Honeywell AQ25A44B Programmable Boiler Relay Control Panel Installation Guide
- June 7, 2024
- Honeywell
Table of Contents
Honeywell AQ25A44B Programmable Boiler Relay Control Panel
INSTALLATION JOB RECORD
Fill in the details of the equipment connected to the control module and the zoning module:
A Low voltage control module wiring
B Low voltage zone thermostats
C Low voltage zone valves with end switches
D Line voltage Boiler pump, DHW pump and AUX output
E Review and set DIP switch settings – once DIP switches for the zoning
module (AQ15740B) have been set, complete the “Installer Settings” diagram by
filling in the circles to indicate the DIP switch position set during
installation
File this with other installation records for equipment used on this installation.
A Boiler Controller Module
B Zoning Thermostats
E Zoning Module DIP Switch Settings
DIP
N umber
| D escrip tion
---|---
1| Zo ne A ddress
Slide the DIP switch to the right-hand (ON) position to indicate which group of zones this is:
The correct settings for each zone module are:
• First Zone (1-4) Module: 1 = ON position; 2, 3, and 4 = OFF position
• Second Zone (5-8) Module: 2 = ON position; 1, 3, and 4 = OFF position
• Third Zone (9-12) Module: 3 = ON position; 1, 2, and 4 = OFF position
• Fourth Zone (13-16) Module: 4 = ON position; 1, 2, and 3 = OFF position
For each zone group, there can be only one DIP switch in the right-hand (ON) position.
2
3
4
5| • If set to SYNC, zone synchronization is enabled.
• If set to NOT, zone synchronization is disabled.
6| • If zone valves are normally closed (N.C.), set the NC/NO DIP switch to the OFF position.
• If zone valves are normally open (N.O.), set the NC/NO DIP switch to the ON position.
7| • If set to Group (ON position), the AUX Pump contacts on the Control Module are switched when any of the zones on this Zoning Module are active.a
• If set to – (OFF position), the AUX Pump contacts are not affected by activity on these zones.
8| • If set to 2-Stg (ON position), then 2-stage operation is activated on thermostat inputs. The zoning module operates as two 2-stage zones or 3 zones (one 2-stage and two 1-stage).
• If set to 1-Stg (OFF position), then operates as four 1-stage zones.
The EQUIPMENT SETUP > AUXILIARY I/O > AUX PUMP menu option on the AQ25A must be set to “GROUP”
NOTE: When wiring zone valves with end switches, note the transformer’s VA:
If low voltage zone valves with end switches are used for zone control, make sure the selected zone valves do not draw more power (VA) than the 38 VA capacity of the AQ10X38 transformer supplied with the AQ25A Control Panel. This integral transformer has enough power to operate 4 motorized zone valves (such as Honeywell V8043E valves or 4 valves using lowamperage draw, heat motor actuators such as Honeywell MV100 actuators), plus power the electronics of the AQ25A’s Control Module and up to 16 AQ1000 thermostats.
If zone valves with high-amperage draw, heat motor actuators are used, such as Taco 500 series zone valves, additional 24 Vac transformer capacity will need to be wired to the Zoning Module to power the valves. See the AQ25A Series Programmable Boiler Control Panels – Product Data document (form 69- 2119) for recommended wiring of additional low voltage VA capacity to AQ2000 Series Zoning Modules.
CAUTION: Equipment Damage Hazard.
Can damage internal circuitry of Zoning Module.
The ES1 and ES2 terminals of the AQ15740B Zoning Module are powered terminals
and must only be connected to a set of dry contacts, such as a zone valve
motor’s end switch. If power is applied to these contacts (for example, by
running line voltage through the zone valves’ end switches to bring on a
circulator feeding those valves), the internal circuitry of the Zoning Module
will be damaged, in which case the warranty for this product will be voided.
EQUIPMENT SETTINGS
The Installer Menu is used to establish and modify the system’s equipment and
option settings. These include equipment settings for boiler operation, DHW
management, zoning, auxiliary input/output operation, and option settings such
as pump/valve exercise, and freeze protection. Use Table 1 to record the
equipment settings for this installation.
