GOODWE EH Series Hybrid Inverter Instruction Manual

June 6, 2024
GOODWE

EH Series Hybrid Inverter

PV Master APP

SEMS Portal APP SEMS Portal website www.semsportal.com

LinkedIn

Company’s offical website

JIANGSU GOODWE POWER SUPPLY TECHNOLOGY CO.,LTD
No.90 Zi Jin Road, SND, Jiangsu, China. www.goodwe.com service@goodwe.com

340-00308-02

EH SERIES USER MANUAL
HYBRID INVERTER
Rev.1.2 2021-01-08

TABLE OF CONTENTS

INTRODUCTION

1.1 OPERATION MODES INTRODUCTION

01

1.2 SAFETY & WARNINGS

02

1.3 PRODUCT OVERVIEW

04

INSTALLATION INSTRUCTIONS

2.1 UNACCEPTABLE INSTALLATIONS

05

2.2 PACKING LIST

05

2.3 MOUNTING

06

2.3.1 SELECT MOUNTING LOCATION

06

2.3.2 MOUNTING

07

2.4 ELECTRICAL WIRING CONNECTION

08

2.4.1 PV CONNECTION

08

2.4.2 BATTERY CONNECTION

09

2.4.3 ON-GRID & BACK-UP CONNECTION

10

2.4.4 SMARTMETER & CT CONNECTION

13

2.5 DRED & EARTH FAULT ALARM

14

2.6 EARTH FAULT CONNECTION

14

MANUAL OPERATION

3.1 WI-FI CONFIGURATION

17

3.2 PV MASTER APP OPERATION

18

3.3 GEI AUTO-TEST INSTRUCTION

18

3.4 BATTERY FUNCTION ACTIVATION

18

OTHERS

4.1 DISCLAIMER

19

4.2 ERROR MESSAGE AND TROUBLESHOOTING

25

4.3 TECHNICAL PARAMETERS AND CERTIFICATES

26

4.4 WARINING QUICK CHECK LIST

28

4.5 CHECKING THE ELECTRICAL CONNECTION

29

INTRODUCTION

01 INTRODUCTION
GoodWe EH series, also called hybrid or bidirecational solar inverters, apply to solar system with participation of PV, battery, loads and grid system for energy management. The energy produced by PV system shall be used to optimize self-consumption, excess power charge battery and the rest power could be exported to the grids. Battery shall discharge to support loads when PV power is insufficient to meet self-consumption. If both PV power and battery power is insufficient, the system will take power form grid to support loads.
In addition, the EH Series includes a Battery-Ready inverter that has no battery function until it is activated. If your inverter is Battery-Ready and not activated now, you can ignore the following battery-related content.

01

Note: The introduction describes a general behavior of EH

system. The operation mode can be adjusted on GoodWe

PV Master APP based on the system layout. Below are the

general operation based on the system layout. Below are

the general operation modes for EH system.

1.1 OPERATION MODES INTRODUCTION
EH system normally has the following operation modes based on your configuration and layout conditions.

Mode
The energy produced by the PV system is used to optimize self-consumption. The excess energy is used to charge the batteries, then exported to gird.

Mode
When there is no PV, and the battery is sufficient , It can supply the load with the grid together.

Mode
When grid fails , the system automatically switches to Back-Up mode, the Back- Up load could be supported by PV and battery.

Mode
Battery could be charged by grid, and charge time/power could be set flexibly on PV Master APP.

INTRODUCTION
1.2 SAFETY & WARNING The EH series hybrid inverter of Jiangsu GoodWe Power Supply Technology Co., Ltd. (hereinafter called as GoodWe) strictly comply with related safety rules for product design and testing. Please read and follow all the instructions and cautions on the hybrid inverter or user manual during installation, operation or maintenance, as any improper operation might cause personal or damage. · SYMBOLS EXPLANATION
Caution! Failing to observe a warning indicated in this manual may result in injury.
Danger of high voltage and electric shock! 02
Danger of hot surface!
Components of the product can be recycled.
This side up! The package must always be transported, handled and stored in such a way that the arrows always point upwards.
No more than six (6) identical packages being stacked on each other.
Product should not be disposed as household waste.
The package/product should be handled carefully and never be tipped over or slung.
Refer to the operating instruc. tions
Keep dry! The package/product must be protected from excessive humidity and must be stored under cover. Inverter will be touchable or operable after minimum 5 minutes of being turned off or totally disconnected, in case of any electrical shock or injury.
CE Mark

INTRODUCTION

· SAFETY WARNING Any installation and operation on hybrid inverter must be performed by qualified electricians, in compliance with standards, wiring rules or requirements of local grid authorities or companies (like AS 4777 and AS/NZS 3000 in Australia).

Prohibit to insert or pull the AC and DC terminals when the inverter is running.

Before any wiring connection or electrical operation on inverter, all battery and AC power must be disconnected from inverter for at least 5 minutes to make sure inverter is totally isolated to avoid electric shock.

The temperature of inverter surface might exceed 60 during working, so please make sure it is cooled down before touching it, and make sure the inverter is untouchable for children

03

Do not open inverter cover or change any components without GoodWe’s authorization,

otherwise the warranty commitment for the inverter will be invalid.

Usage and operation of the inverter must follow instructions in this user manual, otherwise the protection design might be useless and warranty for the inverter will be invalid.

Appropriate methods must be adopted to protect inverter from static damage. Any damage caused by static is not warranted by GoodWe.

PV negative (PV-) and battery negative (BAT-) on inverter side is not grounded as default design. Connecting PV- or BAT- to EARTH are strictly forbidden.

PV modules used on the inverter must have an IEC61730 class A rating, and the total open-circuit voltage of PV string/array is lower than the maximum rated DC input voltage of the inverter. Any damage caused by PV over-voltage is beyond warranty.

The inverter, with built-in RCMU, will exclude possibility of DC residual current to 6mA, thus in the system an external RCD (type A) can be used(30mA).

In Australia, the inverter internal switching does not maintain neutral integrity, which must be addressed by external connection arrangements like in the system connection diagram for Australia on page 16.

In Australia, output of Back-Up side in switchbox should be labeled Main switch UPS supply’, the output of normal load side in switch box should be labeledmain switch inverter supply’.

