APPLICATION
The R4225 Fan Relays provide line voltage control of line voltage fan motors and auxiliary circuits in heating, cooling, and heating-cooling systems. The R8225 Fan Relays provide a low voltage (24 V) control of line voltage fan motors and auxiliary circuits in heating, cooling, and heating- cooling
systems.

  • One-half inch conduit spud fitting for mounting on a junction box
  • Color-coded lead wires for easier wiring.
  • Totally enclosed for long, trouble-free service life.

SPECIFICATIONS

IMPORTANT
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not match the listed specifications exactly. Also, this product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.
Models:
R4225A Fan Relay: SPDT switching; one normally open and one normally closed contact.
R4225B Fan Relay: SPST switching; normally open contacts.
R8225A Fan Relay: SPDT switching; one normally open and one normally closed contact.
R8225B Fan Relay: SPST switching; normally open contacts.
R8225C Fan Relay: DPST switching; one normally open and one normally closed contacts.
R8225D Fan Relay: DPST switching; one normally open main and one normally open auxiliary pole.
Electrical Ratings:

Contacts 120 Vac 240 Vac
Normally Open 3/4 hp. 1 hp.
14 AFL 8 AFL
84 ALR 48 ALR
16 A Res 8 A Res.
Normally Closed 3/4 hp. 3/4 hp.
14 AFL 7 AFL
84 ALR 42 ALR
10 ARes 7 A Res.
Auxiliary 1/10 hp. 1/8 hp.
3 AFL 2 AFL
18 ALR 12 ALR
3 A Res. 2 A Res.

AFL: Amperes Full Load
ALR: Locked Rotor
Res.: Resistive

resideo Fan Relays R4225A - fig 1

Coil Characteristics:

Coil
Voltage
| Inrush| Sealed| Pull-in Voltage| Max. Wattage
---|---|---|---|---
24 V| 11 VA| 6 VA| 18 V| 3.0
120V| 44 VA| 24 VA| 90V| 2.7
240 V| 88 VA| 48 VA| 180 V| 2.7

Contacts:
Silver cadmium oxide.
Maximum Ambient Operating Temperature:
115 F (46 C).
Case:
Molded plastic with steel mounting plate.
Mounting Means:
Mounts to standard 1/2 in. knockout or optional mounting bracket (Fig. 2) with 1/2 in. (12.7 mm) mounting spud.
Approval Bodies:
Underwriters Laboratories Inc. Listed: R4225A,B; R8225A-D; File No. E14480, Guide No. NLDX.
Canadian Standards Association: R4225A,B; R8225A-D; File No. 1620.

resideo Fan Relays R4225A - fig2

INSTALL ATION

When Installing this Product…

  1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
  2. Check ratings given in the instructions and on the product to make sure the product is suitable for your application.
  3. The installer must be a trained, experienced service technician.
  4. After installation is complete, check out product operation as provided in these instructions.

CAUTION
Disconnect power supply before beginning wiring to prevent electrical shock or equipment damage.
Location and Mounting
The R4225A, B/R8225A-D Fan Relays may be mounted in any convenient position. Choose a location where the maximum ambient operating temperature for the unit will not be exceeded. The relays have a 1/2 in. (12.7 mm) conduit spud for mounting a junction box.
To mount, remove the conduit spud nut and place the spud through the knockout in the junction box or hole in the flush mounting bracket (if used). Replace the nut and tighten. Drill a hole in the mounting surface and secure the relay in place using a screw through the tab of the mounting plate. See Fig. 1 for mounting dimensions.
Wiring
Disconnect power supply before beginning installation to prevent electrical shock or equipment damage.
All wiring must comply with local electrical codes and ordinances. Refer to manufacturer’s instructions whenever possible, or refer to Figs. 3-6 for typical hookups. Control wiring on the R4225 is routed through conduit spud.
Control circuit (coil) wires for all fan relays are routed through the side of the plastic relay case.

resideo Fan Relays R4225A - fig 3

PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
CONTROL CIRCUIT INCLUDES APPROPRIATE VOLTAGE POWER SUPPLY, THERMOSTAT, AND SAFETY DEVICES (IF USED). R4225 REQUIRES A LINE VOLTAGE CONTROL CIRCUIT. R8225 REQUIRES A 24 V CONTROL CIRCUIT.
PLENUM SWITCH CONNECTION WIRE MAY BE BLUE OR YELLOW ON SOME MODELS.

Fig. 3. R4225A/R8225A typical hookup with a two-speed fan.

resideo Fan Relays R4225A - fig4

PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
THE CONTROL CIRCUIT INCLUDES AN APPROPRIATE VOLTAGE POWER SUPPLY. THERMOSTAT AND SAFETY DEVICES OF USED). 84225 REQUIRES A LINE VOLTAGE CONTROL CIRCUIT. R5225 REQUIRES A 24 V CONTROL CIRCUIT.

Fig. 4. R4225B/R8225B typical hookup with a one-speed fan.

resideo Fan Relays R4225A - fig6

PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

Fig. 5. R8225C typical hookup with two-speed fan and combination fan and limit controller.

resideo Fan Relays R4225A - fig5

PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
THE CONTROL CIRCUIT INCLUDES A 24 V POWER SUPPLY, TRANSFORMER, AND SAFETY DEVICES (IF USED).
TO AUXILIARY CIRCUIT. MAY BE USED AS A LOCKOUT CONTACT TO PREVENT AN ELECTRIC STRIP HEATER FROM OPERATING UNLESS THE FAN MOTOR IS OPERATING. OR AS CONDENSING UNIT SWITCHING MEANS.

Fig. 6. R8225D typical hookup with one-speed fan and auxiliary load.

CHECKOUT

Operate the system according to the manufacturer’s for at least one cycle in both heating and cooling to make sure the system and the fan relay operate as intended.

 www.resideo.com
Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
60-2165—03 M.S. Rev. 08-20 | Printed in the United States
© 2020 Resideo Technologies, Inc. All rights reserved.
This product is manufactured by Resideo Technologies, Inc. and its affiliates.

resideo Fan Relays R4225A - bar

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals