OXBOX GC2 Series LP Gas Conversion and High Altitude Kit Instruction Manual
- October 27, 2023
- Oxbox
Table of Contents
- BEFORE THE CONVERSION
- 55 Drill Size Burner Orifice Kit (contains (7) 661055)| 1
- 56 Drill Size Burner Orifice Kit (contains (7) 661056)| 1
- 57 Drill Size Burner Orifice Kit (contains (7) 661057)| 1
- 59 Drill Size Burner Orifice Kit (contains (3) 661059)| 1
- 60 Drill Size Burner Orifice Kit (contains (3) 661060)| 1
- 61 Drill Size Burner Orifice Kit (contains (3) 661061)| 1
- CONVERTING TO LP/PROPANE GAS AT ALTITUDES BETWEEN ZERO & 10,000 FT.
- GAS PRESSURE ADJUSTMENT
- COMPLETING THE CONVERSION
- REPLACING THE PRESSURE SWITCH(ES)
- Documents / Resources
LP GAS CONVERSION & HIGH ALTITUDE KIT FOR INSTALLATIONS IN THE UNITED
STATES
INSTALLATION INSTRUCTIONS
For G7 / GC2 Series Furnaces & Appliances Using Honeywell Gas Valves
BEFORE THE CONVERSION
IMPORTANT: Please read all instructions before converting the furnace.
Pay attention to all safety warnings and any other special notes highlighted
in the manual. Safety markings are used frequently throughout this manual to
designate a degree or level of seriousness and should not be ignored. WARNING
indicates a potentially hazardous situation that if not avoided, could result
in personal injury or death.
This conversion kit is only to be used to convert natural gas furnaces to
LP/Propane gas and/or for high altitude applications in the United States. For
installations in Canada, the Canadian conversion kit must be used.
Table 1 is a detailed listing of the components in this conversion kit. Please
check the contents of the conversion kit with that of the parts listing, and
familiarize yourself with each component.
Use caution when servicing or removing components from the appliance. Personal
injury can occur from sharp metal edges present in all sheet metal constructed
equipment.
To avoid nuisance tripping at altitudes between 7,500 to 10,000 feet, a
pressure switch conversion is required. See pressure switch settings in Table
3 (page 6) or Table 4 (page 7) for altitudes between 7,500 and 10,000 feet (in
the US only).
NOTE: If furnace was produced before January 2010, the NOX baffles must
be removed from the furnace before conversion.
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury or
property damage.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance.
- Do not touch any electrical switch; do not use any phone in your building.
- Leave the building immediately.
- Immediately call your gas supplier from a neighbors phone. Follow the gas suppliers instructions.
- If you cannot reach your gas supplier, call the fire department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
DO NOT DESTROY THIS MANUAL. READ ALL INSTRUCTIONS IN THIS MANUAL AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
DESCRIPTION | QTY |
---|
Honeywell Conversion Kit 396221
(to convert VR8205S2890 or VR8215S1289)| 1
Honeywell Conversion Kit 396021 (to convert VR820502381)| 1
Honeywell Conversion Kit 50033841 (to convert VR920501127)| 1
55 Drill Size Burner Orifice Kit (contains (7) 661055)| 1
56 Drill Size Burner Orifice Kit (contains (7) 661056)| 1
57 Drill Size Burner Orifice Kit (contains (7) 661057)| 1
59 Drill Size Burner Orifice Kit (contains (3) 661059)| 1
60 Drill Size Burner Orifice Kit (contains (3) 661060)| 1
61 Drill Size Burner Orifice Kit (contains (3) 661061)| 1
Conversion Warning Label| 1
Conversion Information Label| 1
Installation Instructions| 1
Table 1. LP Gas Conversion Kit
WARNING:
All gas piping must conform with local building codes, or in the absence of
local codes, with the most recent edition of the National Fuel Gas Code
ANSI Z223.1. DO NOT attempt to modify, or tap into existing gas lines
yourself. Fire or explosion may result causing property damage, personal
injury or loss of life. Failure to follow the safety warnings exactly could
result in serious injury, death or property damage.
WARNING: All electrical wiring must comply with the latest edition of the
National Electrical Code ANSI/NFPA 70. Failure to follow these instructions
could result in possible damage to equipment, serious personal injury, or
death.
The installer performing this work assumes all responsibility for this conversion. These instructions are primarily intended to assist qualified individuals experienced in the proper installation of these components. Some local codes require licensed installation/service personnel for this type of equipment. Safety should always be the deciding factor when installing this product and using common sense plays an important role as well. Improper installation of the components or failure to follow safety warnings could result in serious injury, death, or property damage. After completing the installation, return these instructions to the Homeowner’s Package for owner- user’s future reference.
CONVERTING TO LP/PROPANE GAS AT ALTITUDES BETWEEN ZERO & 10,000 FT.
Converting single stage valves to LP/Propane requires the replacement of the burner orifices and the spring found under the cap screw in the pressure regulator. Converting 2 – stage valves to LP/Propane requires the replacement of the burner orifices and the stem/spring assembly in the pressure regulator. Table 2 (page 3), provides the manifold pressure for altitudes above 2,000 feet.
WARNING:
Shut off the gas supply at the manual gas shutoff valve, before disconnecting
the electrical power. A fire or explosion may result causing property damage,
personal injury or loss of life. Failure to follow the safety warnings exactly
could result in serious injury, death or property damage.
WARNING:
To avoid electric shock, personal injury, or death, turn off the electric
power at the disconnect or the main service panel before making any electrical
connections.
WARNING:
The reduction of input rating necessary for high altitude installation may
only be accomplished with factory supplied orifices. Do not attempt to drill
out orifices in the field. Improperly drilled orifices may cause fire,
explosion, carbon monoxide poisoning, personal injury or death.
Before You Convert the Gas Valve
- Turn the thermostat OFF or to its lowest temperature setting.
- Verify the gas supply is shut OFF.
- Verify the electrical power to the appliance is turned OFF.
Removing The Burner Orifices
-
Set the thermostat to the OFF position, or its lowest temperature setting.
-
Shut OFF the gas supply at the manual shutoff valve located outside of the appliance.
-
Turn off all electrical power to the appliance.
-
Remove the door from the burner compartment.
-
Move the gas valve ON/OFF switch to the OFF position as shown in Figure 1. For VR8205Q2381 gas valves, turn the knob to the OFF position.
-
Remove the wires from the terminals of the gas valve.
-
Remove the supply gas piping from the gas valve inlet.
-
Carefully remove four screws securing the gas manifold assembly to the burner assembly.
-
Set the screws aside and remove the gas manifold assembly from the appliance.
-
Carefully remove the burner orifices from the gas manifold assembly.
-
Read the rating plate affixed to the appliance to determine its rated input (Btu/hr) and the size of the factory installed orifices.
Figure 1. Typical Burner & Manifold Assembly
IMPORTANT NOTE:
Before installing an orifice, check the side or face of the orifice for the drill number to ensure that it is the appropriate size. -
Install the appropriate LP/Propane gas burner orifices into the gas manifold assembly.
NOTE: To prevent cross threading, hand tighten the orifices into the gas manifold assembly until snug, then tighten with a wrench.
WARNING:
Do not use Teflon tape or pipe joint compound on the orifice threads. The hole in the orifice may become blocked and cause fire, explosion, property damage, carbon monoxide poisoning, personal injury, or death. -
Reinstall the gas manifold assembly to the burner assembly with the 4 screws, that were removed earlier. NOTE: It is important that the center of the orifices are aligned with the enter of the burners. It is recommended to fire the unit and check alignment of the flame after converting to LP.
-
Reconnect the gas piping to the gas valve inlet.
-
Reconnect the wires to the gas valve terminals.
Single Stage Honeywell Valves
Models: VR8205S2890 or VR8215S1289
IMPORTANT NOTE:
When converting to LP/Propane gas from natural gas, the black spring in the
gas valve must be replaced by the red spring in the kit.
- Remove the cap screw from the gas valve as shown in Figure 2.
- Remove and discard the plastic pressure regulator adjustment screw from the gas valve. See Figure 3.
- Remove the black colored spring from the gas valve.
- Install the red spring from the conversion kit.
- Install the new adjusting screw from the kit.
- Check and adjust the regulator setting. See Gas Pressure Adjustment Section (page 5).
- Reinstall the cap screw.
- Affix the label from the conversion kit to the gas valve.
Table 2. Liquid Propane Conversion Chart
2 – Stage Honeywell Valves
Model VR8205Q2381
IMPORTANT NOTE:
When converting to LP/Propane gas from natural gas, the white stem/spring
assembly in the gas valve must be replaced by the black stem/spring assembly
in the kit.
- Remove two screws securing the pressure regulator cover assembly to the gas valve. Do not discard the screws. See Figure 4.
- Remove the pressure regulator cover assembly from the gas valve.
- Remove and discard the existing white spring / stem assembly from the gas valve.
- Install the black replacement spring / stem assembly from the conversion kit.
- Reinstall the pressure regulator cover assembly onto the gas valve.
- Install the two screws (from step 1)and tighten.
- Affix the label from the conversion kit to the gas valve
Figure 4. Spring / Stem Assembly Removal
GAS PRESSURE ADJUSTMENT
Measuring the Supply Gas Pressure
- Turn OFF the gas supply at the manual valve located on the outside of the unit.
- Using a 3/16” Allen wrench, remove the plug from the inlet pressure tap (INLET side of gas valve). See Figure 6.
- Install an 1/8” NPT pipe thread fitting, that is compatible with a Manometer or similar pressure gauge.
- Connect the Manometer or pressure gauge to the Inlet Pressure Tap.
- Turn ON the main gas supply at the manual valve.
- Check and adjust the incoming gas line pressure to 11.0-14.0 inches Water Column for LP/Propane gas.
- Turn OFF the gas supply at the manual valve.
- Disconnect the Manometer or pressure gauge.
- Remove the NPT fitting and reinstall the INLET pressure tap plug. Hand tighten the plug first to prevent cross-threading. Tighten with 3/16 Allen wrench.
Lighting & Adjustment of the Appliance
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious
injury or property damage.
Never test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of leaks to
check all connections. A fire or explosion may result causing property
damage, personal injury or loss of life.
- Turn ON the manual gas valve, located on the outside of the unit to the ON position.
- Check all gas connections for leaks with a soap and water solution. If the solution bubbles there is a gas leak which must be corrected.
- Turn on the electrical power to the appliance.
- Place the gas valve ON/OFF switch/knob to the ON position. See Figure 6.
- Set the thermostat above room temperature to begin the heating cycle of the furnace.
- Check that the furnace ignites and operates properly. Refer to the installation instructions provided with the unit for the normal operating sequence.
- After ignition, visually inspect the burner assembly to ensure that the flame is drawn directly into the center of the heat exchanger tube. In a properly adjusted burner assembly, the flame color should be blue with some light yellow streaks near the outer portions of the flame.
NOTE: The ignitor may not ignite the gas until all air is bled from the gas line. If the ignition control locks out, turn the thermostat to its lowest setting and wait one minute then turn the thermostat above room temperature and the ignitor will try again to ignite the main burners. This process may have to be repeated several times before the burners will ignite. After the burners are lit, check all gas connections for leaks again with the soap and water solution.
Measuring the Manifold Pressure
The manifold pressure must be measured by installing a pressure gauge
(Manometer, Magnehelic Meter, etc.) to the outlet end of the gas valve as
follows:
- Turn off all electrical power to the appliance.
- Shut OFF the gas supply at the manual shutoff valve located outside of the appliance.
- Using a 3/16” Allen wrench, remove the manifold pressure tap plug located on the outlet side of the gas valve. See Figure 6 (page 5).
- Install an 1/8” NPT pipe thread fitting, that is compatible with a Manometer or similar pressure gauge.
- Connect the Manometer or pressure gauge to the manifold pressure tap.
- Set the room thermostat above room temperature to start the furnace.
- Allow the furnace to operate for 3 minutes and then check the manifold pressure. Compare the measured value with the value shown in Table 2 (page 3). If the manifold pressure is not set to the appropriate pressure, then it must be adjusted.
Adjusting the Manifold Pressure
NOTE: Adjustments do not need to be made to LOW fire for model
VR8205Q2381. Refer to Table 2 for manifold pressures.