ON = FAULT HAS OCCURRED
BLINK = OVERLOAD OF BACK-UP OUTPUT / REDUCE LOAD
OFF = NO FAULT

FAULT

OFF = WiFi NOT ACTIVE

BLINK 4 = WiFi SERVER PROBLEM

BLINK 2 = WiFi NOT CONNECT TO ROUTER

WiFi

1.3 PRODUCT OVERVIEW

PV Terminals

BLINK 1 = WiFi SYSTEM RESETTING

Wi-Fi Box Battery Terminals

DC Switch

BMS Communication Cable

To Smart Meter
Smart Meter Communication Cable To Battery

BLINK 1 = SUPPLYING ENERGY TO GRID / ZEROING
BLINK 2 = SUPPLYING ENERGY TO GRID / SELLING
OFF = GRID NOT CONNECTED OR SYSTEM NOT OPERATING
ON=BMS AND METER COMMUNICATION OK
BLINK 1= METER COMMUNICATION OK, BMS COMMUNICATION FAIL BLINK 2= BMS COMMUNICATION OK, METER COMMUNICATION FAIL OFF= BMS AND METER COMMUNICATION FAIL
ON = WiFi CONNECTED / ACTIVE

ENERGY COM

DRED

Meter
On-Grid Port Back-Up Port
Reserved RS485

ON = CONSUMING ENERGY FROM GRID / BUYING

BLINK = GRID IS ACTIVE BUT NOT CONNECTED OFF = GRID IS NOT ACTIVE

GRID

ON = GRID IS ACTIVE AND CONNECTED

OFF = BATTERY IS DISCONNECTED / NOT ACTIVE

BLINK 1 = BATTERY IS DISCHARGING BLINK 2 = BATTERY IS LOW / SOC IS LOW

BATTERY

ON = BATTERY IS CHARGING

ON = BACK-UP IS READY / POWER AVAIL ABLE OFF = BACK-UP IS OFF / NO POWER AVAILABLE

BACK-UP

OFF = SYSTEM IS NOT OPERATING

BLINK = SYSTEM IS STARTING UP

SYSTEM

ON = SYSTEM IS READY

EXPLANATION

INDICATOR STATUS

HYBRID LED INDICATORS
SYSTEM BACK-UP BATTERY GRID ENERGY COM WiFi FAULT

INTRODUCTION
04

LED Label

Wi-Fi Reset

INSTALLATION INSTRUCTIONS
02 INSTALLATION INSTRUCTIONS 2.1 UNACCEPTABLE INSTALLATIONS

Back-Up

Back-Up Load

BACK-UP CANNOT CONNECT IN PARALLEL.

PV

PV

SINGLE PV STRING CANNOT CONNECT TO TWO OR MORE INVERTERS.

Smart Meter

05

ONE METER CANNOT CONNECT TO MULTI INVERTERS, AND

DIFFERENT CT CANNOT CONNECT TO A SAME FIER CABLE.

ONE BATTERY BANK CANNOT BE CONNECTED TO MULTI INVERTERS.

Incompatible battery

ON-GRID OR BACK-UP SIDE CANNOT CONNECT TO ANY AC GENERATOR.

INVERTER BATTERY CANNOT CONNECT TO INCOMPATIBLE BATTERIES.

BACK-UP SIDE CANNOT CONNECT TO GRID

2.2 PACKING LIST
On receiving the hybrid inverter, please check to make sure all the components as below are not missing or broken. Of course, there are no Smart Meter and Smart Meter User Manual if you buy a Battery-Ready inverter without the Smart Meter.

Inverter×1

Wall-mounted Bracket×1

Smart Meter & CT × 1

Positive PV Plug×2

Negative PV Plug×2

Positive BAT Plug×1

Negative BAT Plug×1

Back Up AC Plug X1 On Grid AC Plug X1 PE terminal × 1 Expansion bolts×4

User manual×1

Quick Installation Guide×1

INSTALLATION INSTRUCTIONS
2.3 MOUNTING 2.3.1 SELECT MOUNTING LOCATION For inverter’s protection and convenient maintenance, mounting location for inverter should be selected carefully based on the following rules:
Any part of this system shouldn’t block the switch and breaker to disconnected inverter from DC and AC power. Rule 1. Inverter should be installed on a solid surface, where is suitable for inverter’s
dimensions and weight. Rule 2. Inverter installation should stand vertically or lie on a slop by max 15° (Pic 1)
15°

Pic 1

Rule 3.Ambient temperature should be lower than 45

Rule 4.The installation of inverter should be protected under shelter from direct sunlight or bad

weather like snow, rain, lightning etc. (Pic 2)

06

No DirectSunlight

No Exposure to Rain

No Exposure to Snow

DirectSunlight

Pic 2

Exposure to Rain

Exposure to Snow

Rule 5.Inverter should be installed at eye level for convenient maintenance. Rule 6.Product label on inverter should be clearly visible after installation. Rule 7.Leave enough space around inverter following the values on pic 3.

300mm

200mm

200mm

300mm

Upward———-300mm Downward——500mm Front————-300mm Both sides——-200mm

500mm

Pic 3

Inverter cannot be installed near flammable, explosive or strong electro- magnetic equipment.[1]

INSTALLATION INSTRUCTIONS

2.3.2 MOUNTING

Remember that this inverter is heavy! Please be careful when lifting out from the package.[3]

The inverter is suitable for mounting on concrete or other non-combustible surface only

Step 1
· Please use the mounting bracket as a template to drill 4 holes on right positions (10mm in diameter, and 80mm in depth) (Pic 4)
· Use expansion bolts in accessory box and fix the mounting bracket onto the wall tightly

Wall bracket

Expansion pipe

Note: Bearing capacity of the wall must be higher than 17kg, otherwise may not be able to keep inverter from dropping.

self-tapping screws Pic 4

07

Step 2

Carry the inverter by holding the heating sink on two sides and Place the inverter on the mounting bracket. (Pic 5)

Note: Make sure the heat sink on inverter is right joint with mounting bracket.

Step 3

Ground cable shall be connected to ground plate on grid side (Pic 6)

Step 4
A lock could be used for anti-theft if it is necessary for individual requirement. (Pic 7)

INSTALLATION INSTRUCTIONS
2.4 ELECTRICAL WIRING CONNECTION 2.4.1 PV WIRING CONNECTION
Before connecting PV panels/strings to inverter, please make sure requirements are followed as below : · The total short- circuit current of PV string must not exceed inverter’s max DC current . · The minimum isolation resistance to ground of the PV string must exceed 19.33 k in case of any shock hazard . · PV strings could not connect to earth/grounding conductor. Use the right PV plugs in the accessory box · (BAT plugs are similar with PV plugs, please confrm before use it.)

