EVALOGIK Z-Wave Mutil-relay ZW12 User Manual

June 6, 2024
EVALOGIK

EVALOGIK Z-Wave Mutil-relay ZW12 User Manual
EVALOGIK Z-Wave Mutil-relay ZW12

Introduction

This product can be operated in any Z-Wave network with other Z Wave Plus™ certified devices from other manufacturers. All non-battery operated nodes within the network will act as repeaters  regardless of vendor to increase reliability of the network. Each module is designed to act as a repeater, which will re-transmit a radio frequency (RF) signal by routing the signal around obstacles and radio dead spots to ensure that the signal is received at its intended destination. ZW12 is a security enabled Z-Wave Plus™ device. A security Enabled Z-Wave Plus™ Controller must be used in order to fully utilize the product. The Device Type of the ZW12 is on/off power switch. The Role Type of the ZW12 is Always On Slave Role Type.

Key Features

  • Remote ON/OFF control via the Z-Wave™ controller
  • Manual ON/OFF control with the front panel push button
  • Support Association Group and Auto Report switch status
  • Support firmware upgrades via Over-the-air (need Gateways support)
  • Support Scenes

Product Overview:

  • A. Push button
  • B. Status LED
  • C. POWER INPUT DC:5V
  • D. Connect the switch
  • E. Relay Output

Indicator Command Class

The indicator (blue color) will flashes according the indicator set command received from HUB.

Basic command class

The basic set command class is mapping to binary switch set.
Basic set will control both two endpoints’ relay to turn on or turn o

| Basic Command| Mapped Command
---|---|---
Basic

Set(value)

| Binary Switch

Set(value)

Basic

Report(Current

value,

duration)

| Binary Switch

Report(Current

value,

duration)

ZW12 Installation Wiring Diagram

Wiring Diagram

Key function description

  • Function 1: press and hold for more than 5s,change SW1 mode
  • Function 2: press 2x and hold for more than 5s,change SW2 mode
  • Function 3: quickly press 3x Button: ADD(inclusion) OR Remove( exclusion)
  • Function 4: press 5x change led parameter
  • Function 5: press 4x, then LED lit for 4s, within this time press 4x again – LED blinks 3 times then off to FACTORY RESET
    (Note: Please use this procedure only when the network primary controller is missing or otherwise inoperable.)

Adding Your Device To A Hub

The device support two methods of inclusion, When using a Z-Wave Plus™ certified controller choose Network Wide Inclusion or SmartStart,

Network Wide Inclusion To A Z-Wave™ Network.

  1. Refer to your primary controller instructions to process the inclusion / exclusion setup procedure.
  2. When prompted by your primary controller, click the Up or Down button three times in one second.

The device is compatible with SmartStart

SmartStart enabled products can be added into a Z-Wave network by scanning the Z-Wave™ QR Code found on the top of the outlet or the back of the box with a controller providing SmartStart inclusion. No further action is required and the SmartStart product will be added automatically within 10 minutes of being switched on and in the network vicinity.

QR CODE

the QR code are sticked to the side of the case,DSK is included in the QR code.
DSK
The DSK code can be found on the DSK label which is attached on the packaging box.

Command Class

[ROOT ENDPOINT]

Command Class Version Required Security Class
Z-Wave Plus Info V2 none
Switch Binary V2 highest granted
Indicator V3 highest granted
Configuration V4 highest granted
Multi Channel V4 highest granted
Association V3 highest granted
Multi Channel Association V4 highest granted
Association Group Information V3 highest granted
Transport Service V2 none
Version V3 highest granted
Manufacturer Specific V2 highest granted
Device Reset Locally V1 highest granted
Notification V8 highest granted
Powerlevel V1 highest granted
Security 2 VI none
Supervision V1 none
Fimware Updata Meta Data V5

7777

| highest granted
Sensor Binary| highest granted

ENDPOINT 1 & ENDPOINT 2

Command Class Version Required Security Class
Z-Wave Plus Info V2 none
Switch Binary V2 highest granted
Association V3 highest granted
Multi Channel Association V4 highest granted
Association Group Information V3 highest granted
Notification V8 highest granted
Security 2 V1 none
Supervision V1 none
Sensor Binary V2 highest granted
Notification Type and events

Notification type Notification events
NOTIFICATION TYPE WATER ALARM(0x05) NOTIFICATION EVENT WATER ALARM NO

EVENT(0x00)
NOTIFICATION EVENT WATER ALARM LEAK DETECTED UNKNOWN LOCATION(0x02)
NOTIFICATION TYPE HEAT ALARM(0x04)| NOTIFICATION EVENT HEAT ALARM NO EVENT(0x00)
NOTIFICATION EVENT HEAT ALARM OVERHEAT DETECTED UNKNOWN LOCATION(0x02)
NOTIFICATION TYPE ACCESS CONTROL(0x06)| NOTIFICATION EVENT WINDOWS DOOR IS OPEN(0x16)
NOTIFICATION EVENT WINDOWS DOOR IS CLOSE(0x17)
NOTIFICATION TYPE CO ALARM(0x02)| NOTIFICATION EVENT CO ALARM NO EVENT(0x00)
NOTIFICATION EVENT CO ALARM SMODE DETECTED UNKNOWN LOCATION(0x02)
NOTIFICATION TYPE CO2 ALARM(0x03)| NOTIFICATION EVENT CO2 ALARM NO EVENT(0x00)
NOTIFICATION EVENT CO2 ALARM_SMODE_DETECTED_UNKNOWN_LOCATION(0x02)
NOTIFICATION TYPE SMOKE ALARM(0x01)| NOTIFICATION EVENT SMOKE ALARM_NO_EVENT(0x00)
NOTIFICATION_EVENT_SMOKE_ALARM_SMODE_DETECTED_UNKNOWN_LOCATION(0x02)

NOTES

  1. For the root endpoint, the Notification and Sensor Binary only supported when the parameter 2 is set to 4~9 or the parameter 3 is set to 4~9. (When one of input or both two inputs are used to sensor alarm.
  2. For the endpoint 1, the Notification and Sensor Binary only supported when the parameter 2 is set to 4~9. (When input (S1 and C) is used to sensor alarm.
  3. For the endpoint 1, the Notification and Sensor Binary only supported when the parameter 3 is set to 4~9. (When input (S2 and C) is used to sensor alarm.

SPECIFICATIONS

  • Model:ZW12
  • Power: 120 VAC, 60 Hz.
  • Signal (Frequency): 908.42 MHZ.
  • Maximum load for outlet 500W Resistive
  • Maximum load for the Z-Wave™ controlled outlet:
  • Range: Up to 100 feet line of sight between the Wireless control and the closest Z-Wave™ receiver module.
  • Operating Temperature Range: 32-104° F (0-40° C)

Specifications subject to change without notice due to continuing product improvement.

WARNING

RISK OF FIRE
RISK OF ELECTRICAL SHOCK
RISK OF BURNS
CONTROLLING APPLIANCES:
EXERCISE EXTREME CAUTION WHEN USING Z-Wave™ DEVICES TO CONTROL
APPLIANCES. OPERATION OF THE Z-Wave™ DEVICE MAY BE IN A DIFFERENT ROOM THAN THE CONTROLLED APPLIANCE, ALSO ANUNINTENTIONAL ACTIVATION MAY OCCUR IF THE WRONG BUTTON ON THE REMOTE IS PRESSED. Z-Wave™ DEVICES MAY AUTOMATICALLY BE POWERED ON DUE TO TIMED EVENT PROGRAMMING. DEPENDING UPON THE APPLIANCE, THESE UNATTENDED OR UNINTENTIONAL OPERATIONS COULD POSSIBLY RESULT IN A HAZARDOUS CONDITION. FOR THESE due to continuing product improvement REASONS, WE RECOMMEND DO NOT RETURN THIS PRODUCT TO THE STORE.
THE FOLLOWING:

  • DO NOT USE Z-Wave™ DEVICES TO CONTROL ELECTRIC HEATERS OR ANY OTHER APPLIANCES WHICH MAY PRESENT
  • A HAZARDOUS CONDITION DUE TO UNATTENDED OR
    UNINTENTIONAL OR AUTOMATIC POWER ON CONTROL.

Configuration Parameters

You may use the below configuration parameters to change settings of the corresponding functionality.

