pulsar AWOP-960PP Distribution Junction Box Installation Guide
- June 8, 2024
- Pulsar
Table of Contents
pulsar AWOP-960PP Distribution Junction Box
Specifications
- Product Name : Distribution Junction Box 9x6mm2
- Model: AWOP-960PP v.1.0
- Edition: 5 from 05.02.2024
- Supersedes Edition : 4 from 21.05.2019
- Technical Assessment: National Technical Assessment CNBOP-PIB-KOT-2019/0109-3704
Description
The junction box for fire alarm systems is designed for connecting fire protection devices in cable installation systems with fire resistance according to the DIN 4102-12 standard, where the uninterruptible power supply or transmission of the signal in case of fire is required.
The junction box can be used for the power supply of fire protection equipment such as ventilators, smoke vents, fire alarm control panels, and emergency warning systems.
Elements of the Junction Box:
Component No. | Description |
---|---|
1 | Mounting holes for mounting to a surface. |
2 | Cable glands. |
3 | Protection connector PE. |
4 | Connection sockets. |
Technical Parameters:
Voltage: Not specified
Diameter of Installation Cable: 9x6mm2
Cross-section of the Cable: Not specified
Protection Class: Not specified
Enclosure Dimensions: Not specified
Temperature Range During Installation: Not specified
Installation:
The junction box should be mounted directly to a concrete base class min. B20 or natural stone using two steel pins of adequate fire resistance.
Cables should be mounted using handles at intervals of 600 mm with a maximum distance of 100 mm from the edge of the junction box.
Disposal:
Waste electrical and electronic equipment must not be disposed of with normal household waste. Follow the European Union WEEE Directive for proper disposal.
pulsar AWOP-960PP Distribution Junction Box
- Pulsar sp. j. Siedlec 150, 32-744 Lapczyca, Poland
- Tel. (+48) 14-610-19-45
- Email: sales@pulsar.pl
- Website: www.pulsar.pl
FAQ
- Q: Can the junction box be used for outdoor installations?
- A: The manual does not specify outdoor use. It is recommended to consult with the manufacturer for outdoor suitability.
Description
The junction box for fire alarm systems is designed for connecting fire protection devices in cable installation systems with fire resistance according to the DIN 4102-12 standard, where the uninterruptible power supply or transmission of the signal in case of fire is required.
The junction box is designed to guarantee the mechanical ability to keep the
cable routes capable of guaranteeing the uninterruptible power supply and
transmission of telecommunication signals in the fire zone.
The junction box can be used for the power supply of fire protection
equipment, such as ventilators and smoke vents, fire alarm control panels,
emergency warning systems, etc. The junction box enables to connection 9 wires
cable.
Elements of the junction box
Table 1. Elements of the junction box.
Table 2. Technical parameters.
Installation
The junction box for fire alarm systems should be mounted directly to the concrete base class min. B20 or natural stone. Other building materials of adequate strength and of fire resistance class of at least R90 are also approved for use.
The junction box for fire alarm systems should be mounted to the ceiling or wall using two steel pins of adequate fire resistance. The cables should be mounted using handles at intervals of 600 mm. The mounting distance between the cables (handles) and the edge of the junction box is maximally 100 mm.
Pay attention to the following boundary conditions:
a) The bushings and expansion bolts should be recessed at least 30 mm
into the concrete.
b) Tension on the pin should not exceed 500 N.
c) Alternatively, the pins with well-documented fire protection designs
can also be used.
d) It should be ensured that the functional class of the cable assemblies
containing junction boxes for fire alarm systems will not be adversely
affected by falling building elements.
Installation cables should be led through the appropriate bushings and then mounted with cable holders located inside the enclosure.
Distribution Junction Box 9x6mm2
Edition: 5 from 05.02.2024
Supersedes edition: 4 from 21.05.2019
National Technical Assessment
CNBOP-PIB-KOT-2019/0109-3704
3rd edition of 23 May 2019.
National assessment and verification of constancy of performance CNBOP-PIB 063-UWB-0174
www.pulsar.pl
www.zasilacze.pl
WE LABEL
Waste electrical and electronic equipment must not be disposed of with normal
household waste.
According to the European Union WEEE Directive, waste electrical and
electronic equipment should be disposed of separately from normal household
waste.