NOTE: There will be MC4 or Ampheno/ plugs in accessory box, the detailed connection as below:

Step 1

Step 2

Prepare PV cables and PV plugs (Pic 8)

Connect PV cables to PV connectors (Pic 9)

MC4 series

AMPHENOL series

0

Pic 8
NOTE: · Please use PV plugs and connectors in
GoodWe accessory box · PV cable should be standard, 2.5- 4mm2
PV cable

Pic 9
NOTE: · PV cable must be tightly crimped into the connectors · For Ampheno/ connector, the limit buckle cannot be pressed · There will be a click sound if connectors are inset correctly into PV plugs

Step 3 Screw the cap on and plug onto inverter side (Pic 10
Pic 10

NOTE: · There will be a click sound if connectors are inset correctly into PV plugs

The polarity of PV strings or on the inverter cannot be connected by reversely, otherwise inverter could be damaged.[3]

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

2.4.2 BATTERY WIRING CONNECTION

2.4.3 ON-GRID & BACK-UP CONNECTION

If your inverter is Battery-Ready, do not connect the battery to the inverter before activating the battery function, otherwise it will stop working! Besides, do not remove the battery plug and save the battery terminals, if lost, contact GOODWE for sale.
Please be careful against any electric shock or chemical hazard. Make sure there is an external DC breaker (40A) connected for battery without build-in DC breaker.
Make sure battery breaker is off and battery nominal voltage meet EH specification before connecting battery to inverter and make sure inverter is totally isolated from PV and AC power.[4]

An external AC breaker is needed for On-Grid connection to be isolate from grid when necessary. Below are the requirements of On-Grid AC breaker.

Inverter model GW3600-EH GW5000-EH GW6000-EH

AC breaker specification 50A/230V AC breaker 63A/230V AC breaker 63A/230V AC breaker

Please following Cments and steps bellow strictly. Use improper wire may cause bad contact and high impedance, which is dangerous to the system.
Use the right BAT plugs in the accessory box. Use the tin-plated cables with a conductor cross section of 4 to 6 mm² (AWG 10) because the maximum battery current is 25A. Battery cable requirements are as (Pic 11).

Grade

Description

Value

A

Outside Diameter

5.5-8.0 mm

B

Conduct Core Section

mm

09

Pic 11

C

C

Conduct Wire Length

15 mm

Battery wiring connection process is as below

Step 1 Open the spring using a screwdriver 12
12

Step 2

Carefully insert the stripped wire with twisted litz wires all the way in (A). The litz wire ends have to be visible in the spring. Close the spring. Make sure that the spring is snapped in (B).

A

B

click!

Step 3
13

Push the insert into the sleeve (C).

Tighten the cable gland to 2 Nm (D).

Step 4

Use a suitable and calibrated torque wrench,

size 15. Use an open-jaw wrench, size 16, to Fit the two connectors together until the

hold the connector in place.

connection audibly locks into place.

Check to make sure the connection is securely

D

locked.

15 2 Nm
C

1.Use separate AC breaker for individual inverter(Pic 16)

2. On AC side, the individual breaker should be connected before loads (between inverter and loads)(Pic 17)

AC breaker AC breaker
AC breaker Grid
Pic 16

Grid AC breaker

Loads

10

Pic 17

Requirement of AC cable connected to On-Grid and Back-Up side

Make sure inverter is totally isolated from any DC or AC power before connecting AC cable.[5]

Note 1. The choice of AC cable needs to meet both the outside diameter and conduct core section requirements. Please refer to the table for selecting the AC cable. 2. Neutral cable shall be blue, line cable is black or brown (preferred) and protective earth cable yellow-green. 3. For AC cables, PE cable shall be longer than N&L cables, so that if in any case AC cable slips or taken out, the protecting earth conductor will be the last to take the strain.

On-Grid wiring connection process is as below

Step 1

Prepare the AC cable according to the table.
Grade A B C D

Description Outside Diameter Separated Wire Length Conduct Wire Length Conduct Core Section

Value 13-22mm 10-15mm 12-14mm 8-10 mm

14

15

*For the compatible lithium batteries (Pylon/BYD ) connection, please refer to battery connection part in EH QUICK INSTALLATION INSTRUCTIONS

NoteIf you don’t use the back-up function or use on-grid power to charge the battery,the wiring conduct core section can use 4-6mm2 .

INSTALLATION INSTRUCTIONS

Step 2 I. Prepare the terminals and AC cables 2. Put AC cable through terminal cover and screw the three cables tightly on the connectors (Pic 18)
Pic 18
NOTE: 1. Please use the terminals in GoodWe components box; 2. Make sure cable jacket is not locked with conductor

Step 3
Lock terminal cover and screw up the terminal cap

Pic 19

Make sure terminal cover is locked up here.

Note: Make sure the terminal cover is rightly locked onto the terminal (Pic 19)

Step 4

Connect the assambled AC terminals onto inverter

Note: Make sure it is connected to ‘On-Grid’ side (other side connected to public grid) (Pic 20)

Pic 20

Back-Up wiring connection process is as below 11
Step 1

Pic 21

Grade A B C D

Description Outside Diameter Separated Wire Length Conduct Wire Length Conduct Core Section

Value 10-14mm 7-10mm 7-9mm 4 -6mm

NoteThe absence of AC breaker on Back-Up side will lead to inverter damage if only electrical short-circuit happened on Back-Up side. And Back-Up function cannot turn off under On-Grid condition. An external AC breaker (32A) is needed for Back-Up connection to be isolate when necessary.
Step 2
I. Prepare the terminals and AC cables 2. Put AC cable through terminal cover and screw the three cables tightly on the connectors (Pic 22)

NOTE: I. Please use the terminals in GoodWe components box; 2 Make sure cable jacket is not locked with conductor

Torque 0.7~0.9N.m
Pic 22

MAMUAL OPERATION

Step 3 Lock terminal cover and screw up the terminal cap

Pic 23

Make sure terminal cover is locked up here.

Note: Make sure the terminal cover is rightly locked onto the terminal (Pic 23)

Step 4
Connect the assambled AC terminals onto inverter

Press the button and hold it to unlock when unplugging AC terminals.
Note: Make sure it is connected to ‘Back-Up’ side (other side connected to public grid) (Pic 24)

Pic 24

Special Adjustable Setting The inverter has filed adjustable setting like tripping point, tripping time, reconnect time, active and invalid of QU/PU curves etc. by special firmware. Please contact GoodWe after sales for the special firmware and adjust methods.

Connection For SPLIT Grid System

In SPLIT grid system, there is a solution allowing inverter to work under On- Grid condition (Pic 25). But the export power

“To Smart Meter”

110V Load
Grid Side

12

and load power might be detected inaccu-

rately as the nominal output power of

220V Load

inverter is 230V and there could be loads of 110V or 220V.

Back-Up Load(230V)

Pic 25

Declaration For Back-Up Function The below statement lays out GoodWe general policies governing the energy storage inverters of the series ES, EM, SBP, ET, EH and BH. 1. For Hybrid inverters (Series ES, EM, EH and ET), the standard PV installation typically consists of the connection of the inverter with both panels and batteries. In case of systems not connected to the batteries, the Back-Up function is strongly not advised to use. GoodWe shall not cover the standard warranty and be liable for any consequences arising from users not following this instruction. 2. Under normal circumstances, the Back-Up switching time is less than 10 ms (the minimal condition to be considered as the UPS level). However, some external factors may cause the system to fail on Back-Up mode. As such, we recommend the users to be aware of conditions and follow the instructions as below: 1) Do not connect loads if they are dependent on a stable energy supply for a reliable operation 2) Do not connect the loads which may in total exceed the maximum Back-Up capacity 3) Try to avoid those loads which may create very high start-up current surges such as Inverter Air-conditioner, high-power pump etc. 4) Due to the condition of battery itself, battery current might be limited by some factors including but not limited to the temperature, weather etc.

