Qubino GOAEZMNHBD1 Flush 2 Relays User Manual
- June 7, 2024
- QUBINO
Table of Contents
Qubino GOAEZMNHBD1 Flush 2 Relays User Manual
Important safety information
Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law. The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material. Use this equipment only for its intended purpose. Follow the disposal instructions. Do not dispose of electronic equipment or batteries in a fire or near open heat source.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart Home. This device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message (two- way communication) and every mains powered node can act as a repeater for other nodes (meshed network) in case the receiver is not in direct wireless range of the transmitter. This device and every other certified Z-Wave device can be used together with any other certified Z-Wave device regardless of brand and origin as long as both are suited for the same frequency range.
If a device supports secure communication it will communicate with other devices secure as long as this device provides the same or a higher level of security. Otherwise it will automatically turn into a lower level of security to maintain backward compatibility.
For more information about Z-Wave technology, devices, white papers etc. please refer to www.z-wave.info.
Product Description
Flush 2 relays module is used for switching on or off two electrical devices
(e.g. lights, fans, etc …). The module can be controlled either through Z-Wave
network or through the wall switches.
The module is designed to be mounted inside a “flush mounting box”, hidden
behind a traditional wall switch.
Module measures power consumption of two electrical devices and supports
connection of digital temperature sensor. It is designed to act as repeater in
order to improve range and stability of Z-wave network.
Prepare for Installation / Reset
Please read the user manual before installing the product
In order to include (add) a Z-Wave device to a network it must be in factory default state. Please make sure to reset the device into factory default. You can do this by performing an Exclusion operation as described below in the manual. Every Z-Wave controller is able to perform this operation however it is recommended to use the primary controller of the previous network to make sure the very device is excluded properly from this network
Reset to factory default
This device also allows to be reset without any involvement of a Z-Wave controller. This procedure should only be used when the primary controller is inoperable.
If the service button S is pressed for more than 6 seconds the module will be reset to the factory defoult state.
Safety Warning for Mains Powered Devices
ATTENTION: only authorized technicians under consideration of the
country-specific installation guidelines/norms may do works with mains power.
Prior to the assembly of the product, the voltage network has to be switched
off and ensured against re-switching.
Installation
- To prevent electrical shock and/or equipment damage, disconnect electrical power at the main fuse or circuit breaker before installation or any servicing.
- Make sure, that no voltage is present in the installation.
- Prevent the disconnecting device from being switched on accidentally.
- Connect the module according to electrical diagram.
- Locate the antenna far from metal elements (as far as possible).
- Do not shorten the antenna.
Notes for the diagram:
N +VDC
L -VDC
Q1 Output for electrical device no. 1
Q2 Output for electrical device no. 2
12 Input for switch to control electrical device no.2
11 Input for s.vitch to control electrical device no.1
TS Terminal for digital temperature sensor (only for Flush 2 Relays
module compatible digital temperature sensor. which must be ordered
separately).
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs to be added to an existing wireless network to communicate with
the
devices of this network. This process is called Inclusion.
Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is then performed doing a special manual action right on the device.
Inclusion
- Press service button S for more than 2 second or press push button I1 three times within 3s (3 times change switch state within 3 seconds).
Exclusion
- Press service button S for more than 6 second or press push button I1 five times within 3s ( 5 times change switch state within 3 seconds) in the first 60 seconds after the module is connected to the power supply.
Note: By this function all parameters of the module are set to default values and own ID is deleted. If service button S is pressed more than 2 and less than 6second module is excluded, but configuration parameters are not set to default values.
Auto-Inclusion
Beside the standard inclusion this devices supports the so called auto
inclusion. Right after powering up the device remains in inclusion state and
can be included by (any) gateway without further actions on the device itself.
The auto inclusion mode will time out after some time.
Product Usage
Electric motor
Conventional incandescent and halogen lights
LED bulb, compact fluorescent bulb (CFL), low voltage halogen bulbs with electronic transformer
Low voltage halogen bulbs with conventional transformer
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Don’t poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing.
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device controlling another device is called association. In order to control a
different device, the controlling device needs to maintain a list of devices
that will receive controlling commands. These lists are called association
groups and they are always related to certain events (e.g. button pressed,
sensor triggers, …). In case the event happens all devices stored in the
respective association group will receive the same wireless command wireless
command, typically a ‘Basic Set’ Command.
Association Groups:
Group Number
| Maximum Nodes|
Description
---|---|---
1
| 1|
Lifeline group (reserved for communication with the main controller).
2
| 16|
basic on/off (triggered at change of the output Q1 state and reflecting its state)
3
| 16|
switch binary report (triggered at change of the output Q1 state and reflecting its st
4
| 16|
power meter report (triggered at change of the output Q1 state)
5
| 16|
basic on/off (triggered at change of the output Q2 state and reflecting its state)
6
| 16|
switch binary report (triggered at change of the output Q2 state and reflecting its st
7
| 16|
power meter report (triggered at change of the output Q2 state)
8
| 16|
multilevel sensor report (triggered at change of temperature sensor)
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further enhanced features.
IMPORTANT: Controllers may only allow configuring signed values. In order
to set values in the range 128 … 255 the value sent in the application shall
be the desired value minus 256. For example: To set a parameter to 200 it may
be needed to set a value of 200 minus 256 = minus 56. In case of a two byte
value the same logic
applies: Values greater than 32768 may needed to be given as negative
values too.
Parameter 1: Input 1 switch type
Input 1 switch type
Size: 1 Byte, Default Value: 1
Setting|
Description
---|---
0
|
mono-stable switch type (push button)
1
|
bi-stable switch type
Parameter 2: Input 2 switch type
Input 2 switch type
Size: 1 Byte, Default Value: 1
Setting
|
Description
---|---
0
|
mono-stable switch type (push button)
1|
bi-stable switch type
Parameter 10: Activate / deactivate functions ALL ON/ALL OFF
Activate / deactivate functions ALL ON/ALL OFFFlush 2 relays module responds
to commands ALL ON / ALL OFF that may be sent by the main controller or by
other controller belonging to the system.
Size: 2 Byte, Default Value: 255
Setting
|
Description
---|---
0
|
ALL ON iCs not active ALL OFF is not active
1
|
ALL ON is not active ALL OFF active
2
|
ALL ON active ALL OFF is not active
255
|
ALL ON active, ALL OFF active
Parameter 11: Automatic turning off output Q1 after set time
When relay Q1 is ON it goes automatically OFF after time defined by this
parameter. Timer is reset to zero each time the module receive ON command
regardless
from where it comes (push button, associated module, controller,..).
Size: 2 Byte, Default Value: 0
Setting|
Description
---|---
0
|
Auto OFF disabled
1 – 32535
|
1second (0,01s) – 32535 seconds (325,35s) Auto OFF enabled with define time, step is 1s or 10ms acc parameter nr.15
Parameter 12: Automatic turning on output Q1 after set time
When relay Q1 is OFF it goes automatically ON after time defined by this
parameter. Timer is reset to zero each time the module receive OFF command
regardless from where it comes (push button, associated module,
controller,..).
Size: 2 Byte, Default Value: 0
Setting
|
Description
---|---
0
|
Auto ON disabled
1 – 32535
|
1second (0,01s) – 32536 seconds (325,35s) Auto ON enabled with define time, step is 1s or 10ms accor parameter nr.15
Parameter 13: Automatic turning off output Q2 after set time
When relay Q2 is ON it goes automatically OFF after time defined by this
parameter. Timer is reset to zero each time the module receive ON command
regardless from where it comes (push button, associated module,
controller,..).
Size: 2 Byte, Default Value: 0
Setting
|
Description
---|---
0
|
Auto OFF disabled
1 – 32535
|
1second (0,01s) – 32535 seconds (325,35s) Auto OFF enabled with define time, step is 1s or 10ms acc parameter nr.15
Parameter 14: Automatic turning on output Q2 after set time
When relay Q2 is OFF it goes automatically ON after time defined by this
parameter. Timer is reset to zero each time the module receive OFF command
regardless
from where it comes (push button, associated module, controller,..).
Size: 2 Byte, Default Value: 0
Setting
| Description
---|---
0|
Auto ON disabled
1 – 32535|
1second (0,01s) – 32536 seconds (325,35s) Auto ON enabled with define time, step is 1s or 10ms accor parameter nr.15
Parameter 15: Automatic turning off / on seconds or milliseconds
selection
Automatic turning off / on seconds or milliseconds selection Note that
parameter is valid for both outputs Q1, Q2 and is the same for turning off or
on.
Size: 1 Byte, Default Value: 0Automatic turning off / on seconds or
milliseconds selection.
Note that parameter is valid for both outputs Q1, Q2 and is the same for
turning off or on.
Size: 1 Byte, Default Value: 0
Setting
| Description
---|---
0
|
seconds selected
1|
milliseconds selected
Parameter 30: Saving the state of the relays Q1 and Q2 after a power
failure
Saving the state of the relays Q1 and Q2 after a power failure
Size: 1 Byte, Default Value: 0
Setting
|
Description
---|---
0
| Flush 2 relays module saves its state before power failure (it returns to
the last position saved before a failure)
1|
Flush 2 relays module does not save the state after a power failure, it returns to "off" position
Parameter 40: Power reporting in Watts on power change for Q1
Set value means percentage, set value from 0 – 100 = 0% – 100%.
Size: 1 Byte, Default Value
Setting
|
Description
---|---
0
|
Reporting Disabled
1 – 100
|
1% – 100% Reporting enabled. Power report is send (push) only when actual power in Watts in real time for more than set percentage comparing to previous actual power in Watts, step is 1%. NOTE: if power less than 1W, the report is not send (pushed), independent of percentage set.
Parameter 41: Power reporting in Watts on power change for Q2
Set value means percentage, set value from 0 – 100 = 0% – 100%
Size: 1 Byte, Default Value: 10
Setting
| Description
---|---
0|
Reporting Disabled
1 – 100
|
1% – 100% Reporting enabled. Power report is send (push) only when actual power in Watts in real time for more than set percentage comparing to previous actual power in Watts, step is 1%. NOTE: if power less than 1W, the report is not send (pushed), independent of percentage set.