Restore state after power failure

Paramter No: 1(0x01)

  • Size:1 Byte (default=1)
  • Value: 00 All relays automatically turn OFF once power is restored
  • Value: 01 All relays remember the status prior to power outage and turns back to it
  • Value: 02 All relays turned on after power failure
  • Value: 03 R1 recovered, R2 ON
  • Value: 04 R2 recovered, R1 – ON

Select switch one’s type Paramter No: 2(0x02)

  • Size:1 Byte (default=2)
  • Value: 00 momentary switch
  • \Value: 01 toggle switch (contact closed -ON, contact opened – OFF)
  • Value: 02 toggle switch (device changes status when switch changes status)
  • Value: 03 garage door mode(toggle switch type for external switch (like in value 1) + built-in 2 second auto-off timer for Z-Wave control (so if user turns the relay on from the Z-Wave hub, it will automatically turn off after 2 seconds)
  • Value: 04 water alarm
  • Value: 05 heat alarm
  • Value: 06 Smoke alarm
  • Value: 07 Door alarm
  • Value: 08 CO alarm
  • Value: 09 CO2 alarm

After changing the values of the parameter, first exclude the device (without setting the parameters to their default values), wait at least 5 seconds and then re-include the device! While par=4 to 9.

Select switch two’s type Paramter No: 3(0x03)

  • Size:1 Byte (default=2)
  • Value: 00 momentary switch
  • Value: 01 toggle switch (contact closed -ON, contact opened – OFF)
  • Value: 02 toggle switch (device changes status when switch changes status)
  • \Value: 03 garage door mode(toggle switch type for external switch (like in value 1) + built-in 2 second auto-off timer for Z-Wave control (so if user turns the relay on from the Z-Wave hub, it will automatically turn off after 2 seconds)
  • Value: 04 water alarm
  • Value: 05 heat alarm
  • Value: 06 Smoke alarm
  • Value: 07 Door alarm
  • Value: 08 CO alarm
  • Value: 09 CO2 alarm

After changing the values of the parameter, first exclude the device (without setting the parameters to their default values), wait at least 5 seconds and then re-include the device! While par=4 to 9.

LED indicator

Paramter No: 5(0x05)

  • Size:1 Byte (default=0)
  • Value: 00 led OFF when output ON,led ON when output OFF
  • Value: 01 led ON when output ON,led OFF when output OFF
  • Value: 02 led always OFF
  • Value: 03 led always ON

EP1 Auto Turn-off Timer(only switch-1 type < 4

Paramter No: 6(0x06)

  • Size:4 Byte (default=0)
  • Value: 00 timer disabled
  • Value: 1-65535 This Timer Turn-off

EP1 Auto Turn-on Timer(only switch-1 type < 4) 

Paramter No: 7(0x07)

  • Size:4 Byte (default=0)
  • Value: 00 timer disabled
  • Value: 1-65535 This Timer Turn-on

EP2 Auto Turn-off Timer(only switch-2 type < 4)

Paramter No: 8(0x08)

  • Size:4 Byte (default=0)
  • Value: 00 timer disabled
  • Value: 1-65535 This Timer Turn-off

EP2 Auto Turn-on Timer(only switch-2 type < 4)

Paramter No: 9(0x09)

  • Size:4 Byte (default=0)
  • Value: 00 timer disabled
  • Value: 1-65535 This Timer Turn-on

Input 1 trigerring(Input1 trigger the relay 1)

Paramter No: 10(0x0A)

  • Size:1 Byte (default=1)
  • Value: 00 trigger disable (only notification to hub according to set par 2)
  • Value: 01 trigger unable (default); trigger the relay and hub notification

Input 2 trigerring(Input2 trigger the relay 2)

Paramter No: 11(0x0B) Size:1 Byte (default=1)

  • Value: 00 trigger disable (only notification to hub according to set par 2)
  • Value: 01 trigger unable (default); trigger the relay and hub notification

EP1 Manual Control

Paramter No: 12(0x0C ) Size:1 Byte (default=1)

  • Value: 00 manual control disabled (no reports to the hub)
  • Value: 01 manual control enabled
  • Value: 02 manual control disabled (sends on/off reports to the hub)