INSTALLATION INSTRUCTIONS

Declaration For Back-Up Loads EH series hybrid inverters are able to supply over load output at its’Back-Up. For details please refer to the technical parameters of EH series inverter (4.3 section). And the inverter has self- protection derating at high ambient temperature.
Accepted loads as below: · Inductive Load: 1.5P non-frequency conversion air- conditioner can be connect to back-up side. Two or more non-frequency conversion air-conditioner connect to back-up side may cause UPS mode unstable. · Capacitive Load: Total power <= 0.6 x nominal power of model. (Any load with high inrush current at start-up is not accepted.) · For complicated application, please contact GoodWe’s after service.

Note: For a convenient maintenance, an DP3T support could be installed on Back-Up and On-Grid side. Then it is adjustable to support load by Back-Up or by grid or just leave it there (Pic 26).
3

Back-up

1:Load is supplied from Back-Up side 2:Load is isolated 3:Load is supplied from grid side

Pic 26

Declaration For Back-Up Overload Protection Inverer will restart itself as overload protection happens. The preparation time for restarting will be longer and longer (max one hour) if overload protection repeats. Take following steps to restart inverter immediately. · Decrease Back-Up load power within max limitation. · On PV Master Adcanced Setting Click”Reset Back-Up Overload History”

2.4.4 SMART METER & CT CONNECTION

Make sure AC cable is totally isolated from AC power before connecting Smart Meter & CT.[6] If you buy a Battery-Ready inverter without the Smart Meter, it is not necessary to view this section. The Smart Meter with CT in GoodWe product box is compulsory for EH system installation, used to detect grid voltage and current direction and magnitude, further to instruct the operation condition of EH inverter via RS485 communication.

1. The Smart Meter and CT is well configured, please do not change any setting on Smart Meter; 2. One Smart Meter can only be used for one EH inverter. 3. CT must be connected on the same direction as the CT indicated.

Smart Meter & CT Connection Diagram (Pic 27)

MAMUAL OPERATION

“To Smart Meter”

Grid
Grid Side

Load
Pic 27
NOTE: 1. Please use the Smart Meter with CT in GoodWe product box. 2.CT cable is 3m as default, could be extended to max 5m. 3. Smart Meter communication cable (RJ45) is attached on the inverter (“To Smart Meter ” cable), could be extended to max 100m, and must use standard RJ45 cable and plug, as below:

Position

Color

1

Orange&white

2

Orange

3

Green&white

4

Blue

5

Blue&white

6

Green

7

Brown&white

8

Brown

BMS Function Smart Meter Function

485_A2

NC

NC

NC

485_B2

485_B1

CAN_H

NC

CAN_L

NC

NC

485_A1

NC

485_B1

NC

485_A1

RS485 485_A 485_B 485_A
NC NC 485_B NC NC

Smart Meter LED Indications

POWER ENERGY
COM

OFF

ON

Blinking

Not working

Working

Importing

Exporting

Blink one time when it transfer data to inverter

POWER ENERGY
COM

2.5 DRED & REMOTE SHUTDOWN CONNECTION
DRED is used for Australia and New Zealand installation (also used as remote shutdown function in European countries), in compliance with Australia and New Zealand safety requirements( or European countries). And DRED device is not provided by GoodWe.

INSTALLATION INSTRUCTIONS

Detailed connection of DRED device is shown below: Step 1 Screw this plate off from inverter (Pic 28).

Note: DRED device should be connected through”DRED port” as the figure shows.

Pic 28

Step 2

1. Plug out the 6-pin terminal and dismantle the resistor on it (Pic 29). 2. Plug the resistor out, leave the 6-pin terminal for next step.

Pic 29

Note: the 6- Pin terminal in the inverter has the same function of DRED device. Please leave it on the inverter if no external device connected.

Step 3-1 For DRED 5
1. Put DRED cable through the plate as shown in Pic 30.
2. Connect DRED cable on the 6-pin terminal.

The function of each connection position as below:

NO

1

2

3

4

5

Function DRM1/5 DRM2/6 DRM3/7 DRM4/8

6 COM/DRMO

Step 3-2 For Remote Shutdown

1. Put the cable through the plate as shown in Pic 31. 2. Wiring from the No. 5 and 6 holes respectively.

Step 4
Connect DRED terminal to the right position onto the inverter (Pic 32).

Screw

The Screw Nut Insulator Cap

RS485 Single hole Cable communication board seal ring

Pic 30

Screw

The Screw Nut Insulator Cap

RS485 Single hole Cable

communication board seal ring

Pic 31

Pic 32
2.6 EARTH FAULT ALARM CONNECTION
GoodWe EH series inverter complies with IEC 62109-2 13.9. Fault indicator LED on inverter cover will light up and the system will email the fault information to customer. Inverter should be installed at eye level for convenient maintenance.

MAMUAL OPERATION

WIRING SYSTEM FOR EH SERIES HYBRID INVERTER Please select Breaker according to the specification below

GW3600-EH GW5000-EH GW6000-EH

40A/600V DC breaker

50A/230V AC breaker 50A/230V AC breaker 63A/230V AC breaker

32A/230V AC breaker 32A/230V AC breaker 32A/230V AC breaker

Depends on household
loads

PV Strings
DC Breaker
40A [1]

To Battery Cable AC Breaker
Smart Meter [4] USB

To Smart Meter CT [2]

Power Meter Grid
AC Breaker

SMART METER Reset
AC Breaker

Grid
House Grid
AC Breaker

On-Grid Load

Battery[3] Back-Up Load
1.For batteries with attached breaker, the external DC breaker is not necessary. 2.Direction of the CT cannot be connected in reverse, please follow House (K)Grid (L)
direction to do the connection. 3.For Battery-Ready inverters, there is no need to route between the battery and the
inverter before activating the battery function. 4.For Battery-Ready inverters without the Smart Meter, there is no need to route them
before purchasing a Smart Meter. For Spain Grid code, the output max. apparent power of GW6000-EH is 6KVA and will be less than 5kVA exported to grid limited by CT controller and power meter. If the generation facility to be connected to the supply network with more than 5 kVA power in single phase, connection of the facility to the network shall be three-phase with an imbalance between phases of less than 5kW.

