Green Cell UPS Power Proof 600VA-2000VA User Manual

June 7, 2024
Green Cell

Green Cell UPS Power Proof 600VA-2000VA

SAFETY

  • Risk of Electric Shock – The UPS device does not have a structure that allows the user to perform independent repairs or replacement. Do not open the housing yourself.
  • The UPS is powered by a sealed, maintenance-free 12V lead-acid battery in AGM technology.
  • If you connect the device to a non-bipolar, three-core, grounded outlet, there is a risk of electric shock.
  • In the event of a fault, the device should be switched off with the built-in button, then disconnected from the mains and all devices connected to the UPS must be disconnected.
  • The device is not protected against moisture. Avoid use in damp rooms. Do not place it near containers with liquid and moisture sources.
  • The device is suitable for work in room conditions.
  • Do not plug the device into its own power outlet. Do not plug the mains plug into the output socket of the device.
  • The UPS has internal guards and stabilizers and limited power. Therefore, do not connect any additional surge protection devices, extension cords or power distributors.
  • The UPS is not suitable for powering equipment outside the category of IT equipment. It can not be used to power medical devices or household appliances (kettles, vacuum cleaners, microwave ovens).
  • To prevent overheating, do not cover the unit, block the access to the air, expose to sunlight, or install it near heat sources such as radiators or heaters.
  • Disconnect the device from the power source before cleaning. Do not use liquid detergents to clean the device.
  • Do not throw the battery into the fire as it can explode.
  • Do not disassemble the built-in battery. The electrolyte is dangerous to eyes and skin.
  • Follow these safety instructions to avoid a short circuit or electric shock:
  • 1. When handling the battery, remove all metal parts (rings, watches) by hand;
  • 2. Use only tools with insulated handles;
  • 3. Use insulating gloves;
  • 4. Do not place metal tools on the battery case near the terminals;
  • 5. Before disconnecting the battery, turn off the UPS and disconnect the power plug from the electrical outlet.
  • Repairs and replacement of the battery must only be carried out by trained technicians at authorized service centers.
  • Replacement should be with a battery of the same type and parameters.
  • During the exchange, the ambient temperature must not exceed 40 degrees Celsius.
  • When installing the device, make sure that the leakage current does not exceed 3.5 mA.

The appliance is marked with the crossed-out waste bin symbol. This mark indicates that this device can not be disposed of with other household waste after its useful life.
ATTENTION! This device must not be disposed of with the trash! The product should be recycled through separate collection of prepared items. Proper handling of used electrical and electronic equipment helps prevent harmful effects on human health and the environment caused by the presence of hazardous components and the improper storage and handling of these equipment.

PRODUCT DESCRIPTION

The PowerProof Series Uninterruptible Power Supply (UPS) is designed to work with PCs. Its light weight and compact dimensions make it an ideal solution in the office or at home when the workplace is very limited. The UPS uses Line Interactive and AVR technologies to protect your equipment and enable operation over a wide range of input voltages. Key Features of PowerProof UPS Devices:

  • advanced controls guarantee high switching speed and operational safety;
  • AVR technology makes your devices up to 15% resistant to mains voltage fluctuations;
  • Green Power function for energy saving;
  • Cold start function;
  • automatic switching after restoration of the power supply;
  • compact size, light weight;
  • Overload protection.

BASIC FUNCTIONS OF THE GREEN CELL UPS

  1. Device
    After removing it from the packaging, make sure that no damage in transit is visible on the case of the device. If you notice any damage, do not connect the device and contact the seller.

  2. Charging
    The device leaves the factory with fully charged batteries. However, due to the self-discharge phenomenon, it may be necessary to charge it after receiving. Switch on the device and connect it to the mains.
    Leave the UPS for about 6 hours without load to fully charge it.

  3. Location
    The device should be used under controlled conditions to ensure adequate airflow. Be sure to avoid: large pollutants (dust, sand, etc.), Humidity, Corrosion sources high temperatures.
    At the same time, make sure the UPS is not near the computer monitors to avoid interference.

  4. Connection
    Connect the PowerProof power supply to a bipolar socket with ground pin. Then you can connect the computer and other devices to the output jacks. ATTENTION! Do not connect devices via extension cords or distributors.

  5. Commissioning
    To start the device, press the POWER button on the front of the case.
    To turn off the UPS, press the button again.

  6. cold start
    Press the POWER button to force the battery to work.

TROUBLESHOOTING

Signs Possible causes Suggested solution
Lack of lighting the LED diodes 1. Low battery 1. Charge the battery for

at least 8 hours
2. Defective battery| 2. Replace the battery by a new one of the same Type
3. POWER button not pressed| 3. Press the POWER button again
During the Mains operation off a permanent alarm tone. Very short hold time in battery mode.| 1. The device is overloaded.| 1. Check the device load and compare them to the technical data. Disconnect some devices.
2. The battery is discharged.| 2. Charge the battery for at least 8 hours
3. The battery is damaged.| 3. Replace the battery by a new one of the same Type
The device goes into the even though the mains voltage is available Battery operated.| Unplug the power plug.| Review and correct the connection of the power plug.

DESCRIPTION OF INDICATORS AND CONNECTIONS

Front panel:

  1. Switch
  2. LCD display

diagram

LCD display:

  1. Input voltage
  2. Output voltage
  3. Power supply (if the UPS is in AVR mode, the display flashes)
  4. Battery supply
  5. Battery level
  6. Warning of low battery & load level
  7. Overload warning (symbol flashes)
  8. Symbol for failure (lights up in the event of a short circuit, overload, overload)

diagram

Rear control panel

  1. Connection socket for Mains power supply
  2. 230V output socket
  3. USB and RJ11 sockets (optional)
  4. USB and RS232 sockets (optional)
  5. RJ45 socket (optional)
  6. RESET button to Break the connection

diagram

SPECIFICATION

model PowerProof
capacity VA 600VA
input voltage 110VAC/12/VAC
voltage range 81-145VAC / 162-290VAC
output voltage regulation (operating with a battery) +/-10%
frequency 50Hz / 60Hz
battery frequency control +/-1Hz
output wave- form modified sin wave
battery type of battery 12V/7.0 AH ×1

×2
charging time| 6-8 hours to 90% after full discharge
transfer time| standard| 2-6ms
sound alert| battery work mode| sound alert every 10 seconds
low battery| sound alert every 1 second
overload| sound alert every 0,5 second
error| continuous sound alert
protection| full protection| against overload, overcharging and deep discharge
dimensions| dimensions (mm)| 298 × 101 × 142| 353 × 149.3 × 162| 380 × 158 × 198
weight| net weight (kg)| 4.35| 4.7| 7.8| 10.1| 10.5
work environment| temperature| 00C-400C
noise level| below 40dB

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals