MITSUBISHI Plasma Quad Connect Instruction Manual

June 6, 2024
Mitsubishi

MITSUBISHI Plasma Quad Connect Instruction Manual
MITSUBISHI Plasma Quad Connect

This Service Handbook includes only the contents about the Plasma Quad Connect.
For indoor units or other interfaces connected to this product, refer to the service handbook of each device.

Connectable indoor units

  • MAC-100FT-E
    Connectable indoor units are the MSZ series, PKA series, PKFY series, PEFY series, PEAD series and SEZ series with CN105, the connector for the optional parts for remote control.
    See specifications of each indoor unit to find out if CN105 is installed or not.

  • MAC-110FT-E
    Connectable indoor units are the PEFY series, MEXZ series, PEAZ series and PEAD series with CN105, the connector for the optional parts for remote control.
    See specifications of each indoor unit to find out if CN105 is installed or not.

Note:
Some indoor units cannot be attached to the Plasma Quad Connect.
Ask your dealer about the details of the target models.

Precautions on failure diagnosis

[Precautions for setting up, or use of the Plasma Quad Connect]

Be sure not to do
Never touch with wet hand.
Never splash water on the unit.
Be sure to follow the instruction.

Warning
(Improper handling may have serious consequences, including serious injury or death.)

  • Do not disassemble, modify, or repair by yourself (user).
    It can cause electric shock, fire, or injury

  • This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience  and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.

  • Children should be supervised to ensure that they do not play with the appliances.

  • This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.

  • Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.

  • Do not install the Plasma Quad Connect nearby the automatic control devices such as automatic doors or fire alarms
    It can cause accidents due to malfunctions.

  • Do not touch the Plasma Quad Connect with wet hands.
    It can cause damage to the device, electric shock, or fire.

  • Do not splash water on the Plasma Quad Connect or use it in a bathroom.
    It can cause damage to the device, electric shock, or fire.

  • Do not install the Plasma Quad Connect by yourself (user).
    Improper installation may result in fire, electric shock, or injury due to fall of the Plasma Quad Connect. Consult the dealer from whom you purchased the Plasma Quad Connect or professional installer

  • When the Plasma Quad Connect is dropped, or the holder or cable is damaged, disconnect the power supply or turn the breaker OFF.
    It may cause fire or electric shock. In this case, consult your dealer.

  • In case of an abnormal condition (such as a burning smell), stop the indoor unit and disconnect the power supply or turn the breaker OFF.
    A continued operation in the abnormal state may cause a malfunction, fire, or electric shock.
    In this case, consult your dealer.

Caution
(Improper handling may have consequences, including injury or damage to building.)

  • Do not mount the Plasma Quad Connect where children can reach.
    It can cause injury.

  • Do not step on unstable stepstool to set up or clean the Plasma Quad Connect.
    It may cause injury if you fall down.

Instructions for use

Do not use or keep the product in the following environment

Where the product is exposed to direct sunlight

  • Area with poor ventilation
  • Where rain and fog enters
  • Extremely high/low temperature area
  • Dusty area

System Construction

  • When only the Plasma Quad Connect is connected to an indoor unit
    Plasma Quad Connect

  • When the Plasma Quad Connect and other interfaces are connected to an indoor unit.
    Plasma Quad Connect

Procedure of failure diagnosis

Check the following items when the Plasma Quad Connect or the other connected interface does not work properly.

Checking method when the Plasma Quad Connect does not work properly
Perform operation check of the Plasma Quad Connect according to the following flow chart.

When only the Plasma Quad Connect is connected

Plasma Quad Connect
It will take up to about 3 minutes before the LED starts blinking orange after turning on the breaker.

When the other interface is also connected
Plasma Quad Connect

Failure diagnosis method of the Plasma Quad Connect

Perform failure diagnosis of the Plasma Quad Connect according to the following procedure.

Failure diagnosis method

Short-circuit the jumper wire on the printed circuit board with a crocodile clip, then turn on the  power

Short-circuit jumper

The LED on the printed circuit board indicates the state of the Plasma Quad Connect. The lighting pattern of each LED is shown in the table below.

LED71 / LED73 (White)

LED status PQC status
Lit PQC ON
Off PQC OFF
Blink Abnormal

The LED71 is placed on the display printed circuit board.
The LED71 and LED73 indicate PQC status in the same lighting pattern.

LED74 (Orange)

LED status PQC status
Blink Normal communication
Off Abnormal communication