To record the equipment and option settings:
A Press the Home button to return to the Home Page display.
B Press and hold the OK button for 3 seconds until the message, INSTALLER
MODE – ARE YOU SURE?, displays.
C Select YES, then press and release the OK button to display the
Installer Menu.
D Select the Equipment Setup sub-menu.
E Record the configured settings in Table 1.
F Exit Installer mode by selecting the Installer Exit menu option.
Table 1. Installer Menu – Equipment Setup Sub-menu.
EQUIPMENT SETUP SUB-MENU
Sub-Menu and Option| Range| Factory Default| Equipment
Settings Used
BOILER SETTINGS
| HIGH LIMIT| 120°F to 225°F (49°C to 107°C)| 190°F (88°C)|
LOW LIMIT| 60°F to 180°F (15°C to 82°C)| 150°F|
BOILER DIFF| 2°F to 41°F (1°C to 23°C) / AUTO| AUTO|
W.W.S.D.| 35°F to 100°F (2°C to 38°C)| 70 °F (21°C)|
MIN. RETURN| – – / 80°F to 180°F (27°C to 82°C)| 140 °F (60°C)|
BOILER OPERATION
| CYCLES/HOUR| 2 to 6| 4|
FIRE DELAY| 0 seconds to 3 minutes (in 5 second increments)| 10 (seconds)|
PURGE TIME| OFF, 10 seconds to 30 minutes (in 10 second increments)| 30
(seconds)|
EXERCISE| YES / NO| YES|
FREEZE PROT| YES / NO| YES|
10V MOD. SELECT
| 10V MOD| 0-10V / 2-10V| 0-10V|
USAGE| NONE / BOILER| NONE|
DOMEST.HOT WATER
| DHW| ENABLE / DISABLE| ENABLE|
DHW PRIO| YES / NO| NO|
PRIO.OVER.| YES / NO| YES|
DHW DEVICE| PUMP / VALVE| PUMP|
DHW VLV.OP| 0 – 230 seconds
(in 5 second increments)
| 15
(seconds)
|
DHW PURGE| YES / NO| YES|
DHW SENSOR| YES / NO| NO|
DHW SETPOINT| 60°F to 160°F (16°C to 71°C)| 140°F (60°C)|
DHW DIFF| – –
5°F to 40°F (2.5°C to 22°C)
| 20°F (-7°C)|
DHW VACANCY| – – [41°F + DHW DIFF] to 160°F ([5°C + DHW DIFF] to 71°C)| 45°F
(7°C)|
ZONING
| HT DMND PRIO| YES / NO| NO|
PRIO.OVER| YES / NO| NO|
ZONING VALVES TIME TO OPEN| 5 – 230
(seconds)
| 15
(seconds)
|
HT DMND PRIO| YES / NO| NO|
EQUIPMENT SETUP SUB-MENU
Sub-Menu and Option| Range| Factory Default| Equipment
Settings Used
AUXILIARY I/O
| AUX.IN (optional)| SETBACK / VACANCY / EM. SHUT / NONE| SETBACK|
AUX.OUT (optional)| BOILER / SETBACK / ZONE OP. / ALARM /
AUX.IN / DHW IN / HEAT IN / HT DMND / COOL / NONE
| BOILER|
AUX.PUMP (optional)| BOILER / GROUP / OCC / BYPASS / FAN / NONE / AUX.IN / DHW
IN / HEAT IN / HT DMND| BOILER|
A/C SETTINGS
| CYCLES/HOUR| 2 / 3 / 4 / 5 / 6| 4|
MIN.OFF TIME| 2 to 10 (minutes)| 5M|
C.W.S.D.| 32°F to 100°F (0°C to 38°C)| 65°F (18°C)|
FAN MODE| AUTO / ON| AUTO|
A/C EQUIP CONFIG
| ZONE| A-1 to D-16| A-1|
A/C UNIT| NONE / 1| 1|
COOLING| ENABLE / DISABLE| ENABLE|
ENVIRACOM (not used at this time – reserved for future use)
| Modules ID:| n/a| n/a|
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark
© 2013 Honeywell International Inc.
69-2122—05 L.L. Rev. 10-13
Printed in United States
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>