INSTALLATION INSTRUCTIONS
System Connection Diagrams Note: For Australia safety country, the neutral cable of On-Grid side and Back-Up side must be connected together, otherwise Back-Up function will not work.

BMS
L N Battery

GoodWe EH Series Hybrid Inverter

Back-up Meter

Solar Array

The Grounding screw hole at the lower right corner

L N PE
On-Grid

Distribution box

Don’t connect this terminal for Australian and New Zealand grid system !!!
RS485

RCD
Smart Meter
CT

RCD E-BAR

N-BAR
E-N Link
E-BAR

L

N

Back-up Loads

PE

L
N Grid PE

L N PE Normal Loads
17 This diagram is an example for AustraliaSouth Africa and New Zealand grid system.

BMS
L N Battery

GoodWe EH Series Hybrid Inverter

Back-up Meter

Solar Array

The Grounding screw hole at the lower right corner

L N PE
On-Grid

Distribution box
RCD

RS 485

Smart Meter
CT

RCD E-BAR

E-BAR

L

N

Back-up Loads

PE

L
N Grid PE

L N PE Normal Loads
This diagram is an example for grid systems without special requirement on electrical wiring connection.
Note:The back-up PE line and rack earth must be grounded properly and effectively. Otherwise the back-up function may be abnormal when the grid fail.
Note: After the inverter is installedand worked normal when the grid connected , please turn off the grid power to check whether the back-up function is normal, which can avoid the problems in subsequent uses.

MAMUAL OPERATION

03 MAMUAL OPERATION

3.1 WIFI CONFIGURATION

· This part shows configuration on web page · Wi-Fi configuration is absolutely necessary for online monitoring and after-sales maintenance
PREPARATION: 1. Inverter must be powered up with only PV power 2. Need a router with available internet access to GoodWe portal https://www.semsportal.com

Step 1
1.Connect Solar-WiFi to your PC or smart phone( means the last 8 characters of the inverter serial No.) 2.Open browser and login 10.10.100.253 Admin (U): admin; Password: admin 3.Then click “OK”

10.10.100.253

Admin( U) Password

Remember the password( R)

OK

CANCEL

Step 2

Step 3

1.Click “Start Setup” to choose your router 2.Then click “Next”

Device information

Fimware verison

1.6.9.3.38.2.1.38

MAC address

60:C5:A8:60:33:E1

Wireless AP mode

Enable

SSID

S olar-WiFi

IP address

10.10.100.253

Wireless STA mode

Disable

Router SSID

WiFi_ Burn-in

Encryption method

WAP/WAP2-PSK

Encryption algorithm Router Password

AES WiFi_ Burn-in

Cannot join the network, may be caused by:

router doesn’t exist, or signal is too week, or password is incorrect Help:Wizard will help you to complete setting within one mimute. Start Setup

Please select your current wireless network:

SSID WIFI Test

Sec mode WAP2-PSK

Enctype AES

Channel 6

RSSI 54%

Note: When RSSIof the slected Wifi Network is lower than 1096,the conneteon may be ustbl, please sletoehe vailable neworkor shorten the distance between the device and the router. ifyour wreles router does not bass, plese cik “Next” and add a wireless network manually.

Back

Next

1. Fill in the password of the router, then click “Next” 2. Click “Complete”

Add wireless network manually

Network name (SSID) Encryption method

WiFi-Test WAP/WAP2-PSK

Encryption algorithm

AES

Please enter the wireless network pass word:

Password (8-63 bytes)

hellogoodwe

show psk

Note: case sensitive for S S ID and password

Please make sure all parameters of wireless network are matched with router, including password

Back

Nex t

Save success!
Click ‘Complete’, the current configuration will take effect after restart.
If you still need to configure the other pages of information, please go to complete your required configuration.
Configuration is completed, you can log on the Management page to restart device by Click on ‘OK’ button.
Confirm to complete?

Back Complete

18

Note: 1. Please make sure the password, Encryption Method/Algorithm is right the same with the router’s. 2. If everything is right well, the Wi-Fi LED on inverter will change from double blink to quartic blink then to solid status, which means Wi-Fi is connected to GoodWe icloud successfully. 3. Wi-Fi configuration could also be done on PV Master, details please check on PV Master APP.

MAMUAL OPERATION
· Wi-Fi Reset & Reload Wi-Fi Reset means restarting Wi-Fi module, Wi-Fi settings will be reprocessed and saved automatically. Wi-Fi Reload means setting Wi-Fi module back to default factory setting.

Wi-Fi RESET Button

Wi-Fi Reset

Wi-Fi Reload

short press RESET button – Wi-Fi Led will blink for a few seconds

long press RESET button (longer than 3s) – Wi-Fi Led on inverter will double blink until doing Wi-Fi configuration again.

Note: Wi-Fi Reset & Reload function is only used when: 1. Wi-Fi lost connection to internet or cannot connect to PV Master APP successfully. 2. Cannot find “Solar-WiFi signal” or have other Wi-Fi configuration problem. 3. Please do not use this button if Wi-Fi monitoring works well.

3.2 PV MASTER APP OPERATION
PV Master is an external monitoring/ configuration application for GoodWe hybrid inverters, used on smart phones or pad for both Android and iOS system, main functions as below: 1. Edit system configuration to make the system work as customer needs.
19 2. Monitor and check performance of the hybrid system.
3. Wi-Fi configuration.
Please download PV Master OPERATION INSTRUCTIONS from www.goodwe.com
3.3 CEI AUTO-TEST FUNCTION
PV Auto-Test function of CEI is integrated in PV Master APP for Italy safety country requirement. For detailed instruction of this function please reger to PV Master Operation Instructions.
3.4 BATTERY FUNCTION ACTIVATION

If your inverter is Battery-Ready and you want to activate the battery function, you need to contact the dealer to purchase an activation code and activate the battery function in PV MASTER.
In the Advanced Setting, click on Set, enter the activation code, then go to the Basic Setting to select the work mode, battery model and test

OTHERS

04 OTHERS

4.1 DISCLAIMER

The EH series hybrid inverters are transported, used and operated under environmental

and electrical conditions. GoodWe has the right not providing after-sales services or

assistance under following conditions:

· Inverter is damaged during transferring.

· Inverter is out of warranty year and extended warranty is not bought.

· Inverter is installed, refitted or operated in improper ways without authority from

GoodWe.

· Inverter is installed or used under improper environment or technical condition

mentioned in this user manual, without authority from GoodWe.

· Installation or configuration of the inverter does not follow requirements mentioned in

this user manual.

· The inverter is installed or operated against the requirements or warnings that are

mentioned in this user manual.

· Inverter is broken or damaged by any force majeure like lightening, earthquake, fire

hazard, storm and volcanic eruption etc.

· Inverter is disassembled, changed or updated on software or hardware without

authority from GoodWe.