Parameter 42: Power reporting in Watts by time interval for Q1
Set value means time interval (0 – 32535) in seconds, when power report is
send.
Size: 2 Byte, Default Value: 300
Setting
| Description
---|---
0|
Reporting Disabled
1 – 32535
|
= 1 second – 32535 seconds. Reporting enabled, Power report is send with time interval set by entered
Parameter 43: Power reporting in Watts by time interval for Q2
Set value means time interval (0 – 32535) in seconds, when power report is
send.
Size: 2 Byte, Default Value: 30
Setting
|
Description
---|---
0
| Reporting Disabled
1 – 32535|
= 1 second – 32535 seconds. Reporting enabled, Power report is send with time interval set by entered
Parameter 63: Output Q1 Switch selection
Set value means the type of the device that is connected to the Q1 output. The
device type can be normally open (NO) or normally close (NC).
Size: 1 Byte, Default Value: 0
Setting
|
Description
---|---
0
| When system is turned off the output is 0V (NC).
1|
When system is turned off the output is 230V (NO).
Parameter 64: Output Q2 Switch selection
Set value means the type of the device that is connected to the Q2 output. The
device type can be normally open (NO) or normally close (NC).
Size: 1 Byte, Default Value: 0
Setting
|
Description
---|---
0
| When system is turned off the output is 0V (NC).
1|
When system is turned off the output is 230V (NO).
Parameter 110: Temperature sensor offset settings
Set value is added or subtracted to actual measured value by sensor.
Size: 2 Byte, Default Value: 32536
Setting
| Description
---|---
1 – 100|
value from 0.1 deg.C to 10.0 deg.C is added to actual measured temperature.
1001 – 1100
| value from -0.1 deg.C to -10.0 deg.C is subtracted to actual measured
temperature.
32536|
offset is 0.0 deg.C
Parameter 120: Digital temperature sensor reporting
If digital temperature sensor is connected, module reports measured
temperature on temperature change defined by this parameter.
Size: 1 Byte, Default Value: 5
Setting
|
Description
---|---
0
| Reporting disabled
1 – 127|
0,1 deg.C – 12.7 deg.C. – step is 0,1 deg.C
Technical Data
Dimensions
| 42x37x16 mm
---|---
Weight|
28 gr
Hardware Platform
| ZM5202
EAN|
3830062070119
IP Class
| IP 20
Voltage|
230 V
Load
| 2x 4A
Device Type|
On/Off Power Switch
Network Operation
| Always On Slave
Z-Wave Version|
6.51.06
Certification ID
| ZC10-15100010
Z-Wave Product Id|
0x0159.0x0002.0x0051
Frequency
| Europe – 868,4 Mhz
Maximum transmission power|
5 mW
Supported Command Classes
- Switch All
- Association
- Association Group Information
- Basic
- Configuration
- Device Reset Locally
- Manufacturer Specific
- Meter
- Multi Channel Association
- Sensor Multilevel
- Powerlevel
- Switch Binary
- Version
- Zwaveplus Info
Controlled Command Classes
- Basic
Explanation of Z-Wave specific terms
- Controller — is a Z-Wave device with capabilities to manage the network. Controllers are typically Gateways, Remote Controls or battery operated wall controllers.
- Slave — is a Z-Wave device without capabilities to manage the network. Slaves can be sensors, actuators and even remote controls.
- Primary Controller — is the central organizer of the network. It must be a controller. There can be only one primary controller in a Z-Wave network.
- Inclusion — is the process of adding new Z-Wave devices into a network.
- Exclusion — is the process of removing Z-Wave devices from the network.
- Association — is a control relationship between a controlling device and a controlled device.
- Wakeup Notification — is a special wireless message issued by a Z-Wave device to announces that is able to communicate.
- Node Information Frame — is a special wireless message issued by a Z Wave device to announce its capabilities and functions.
Quickstart
This is a On/Off Power Switch for Europe. To run this device please connect it
to your mains power supply. Auto-inclusion procedure, first set main
controller into inclusion mode and then connect module to power supply.
NOTE: When connecting temperature sensor to module that has already been
included you have to exclude module first. Switch off power supply , connect
the sensor and re-include the module.
(c) 2020 Z-Wave Europe GmbH, Antonstr. 3, 09337 Hohenstein-Ernstthal, Germany, All rights reserved, www.zwave.eu. The template is maintained by Z-Wave Europe GmbH. The product content is maintained by Z-Wave Europe GmbH , upportteam,support@zwave.eu. Last update of the product data: 2017-12-27
http://manual.zwave.eu/backend/make.php?lang=en&sku=GOAEZMNHBD1
References
- manual.zwave.eu/backend/make.php?lang=en&sku=GOAEZMNHBD1
- Z-Wave Europe - The leading european distributor for Smart Home products.
- Z-Wave Europe - The leading european distributor for Smart Home products.