12| Q1-29
4| M-10| 13| Q1-41
5| M-11| 14| Q1-25
6| M-3| 15| Q1-42
7| M-2| S1-I3| 1| NC
8| M-9| 2| Q1-4
9| M-5| 3| Q1-22
10| M-6| 4| NC
11| NC| 5| Q1-23
12| M-7| 6| Q1-5
13| M-8| |
14| M-12| |
15| M-13| |
M3| 1| M-29| |
2| M-30| |
3| M-41| |
4| NC| |
5| M-34| |
6| M-35| |
7| M-31| |
8| M-36| |
NOTE: Connector S2-A and S2-B, STIE-A and STIE-B connected wire number starts with Q2, Q3; Others are the same with S1-A, S1-B, connected separately with WH821-Q2-30-RM and WH821-Q3-30-RM. For example: P1 wire number of connector S2-A is Q2-32.
Wire number definition:
APPLICATION DIAGRAM
Fig. 3 Application Diagram
OPTIONAL ACCESSORY ILLUSTRATION
The connected wire harness and terminals matched with terminal block of this product are optional; Users can make clarification at ordering, note the harness requirements and breaker type. See Table 4 for details.
Table 4 Optional Accessory Description
Category | Note |
---|---|
Optional Wire Harness | There are four in total, one of them will be connected |
to the controller side and the other three will be connected to the circuit
breaker side. The length of the wire harness (unit: m) and the model of the
circuit breaker should be indicated when choosing.
Optional Terminals| Include the matching terminals and connector terminals.
CASE DIMENSIONS
This adapter is designed by screw installation method, and is fixed by four screws at installation. Unit: mm
Fig. 4 Case Dimensions and Cutout