Overview
DP4/DP4CB power distributing modules conveniently convert a single AC or DC input into four (4) individually fused or PTC protected outputs.
Specifications
Input:
Up to 48VAC/VDC, 10A.
Outputs:
- DP4: Four (4) individually fused outputs (fuses are rated @ 3.5A; up to 5A fuses may be used).
- DP4CB: Four (4) PTC protected auto-resettable outputs (PTCs are rated @ 2.5A).
- Surge suppression.
Visual Indicators:
Power output LED indicator.
Additional Features:
- Power ON / OFF switch.
- Includes Snap Track ST3 and clips.
- DIN Rail mount ready.
Board Dimensions (L x W x H, approximate):
3.25” x 3” x 0.75” (82.55mm x 76.2mm x 19.5mm).
Installation Instructions
DP4/DP4CB should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
-
Mount DP4/DP4CB using included ST3 snap track and clips:
- Slide the board into the outermost slots on the ST3 (Fig. 2);
- Attach the clips to the back of ST3 using provided guides and slots;
- Mount DP4/DP4CB onto the DIN rail using the clips (Fig. 2).
-
Connect input power to the terminals marked [(AC) + DC – (AC)] (Fig. 1).
-
Measure polarity and output voltage before connecting devices. This helps avoid potential damage.
-
Set power switch [SW1] to the OFF position.
-
Connect devices to be powered to the terminal pairs 1 to 4 marked [1A and 1B] to [4A and 4B] (Fig. 1). Note: For DC voltage applications terminals marked A are Positive (+) and
terminals marked B are Negative (–). -
Set power switch [SW1] to the ON position. Fig. 1 – DP4/DP4CB
Altronix is not responsible for any typographical errors.