-
Single stage gas valve: Remove the cap screw from the top of the gas valve regulator. See Figure 2 (page 4) for VR8205S2890 or VR8215S1289 models. 2-stage gas valve: For VR8205Q2381 models, remove the plastic cap covering the adjustment screws (Figure 4 page 4).
-
Using a screwdriver or Allen wrench (where appropriate), slowly. turn the adjustment screw till the appropriate manifold pressure listed in Table 2 is achieved. See Figure 2 for VR8205S2890 or VR8215S1289 models. See Figure 4 for VR8205Q2381 models or Figure 5 for VR9205Q1127 models.
NOTE: Turning the screw clockwise increases the pressure, turning the screw counter-clockwise decreases the pressure. To prevent the screw from backing all the way out from the valve, turn the screw slowly. -
Replace and tighten the cap screw or the plastic cap over the adjustment screw.
Model VR8205Q2381
Figure 5. Inlet & Manifold Pressure Tap Locations
Removing the Manometer/Pressure Gauge
After the manifold pressure is properly adjusted, the Manometer or pressure
gauge must be removed from the gas valve.
- Turn the thermostat to its lowest setting.
- Turn OFF the main gas supply to the unit at the manual shutoff valve, which is located outside of the unit.
- Turn OFF all of the electrical power supplies to the unit.
- Remove the pressure gauge adapter from the gas valve and replace it with the 1/8” NPT manifold pressure plug that had been removed earlier. NOTE: Make sure the plug is tight and not cross-threaded.
- Turn ON the electrical power to the unit.
- Turn ON the main gas supply to the unit at the manual shut-off valve.
COMPLETING THE CONVERSION
WARNING:
Do not alter or remove the original rating plate from the furnace.
-
Attach the following labels:
• The conversion warning label should be affixed to the outside of the unit door.
• The conversion information label should be affixed near the rating plate on the inside of the control area.
• The gas valve conversion label should be affixed on the gas valve.
NOTE: Each label should be prominently visible after installation. -
Reinstall the appliance door.
-
Run the appliance through 3 complete cycles to assure proper operation.
REPLACING THE PRESSURE SWITCH(ES)
- Turn off all electrical power to the appliance.
- Remove the door from the burner compartment.
- Label and remove the wires from the terminals of the pressure switch(es).
- Label and remove tubing from pressure switch(es)
- Remove the tubing from the pressure switch(es).
- Remove the screws mounting the pressure switch(es).
- Install the appropriate pressure switch in the same location using the supplied screws.
- Reconnect the tubing to the proper pressure switch(es).
- Reconnect the wires to the proper pressure switch terminals.
SINGLE STAGE PRESSURE SWITCH SETTING FOR ALTITUDES BETWEEN 7,500 AND 10,000
FURNACE MODELS| INDUCER SETTING (IN. W.C.)| INDUCER PN|
COLLECTOR SETTING
(IN. W.C.)| COLLECTOR PN
---|---|---|---|---
G7SA 045C-23A1| 0.6| 632499R| NA| NA
G7SA 045C-23A2| 0.6| 632499R| NA| NA
G7SA 054C-23A1| 0.6| 632499R| NA| NA
G7SA 054C-23A2| 0.6| 632499R| NA| NA
G7SA 072C-35C1| 0.6| 632499R| NA| NA
G7SA 090C-24B1| 0.6| 632499R| NA| NA
G7SA 090C-35C1| 0.65| 1021833R| NA| NA
G7SA 090C-35C2| 0.65| 1021833R| NA| NA
G7SA 108C-35C1| 0.65| 1021833R| NA| NA
G7SA 126C-45D1| 0.65| 1021833R| NA| NA
G7SC 038D-23A1| 0.5| 632492R| 1.4| 1021834R
G7SC 038D-23A2| 0.5| 632492R| 1.4| 1021834R
G7SC 054D-24B1| 0.7| 632624R| 1.4| 1021834R
G7SC 072D-24B1| 0.7| 632624R| 1.1| 1021835R
G7SC 072D-35C1| 0.5| 632492R| 1.4| 1021834R
G7SC 072D-35C2| 0.5| 632492R| 1.4| 1021834R
G7SC 090D-35C1| 0.5| 632492R| 1.1| 1021835R
G7SC 108D-45D1| 0.5| 632492R| 1.4| 1021834R
G7SC 120D-45D1| 0.5| 632492R| 1.4| 1021834R
G7SD 038D-23EB1| 1| 1018532R| 0.2| 1021836R
G7SD 038D-24B1| 1| 1018532R| 0.2| 1021836R
G7SD 054D-23EB1| 0.8| 632495R| 0.5| 632492R
G7SD 054D-24B1| 0.8| 632495R| 0.5| 632492R
G7SD 072D-35C1| 0.8| 632495R| 0.5| 632492R
G7SD 072D-35C2| 0.8| 632495R| 0.5| 632492R
G7SD 072D-35EC1| 0.8| 632495R| 0.5| 632492R
G7SD 090D-35C1| 0.8| 632495R| 0.6| 632493R
G7SD 090D-35EC1| 0.8| 632495R| 0.6| 632493R
G7SD 108D-35ED1| 1| 1018532R| 0.8| 632495R
G7SD 108D-45D1| 1| 1018532R| 0.8| 632495R
G7SD 120D-35ED1| 1.2| 632622R| 1.1| 1021835R
G7SD 120D-45D1| 0.9| 632487R| 1.1| 1021835R
G7SK 054C-23A1| 0.65| 1021833R| NA| NA
G7SK 054C-23A2| 0.65| 1021833R| NA| NA
G7SK 072C-24B1| 0.6| 632499R| NA| NA
G7SK 090C-24B1| 0.6| 632499R| NA| NA
G7SK 108C-35C1| 0.65| 1021833R| NA| NA
G7SK 126C-45D1| 0.85| 632636R| NA| NA
G7SL 054D-24B1| 0.8| 632495R| NA| NA
G7SL 072D-24B1| 0.8| 632495R| NA| NA
G7SL 090D-35C1| 0.8| 632495R| NA| NA
G7SL 120D-45D1| 0.5| 632492R| NA| NA
G7SM 054D-24B1| 0.8| 632495R| NA| NA
G7SM 072D-35C1| 0.8| 632495R| NA| NA
G7SM 090D-35C1| 0.8| 632495R| NA| NA
G7SM 118D-45D1| 0.7| 632624R| NA| NA
Table 3. Single Stage Pressure Switch Settings
TWO STAGE PRESSURE SWITCH SETTING FOR ALTITUDES BETWEEN 7,500 AND 10,000
FURNACE
MODELS| INDUCER
LOW SETTING
(IN. W.C.)| INDUCER
HIGH SETTING
(IN. W.C.)| INDUCER
PN| COLLECTOR
LOW SETTING
(IN. W.C.)| COLLECTOR
HIGH SETTING
(IN. W.C.)| COLLECTOR
PN
---|---|---|---|---|---|---
G7TA 060C-23A1| 0.33| 0.63| 1021811R| NA| NA| NA
G7TA 060C-VA1| 0.33| 0.63| 1021811R| NA| NA| NA
G7TA 080C-24B1| 0.2| 0.55| 1021812R| NA| NA| NA
G7TA 080C-VB1| 0.2| 0.55| 1021812R| NA| NA| NA
G7TA 100C-24B1| 0.3| 0.6| 1021813R| NA| NA| NA
G7TA 100C-35C1| 0.2| 0.6| 1021814R| NA| NA| NA
G7TA 100C-VC1| 0.2| 0.6| 1021814R| NA| NA| NA
G7TA 120C-35C1| 0.2| 0.6| 1021814R| NA| NA| NA
G7TA 120C-VC1| 0.2| 0.6| 1021814R| NA| NA| NA
G7TA 140C-45D1| 0.3| 0.7| 632566R| NA| NA| NA
G7TA 140C-VD1| 0.3| 0.7| 632566R| NA| NA| NA
G7TC 060D-24B1| 0.33| 0.63| 1021811R| 0.6| 0.85| 1021828R
G7TC 060D-VB1| 0.33| 0.53| 1021819R| 0.6| 0.85| 1021828R
G7TC 080D-35C1| 0.5| 0.9| 1021815R| 0.7| 0.75| 1021829R
G7TC 080D-VC1| 0.5| 0.9| 1021815R| 0.7| 0.75| 1021829R
G7TC 100D-35C1| 0.4| 0.7| 632614R| 0.7| 0.75| 1021829R
G7TC 100D-VC1| 0.4| 0.6| 1021818R| 0.7| 0.75| 1021829R
G7TC 120D-45D1| 0.3| 0.7| 632566R| 0.7| 1.45| 1021830R
G7TC 120D-VD1| 0.3| 0.6| 1021813R| 0.7| 1.45| 1021830R
G7TE 060D-24B1| 0.26| 0.7| 1021820R| 0.6| 0.9| 1017676R
G7TE 060D-VB1| 0.26| 0.7| 1021820R| 0.6| 0.9| 1017676R
G7TE 080D-35C1| 0.35| 0.75| 1021821R| 0.5| 0.8| 1021831R
G7TE 080D-VC1| 0.35| 0.75| 1021821R| 0.5| 0.8| 1021831R
G7TE 100D-35C1| 0.4| 0.75| 1021822R| 0.5| 0.8| 1021831R
G7TE 100D-VC1| 0.4| 0.75| 1021822R| 0.5| 0.8| 1021831R
G7TE 115D-45D1| 0.3| 0.75| 1021823R| 0.7| 1.5| 1021832R
G7TE 115D-VD1| 0.3| 0.75| 1021823R| 0.7| 1.5| 1021832R
G7TK 060C-23A1| 0.2| 0.6| 1021814R| NA| NA| NA
G7TK 060C-VA1| 0.2| 0.6| 1021814R| NA| NA| NA
G7TK 080C-24B1| 0.3| 0.6| 1021813R| NA| NA| NA
G7TK 080C-VB1| 0.3| 0.6| 1021813R| NA| NA| NA
G7TK 100C-35C1| 0.2| 0.6| 1021814R| NA| NA| NA
G7TK 100C-VC1| 0.2| 0.6| 1021814R| NA| NA| NA
G7TK 120C-35C1| 0.2| 0.55| 1021812R| NA| NA| NA
G7TK 120C-VC1| 0.2| 0.55| 1021812R| NA| NA| NA
G7TK 140C-45D1| 0.3| 0.7| 632566R| NA| NA| NA
G7TL 060D-24B1| 0.45| 0.75| 1021817R| NA| NA| NA
G7TL 060D-VB1| 0.45| 0.75| 1021817R| NA| NA| NA
G7TL 080D-35C1| 0.5| 0.9| 1021815R| NA| NA| NA
G7TL 080D-VC1| 0.5| 0.9| 1021815R| NA| NA| NA
G7TL 100D-35C1| 0.4| 0.6| 1021818R| NA| NA| NA
G7TL 100D-VC1| 0.4| 0.6| 1021818R| NA| NA| NA
G7TL 120D-45D1| 0.45| 0.75| 1021817R| NA| NA| NA
G7TL 120D-VD1| 0.45| 0.75| 1021817R| NA| NA| NA
G7TN 060D-24B1| 0.5| 0.85| 1021824R| NA| NA| NA
G7TN 060D-VB1| 0.5| 0.85| 1021824R| NA| NA| NA
G7TN 080D-35C1| 0.55| 0.8| 1021825R| NA| NA| NA
G7TN 080D-VC1| 0.55| 0.8| 1021825R| NA| NA| NA
G7TN 100D-35C1| 0.45| 0.8| 1021826R| NA| NA| NA
G7TN 100D-VC1| 0.45| 0.8| 1021826R| NA| NA| NA
G7TN 115D-45D1| 0.3| 0.7| 632566R| NA| NA| NA
G7TN 115D-VD1| 0.3| 0.7| 632566R| NA| NA| NA
Table 4. Two-Stage Pressure Switch Settings
Specifications & illustrations subject to change without notice or incurring
obligations (11/18).
O’Fallon, MO, © Nortek Global HVAC LLC 2018. All Rights Reserved.
709369C
(Replaces 709369B)
Documents / Resources
|
OXBOX GC2 Series LP Gas Conversion and High Altitude
Kit
[pdf] Instruction Manual
GC2 Series LP Gas Conversion and High Altitude Kit, GC2 Series, LP Gas
Conversion and High Altitude Kit, High Altitude Kit
---|---
Read User Manual Online (PDF format)