SimplyVAV STE-8001 Digital Wall Sensor User Guide

June 5, 2024
SimplyVAV

SimplyVAV STE-8001 Digital Wall Sensor

Use an STE-8001 or STE-8201 sensor to configure the SimplyVAV controller. If another type of sensor is installed as the room sensor, temporarily connect an STE-8001 as a service tool.

To get started

  1. Press the up and down buttons simultaneously to start configuration or balancing.
  2. Enter Password 2 if required. New installations do not have a password.
  3. Press the up and down buttons to move between functions or change values.
  4. Press the set point button to choose a selection or save a value

SimplyVAV-STE-8001-Digital-Wall-Sensor-1

  • CNFG The main configuration parameters for the VAV terminal unit.
  • COMM Set BACnet device instance, MAC address, and network baud.
  • BLNC Set airflow balancing parameters. Only the PRI (primary) menu is used for single duct
  • VAVSTPT Enter temperature setpoints and limits.
  • BOX Set up reheat, fan operation, and basic terminal unit functions.
  • FLOW Set airflow setpoints and limits.
  • ADVC Enter passwords and enable model specific features.
  • RSTR Restore to factory settings

For complete details on controller configuration, browse to the KMC Controls website and download a PDF file of the SimplyVAV Application and Installation Guide. Not used for all models Select English (factory setting) or Metric before setting other parameters.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

SimplyVAV User Manuals

Related Manuals