· Inverter is installed, used or operated against any related items in international or local

policies or regulations.

1240

· Any non-compatible batteries, loads or other devices connected to EH system.

· Obtain the Battery-Ready inverter activation code through illegal channels.

Note: GoodWe will keep right to explain all the contents in this user manual. To insure IP65, inverter must be sealed well, please install the inverters in one day after unpacking, otherwise please seal all unused terminals/holes, not allowed to keep any terminals/holes open, confirm there is no risk to have water & dust in.

*Maintenance The inverter requires periodically maintenance, details as below: · Make sure inverter is totally isolated from all DC and AC power for at least 5 mins before maintenance. · Heat sink: Please use clean towel to clean up heat sink once a year. · Torque: Please use torque wrench to tighten AC and DC wiring connection once a year. · DC breaker: Check DC breaker regularly, active the DC breaker 10 times in a row once a year. · Operating DC breaker will clean contacts and extend lifespan of DC breaker. · Water-proof covers: Check if water-proof covers of RS485 and other part are fastend once a year.

OTHERS

OTHERS

4.2 ERROR MESSAGE AND TROUBLESHOOTINGS

· ERROR MESSAGE The error message below will be displayed on PV Master APP or reported by Email if the error really happens.

ERROR MESSAGE

EXPLANATION

Utility Loss

Not available of public grid power (power lost or on-grid connection fails)

REASON Inverter does not detect the connection of grid

VAC Failure

Grid voltage is not within permissible range

Inverter detects that AC voltage is beyond the normal range required by the safety country

FAC Failure

Grid Eficiency is not within permissible range Inverter detects that Grid frequency is beyond the normal range required by the safety country

PV/BAT Over Vlotage PV or BAT voltage is too high

The total voltage (opencircuit voltage) of each PV string is higher than the max DC input voltage of the inverter. Or the battery voltage is higher than the max BAT input voltage of the inverter

21

Over Temperature Temperature inside of the inverter is too high Inverter working environment leads to a high temperature condition

Isolation Failure

Ground insulation impedance of PV

string is too low

17

Ground l Failure

Ground leakage current is over-high

lsolation failure could be caused by multi reasons like PV panels are not grounded well, DC cable is broken, PV panels are aged or surrounding humidity is comparatively heavy, etc.
Ground I failure could be caused by multi reasons like neutral cable on AC side is not connected well or surrounding humidity is comparatively heavy, etc.

SOLUTIONS
1. Check (use multi-meter) ifAC side has voltageMake sure grid power is available 2. Make sure AC cables are connected tightly and right well 3. If all is well, please try to turm off AC breaker and turn on again after 5 mins
1. Make sure safety country of the inverter is set right 2. Check (use multi- meter) if AC voltage (Between L&N or L&L)is within a normal range (Also on AC breaker side) a. if AC voltage is high, then make sure AC cable complies with that required on user manual and AC cable is not too long b. if voltage is low, make sure AC cable is connected well and the jacket of AC cable is not compressed into AC terminal 3. Make sure the grid voltage of your area is stable and within normal range.
1. Make sure safety country of the inverter is set right 2. If safety country is right, then please check on inverter APP if AC frequency (Fac) is within a normal range 3. If FAC filure only appear a few times and resolved soon, it should be caused by occasional grid frequency unstability.
Check PV string VOC is lower than Max PV Input Voltage of the inverter If VOC of PV string is high, please decrease panels to make sure VOC is with the max DC input voltage of the inverter.
1. Try to decrease surrounding temperature 2. Make sure the installation complies with the instruction on inverter user manual 3. Try to close inverter for 15 mins, then start up again.
1. Use multi meter to check if the resistance between earth & inverter frame is about zero. If it’s not, Please make the connection between earth & inverter frame well.
2. If the humidity is very high, there maybe Isolation Failure occur. 3. Check the resistance betwen PV1+/PV2+/BAT+/PV- to earth, if the resistance is lower than 33.3k, check the system wiring connection. 4. Try to restart the inverter, check if the fault is still happens, if not, means it is just an occasional situation, or contact GoodWe.
Check use multi-meter if there is voltage value (normally should be close to 0V) between earth & inverter frame. If there is a voltage, it means the Neutral & ground cable are not connected well on AC side. If it happened only at early morning, dawn or on rainy days with high air humidity, and recover soon, it should be normal.

Relay Check Failure Self checking of relay fails

DC Injection High

EEPROM R/W Failure

SPI Failure

Internal communication fails

DC Bus High

BUS voltage is over-high

Back-Up Over Load Back-up sid is over loaded

Battery License Fault Battery function is not activated

Neutral & ground cable are not connected well on AC side or just occasional failure.
Inverter detects a higher DC component in AC output Caused by a strong external magnetic field etc. Caused by a strong external magnetic field etc.
Total Back-Up load power is higher than the nominal backup output power
Connect the battery to the inverter without the battery function activated

Check use multi-meter if there is high voltage (normally should be lower than 10V) between N&PE cable on AC side. If the voltage higher than 10V, it means the Neutral & ground cable are not connected well on AC side or restart inverter. Try to restart inverter, check if it still happens, if not, means it is just an occasional situation or contact GoodWe Try to restart inverter, check if it still happens, if not, means it is just an occasional situation or contact GoodWe Try to restart inverter, check if it still happens, if not, means it is just an occasional situation or contact GoodWe Try to restart inverter, check if it still happens, if not, means it is just an occasional situation or contact GoodWe
Decrease Back-Up loads to make sure the total load power is lower than Back-Up nominal output power (please refer to page 12)
First purchase the activation code and activate the battery function in PV MASTER, then connect the battery to use.

22

OTHERS
· TROUBLESHOOTINGS Checking Before Turning On AC power
Battery Connection: Confirm the connection between EH and battery : polarity ( +/-)notreversed, refer to Pic 33. PV Input Connection: Confirm the connection between EHand PV panels : polarity ( +/-)notreversed, refer to Pic 34. On-Grid & Back-Up Connection: Confirm ON-GRID connected to power grid and Back-up toloads : polarity (L/N are in sequence)hot reversed, refer to Pic 35. Smart Meter &CT Connection: Make sure Meter &CTare connected between house loadsand grid. and follow the Smart Meterdirection sign on CT, refer to Pic 36.

Pic 33

Pic 34

Pic 35

Pic 36

23 Checking as Start EH up and Turn On AC Power
Battery Settings,BMS Communication and Safety Country: After connecting Solar- WiFi ( meansthe last 8 characters of the inverter serial No.), check on PV Master APP Param to make sure batterytype is right what you have installed, and Safety Country is right. If not right, please set it right in “Set”(Pic 32)

Note: For compatible lithium batteries, BMS status is “Communication OK” after selecting the right battery type.

