SimplyVAV STE-8001 Digital Wall Sensor User Guide

June 5, 2024
SimplyVAV

SimplyVAV STE-8001 Digital Wall Sensor

Use an STE-8001 or STE-8201 sensor to configure the SimplyVAV controller. If another type of sensor is installed as the room sensor, temporarily connect an STE-8001 as a service tool.

To get started

  1. Press the up and down buttons simultaneously to start configuration or balancing.
  2. Enter Password 2 if required. New installations do not have a password.
  3. Press the up and down buttons to move between functions or change values.
  4. Press the set point button to choose a selection or save a value

SimplyVAV-STE-8001-Digital-Wall-Sensor-1

  • CNFG The main configuration parameters for the VAV terminal unit.
  • COMM Set BACnet device instance, MAC address, and network baud.
  • BLNC Set airflow balancing parameters. Only the PRI (primary) menu is used for single duct
  • VAVSTPT Enter temperature setpoints and limits.
  • BOX Set up reheat, fan operation, and basic terminal unit functions.
  • FLOW Set airflow setpoints and limits.
  • ADVC Enter passwords and enable model specific features.
  • RSTR Restore to factory settings

For complete details on controller configuration, browse to the KMC Controls website and download a PDF file of the SimplyVAV Application and Installation Guide. Not used for all models Select English (factory setting) or Metric before setting other parameters.