EP2 Manual Control

Paramter No: 13(0x0D)

  • Size:1 Byte (default=1)
  • Value: 00 manual control disabled (no reports to the hub)
  • Value: 01 manual control enabled
  • Value: 02 manual control disabled (sends on/off reports to the hub)

EP1 Auto Turn-Off Timer Unit Paramter No: 15(0x0F)

  • Size:1 Byte (default=0)
  • Value: 00 minutes
  • Value: 01 seconds
  • Value: 02 hours

EP1 Auto Turn-ON Timer Unit Paramter No: 16(0x10)

  • Size:1 Byte (default=0)
  • Value: 00 minutes
  • Value: 01 seconds
  • Value: 02 hours

EP2 Auto Turn-Off Timer Unit Paramter No: 17(0x11)

  • Size:1 Byte (default=0)
  • Value: 00 minutes
  • Value: 01 seconds
  • Value: 02 hours

EP2 Auto Turn-ON Timer Unit Paramter No: 18(0x12)

  • Size:1 Byte (default=0)
  • Value: 00 minutes
  • Value: 01 seconds
  • Value: 02 hours

Sw1,Sw2 setting Paramter No: 24(0x18)

  • Size:1 Byte (default=0)
  • Value: 00 Normal
  • Value: 01 Union (only switch type1 < 4 && switch type2 < 4) IF both switches OFF – only one of them may be turned ON.
    • turning sw1 ON : delayed 0.5 s, sw2 and R2 turned off first (immediately)
    • turning sw2 ON – delayed 0.5s , sw1and R1 turned off first ( immediately ) The situation for DC motor control(SW1 control
    • Right, SW2 control-left.
    • Main switch can turn ON and OFF only sw1

WARRANTY

Evalogik Products warrants this product to be free from manufacturing defects for a period of two years from the original date of consumer purchase. This warranty is limited to the repair or replacement of this product only and does not extend to consequential or incidental damage to other products that may be used with this product.

This warranty is in lieu of all other warranties, expressed or implied. Some states do not allow limitations on how long an implied warranty lasts or permit the exclusion or limitation of incidental or consequential damage, so the above limitations may not apply to you.

This warranty gives you specific rights, and you may also have other rights which vary from state to state. if the unit should prove defective within the warranty period.

Federal Communications Commission (FCC) Statement

FCC Caution: Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV technician for help. This equipment should be installed and operated with minimum distance 20cm between the radiator and your body. Z-Wave Multi- relay IC Caution:

This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device

Support for Association Groups

ZW12 supports 3 association groups. Group 1 supports 1 node ID,Group 2 and Group 3 Supports maximum of 5 node ID’s

Root Device Endpoint 1 Endpoint2
Group 1:Lifeline Group 1:Lifeline Group 1:Lifeline
Group 2:Basic set From Endpointl Group 2:Basic set command
Group 3:Basic set From Endpoint2 Group 2:Basic set command

Association group_1: Z-Wave™ Plus Lifeline

Association group_1 is default to associate with the primary controller (Gateway/Hub/Controller) for ZW12 Status change report,

  1.  ZW12 will trigger AUTO report function if the Switch status had been changed.  (ex. Switch Binary Report/Indicator Report/ Notification Report/ Device Reset Locally Notification/Sensor Binary Report)

Association group_2:basic set command on/off controlt

When the output of the ZW12 is changed, On (0xFF) or Off (0x00). The ZW12 will automatically send out a related basic set command. On (0xFF) or Off (0x00) to its associated group.

Association group_3:basic set command on/off controlt

When the output of the ZW12 is changed, On (0xFF) or Off (0x00). The ZW12 will automatically send out a related basic set command. On (0xFF) or Off (0x00) to its associated group.

Restoring Factory Defaults

ZW12 is removed from the network and will be restored to the factory setting
All Configuration Parameters values and Association information will be restored to factory default settings and excluded from the network.

Manual Reset:press 4x, then LED lit for 4s, within this time press 4x again – LED blinks 3 times then off to FACTORY RESET

Remark : All the setting and data will be permanently deleted.

Please use this procedure only when the network primary controller is missing or otherwise inoperable.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

EVALOGIK User Manuals

Related Manuals