OTHERS
Possible Problems During Operation
No Discharge or Output From EH at Night Without PV or PV Power Lower Than Load Power: Solution: 1.Communication between EH and Smart meter is OK or not. 2.Make sure load power is higher than 100W.
a. Battery will not discharge continuously unless load power is higher than 100W. b. If battery stil not discharge when Meter power is higher than100W, then please check Meter &
CT connection and direction. 3. Make sure SOC is higher than 1-DOD. Or if battery discharged to below 1-DOD, than battery will
only discharge again when SOC charged to (20%+1-DOD)/2 and sOC > 105% -DOD (if need battery discharge immediately, Inverter should be restarted) 4. Check on APP if it is set as charge time, during charge time, battery will not discharge (battery will charge in priority during coincident time of charge/discharge)
Battery Not Charge When PV Power Higher Than Load Power: Solution:
1.Check if it is during discharge time set on App. 2.Check if battery is fully charged or not, or battery voltage reach “charge voltage” or not.
High Power Fluctuation on Battery Charge or Discharge: Solution:
24
1.Check if there is a fluctuation on load power. 2.Check if there is a fluctuation on PV power.
Battery Does Not Charge: Solution:
1.Make sure BMS communication is OK on PV Master (for lithium batteries). 2.Check if CT connected in the right position and to right direction as on the user manual page 15. 3.Check if the total load power is much higher than PV power.

Pic 37

OTHERS
About Wi-Fi Configuration Q: Why cannot connect Solar-Wifi signal on my phone? A: It is the character of the Wi-Fi module that it can connect to only one device at a time. If the signal is connected to another device at the time for some reason, then you cannot connect to the signal.
About Battery Operation Q: Why battery does not discharge when grid is not available, while it discharge normally when grid is available? A: On APP Off- Grid Output and backup function should be turned on to make battery discharge under off-grid mode.
Q: Why there is no output on Back-Up side? A: For Back-Up supply, the”Back-Up Supply” on PV Master App must be turned on. Under off grid mode or grid power is disconnected, “Off-Grid Output Switch” function must be turmed on as well. Note: As turn”Off-Grid Output Switch”on don’t restart inverter or battery, otherwise the function will switch off outomatically.
Q: On Portal, why battery SOC has a sudden jump up to 95%? A: This normally happens on when BMS communication fail on lithium battery. If battery enter float charge, SOC will be reset to 95% compulsively. Q: Why battery cannot be fully charged to 100% A:Battery will stop charge when battery voltage reaches charge voltage set on PV Master APP
25
Q: Why battery switch always trip when starts it up (Lithium battery)? A: The switch of lithium battery normally trips for following reasons: 1.BMS communication fails. 2.Battery SOC is too low, battery trips to protect iself. 3.An electrical short-cut happened on battery connection side. Or other reasons please contact GoodWe for details. Q: Which battery should I use for EH? A:For EH series inverter, it could connect Lithium batteries which have compatibility with EH series inverter. With nominal voltage from 85V to 450V. Compatible lithium batteries can see on battery list in PV MASTER APP
About PV Meter Operation and Monitoring Q: Why Cannot save settings on PV Master App? A: This could be caused by losing connection to Solar-WiFi. 1.Make sure you connected Solar-WiFi (make sure no other devices connected) or router (if connected Solar-WiFi to router) and on APP home page shows connection well. 2.Make sure EH under waiting mode (on APP) before you change any sttings on PV Master APP disconnect grid/load/battery, only leave PV connected and then restart EH till see work mode as “wait” on APP.

OTHERS

4.4 TECHNICAL PARAMETERS AND CERTIFICATES
Q: On the App, why the data on the homepage and Param page is diferent, like charge/discharge, ·PVTvEaCluHeN, loICaAdLvaPluAeRoArMgrEidTvEaRluSeO? F HYBRID CONVERTERS A: As the data on APP is from inverter and on home page and Param page, the data refresh frequency is diferent, so there will be a data inconformity between diferent pages on APP as well as between that on portall and APP.
Q: On App, some columns show NA, like battery SOH, etc. why is that? A: NA means App does not receive data from inverter or server, normally it is because communication problem, such as battery communication, and communication between inverter and the APP:

About Meter and Power Limit Function Q: How to Act Output Power Limit function? A: For EH system, the function could be realized by: 1. Make sure Meter connection and communication well; 2. Turn on Export Power Limit function and Set the max output power to grid on APP; Note: If Out-put Power Limit set as 0W, then there might still have deviation max 100W exporting to grid.
Q: Why there is still power exporting to grid after I set power limit as 0W? A: Export limit could theoretically to minimum 0W, but there will have a deviation of around 50- 100W for EH system.

Q: Can I use other brand Meter to take over Meter in EH system or change some settings on Meter?

A: Cannot, because there the communication protocol is inset between inverter and Meter,

other brand Meter cannot communicate. Also any manual setting change could cause Meter

26

communication failure.

Q: What is the max current allowed going through CT on Meter? A: The max current forCT is 120A

Other Questions Q: Is there a quick way to make the system work? A: The shortest way, please refer to EH QUICK INSTALLATION INSTRUCTIONS and PV MASTER APP INSTRUCTION.
Q: What kind of load can I connect on Back-Up side? A: Please refer to user manual on page 12
Q: Whether the warranty of the inverter still valid if the installation or operation does not follow the user manual instructions, for some special conditions when we cannot 100% follow them?
A: Normally if any problem caused by disobey the instructions on user manual, we can provide technical support to help to solve the problem, but cannot guarantee a replacement or returns. So if there is any special condition when you cannot 100% follow the instructions, please contact GoodWe for suggestions.

OTHERS

4.3 TECHNICAL PARAMETERS AND CERTIFICATES

TECHNICAL PARAMETERS OF EH INVERTER

Technical Data

GW6000-EH

GW5000-EH

GW3600-EH

Battery Input Data

Battery Type

Li-Ion

Battery Voltage Range(V)

85~460

Start-up Voltage (V)

90

Max. Charging/Discharging Current (A)

25/25

Max. Charging/Discharging Power (W)

6000

5000

3600

Battery Ready Optional Function

YES

YES

YES

PV String Input Data

Max. DC Input Power (W)

8000

6650

4800

Max. DC Input Voltage (V)

580

580

580

MPPT Range (V)

100~550

100~550

100~550

Start-up Voltage (V)

90

Min. Feed-in Voltage (V) *6

100

MPPT Range for Full Load (V)

250~550

210~550

150~550

Nominal DC Input Voltage (V)

380

380

380

Max. Input Current (A)

12.5/12.5

Max. Short Current (A)

15.2/15.2

No. of MPP Trackers

2

No. of Strings per MPP Tracker

1

AC Output/Input Data (On-grid)

Nominal Apparent Power Output to Utility 6000
Grid (VA)*2

5000

3600

Max. Apparent Power Output to Utility Grid(VA)*2

6000/6600*1

5000/5500*1

3600/3960*1

27

Max. Apparent Power from Utility Grid (VA) 12000(Charging

10000(Charging

7200(Charging

6kw,backup output 6kw) 5kw,backup output 5kw) 3.6kw,backup output 3.6kw)

Nominal Output Voltage (V)

230

Nominal Output Freqency (Hz)

50/60

Max. AC Current Output to Utility Grid (A)2 26.1/28.71

21.7/24*1

16/18*1

Max. AC Current From Utility Grid (A)

52.2

43.4

32

Output Power Factor

Adjustable from 0.8 leading to 0.8 lagging

Output THDi (@Nominal Output)

<3%

Back-up Output Data (Back-up)

Max. Output Apparent Power (VA)

6000

5000

3600

Peak Output Apparent Power (VA)

720060sec

600060sec

432060sec

Max. Output Current (A)

26.1

21.7

15.7

Automatic Switch Time (ms)

<10

Nominal Output Voltage (V)

230 (±2%)

Nominal Output Frequency (Hz)

50/60 (±0.2%)

Output THDv (@Linear Load)

<3%

OTHERS

Efficiency

PV Max. Efficiency

97.60%

PV Europe Efficiency

97.00%

PV Max. MPPT Efficiency

99.90%

Battery Charged By PV Max. Efficiency

98.00%

Battery Charge/discharge From/To AC Max. Efficiency

96.60%

Protection

Anti-islanding Protection

Integrated

Battery Input Reverse Polarity Protection

Integrated

Insulation Resistor Detection

Integrated

Residual Current Monitoring Unit

Integrated

Output Over Current Protection

Integrated

Grid Output Short Protection

Integrated

Output Over Voltage Protection

Integrated

General Data

Operating Temperature Range ()

-35~60

Relative Humidity

0~95%

Operating Altitude (m

4000

Cooling

Nature Convection

Noise (dB)

<35

User Interface

LED & APP

Communication with BMS*3

RS485; CAN

Communication with Meter

RS485

Communication with Portal

Wi-Fi/Ethernet(Optional)

Weight (kg)

17

Size (WidthHeightDepth mm

354433147

Mounting

Wall Bracket

Protection Degree

IP65

Standby Self Consumption (W)*4 Topology

<10

28

Battery Non-Isolation

Certifications & Standards*5

Grid Regulation

VDE-AR-N 4105

Safety Regulation

IEC/EN 62109-1&2

IEC/EN 62109-1&2

IEC/EN 62109-1&2

EMC

EN61000-6-1

*1: For CEI 0-21.

*2: The grid feed in power for VDE-AR-N 4105 and NRS097-2-1 is limited 4600VA, for AS/NZS 4777.2 is limited 4950VA & 21.7A.

*3: CAN communication is configured by default. If 485 communication is used, please replace the corresponding communication

line.

*4: No Back-up Output.

*5: Not all certifications & standards listed, check the official website for details.

*6: When there is no battery connected, inverter starts feeding in only if string voltage is higher than 200V.

OTHERS

1: For CEI 0-21. 2: The grid feed in power for VDE-AR-N 4105 and NRS097-2-1 is limited 4600VA, for AS/NZS 4777.2 is limited 4950VA & 21.7A. 3: CAN communication is configured by default. If 485 communication is used, please replace the corresponding communication line. 4: No Back-up Output. *5: Not all certifications & standards listed, check the official website for details.
CERTIFICATES OF ET SERIES

on it d uc er d ot or n i Po m

pe d T y te
t es

t u v – s u d .c o m/ ps- cer t

G100 IEC62109-1 RD1699 VDE0126-1-1

CEI 0-21 VDE-AR-N 4105 NRS 097-2-1

· OTHER TEST · For Australia requirements, in the THDi test, there should add Zref between inverter and mains.
RA, XA for Line conductor RN, XN for Neutral conductor
Zref:
29 RA=0,24;XA=j0,I5 at 50Hz;
RN=0,I6;XN=j0,10 at 50Hz.

OTHERS

4.4 WARNING QUICK CHECK LIST
[1] Inverter cannot be installed near flammable, explosive or strong electro- magnetic equipment, page 06 [2] Remember that this inverter is heavy! Please be careful when lifting out from the package, page 07 [3] The polarity of PV strings or on the inverter cannot be connected by reversely, otherwise inverter could be damaged, page 08 [4] Make sure battery breaker is off and battery nominal voltage meet EH specification before connecting battery to inverter and make sure inverter is totally isolated from PV and AC power, page 09 [5] Make sure inverter is totally isolated from any DC or AC power before connecting AC cable, page 11 [6] Make sure AC cable is totally isolated from AC power before connecting Smart Meter & CT, page 13
Appendix: Protection Category Definition

Overvoltage Category Definition

Category

Applies to equipment connected to a circuit where measures have been taken to reduce transient overvoltage to a low level

Category

Applies to equipment not permanently connected to the installation. Examples are appliances, portables tools and other plug- connected equipment

Category

Applies to a fixed equipment downstream of and including the main distribution board. Examples are switchgear and other equipment in an industrial installation

Applies to equipment permanently connected at the origin of an installation (upstream of the main distribution board). Example

3

Category

are electricity meters, primary over-current protection equipment and other equipment connected directly to outdoor open

lines

Moisture Location Category Definition

Moisture Parameters Temperature Range
Humidity Range

3K3 0~+40 5%~85%

Level
4K2 -33~+40 15%~100%

4K4H -20~+55 4%~100%

OTHERS

Environment Category Definition

Environment Condition

Ambient Temperature

Outdoor

-20~50

Indoor Unconditioned

-20~50

Indoor Conditioned

0~40

Relative Humidity 4%~100% 5%~95% 5%~85%

Applied to PD3 PD3 PD2

Pollution Degree Definition

Pollution Degree Pollution Degree Pollution Degree

No pollution or only dry, non-conductive pollution occurs. The pollution has no infuence
Normally only non-conductive pollution occurs. Ooccasionally, however, a temporary conductivity caused by condensation must be expected.
Conductive pollution occurs, or dry, non-conductive pollution occurs, which becomes conductive due to condensation, which is expected.

Pollution Degree

Persistent conductive pollution occurs, for example, the pollution caused by conductive dust, rain and snow.

4.5 CHECKING THE ELECTRICAL CONNECTION 31
1. Check if the AC or DC wire is loose. 2. Check if the earth wire is reliable grounding.
3. Check if the waterproof covers of BMS and Meter port is fasten. 4. Please use torque wrench to tighten the AC and battery terminal wiring connection
once a year; followed 2.4 torque instruction.
Caution: Maintenance cycle is once half a year.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals