The Dri-Eaz®LGR i-Series dehumidifiers reduce humidity in enclosed structural environments by removing water vapor from the air. The i-Series product line is engineered to be rugged, durable, and highly portable, making them ideally suited for water damage restoration, structural drying, construction, and other applications requiring temporary, high-performance dehumidification.
Patents: LBpatents.com
READ AND UNDERSTAND BEFORE OPERATING

SAFETY INSTRUCTIONS

WARNING! Do not alter or modify your unit in any way. Use only replacement parts authorized by Dri-Eaz Products, Inc. Modifications or use of unapproved parts could create a hazard and will void your warranty. Contact your authorized distributor for assistance.
CORRECT PLUG REMOVAL
Grasp IEC plug and pull straight out IMPORTANT: Damage to IEC receptacle or dehumidifier resulting from improper removal of the power cord is not covered by warranty. The IEC power cord is a worn item and is not covered by a warranty.

WARNING! Electric shock hazard, rotating fan, hot surface hazards. Unplug the unit before opening the cover for cleaning or servicing. The unit must be grounded.

  • Inspect the power cord before use. If the cord is damaged, do not use it. Always grasp the plug (not the cord) to unplug.
  • Insert the three-prong plug-on power cord into a matching electrically grounded outlet. Do not use an adapter. Never cut off the third prong. Do not use an extension cord.
  • The unit must be operated on a 115V/60Hz circuit protected by a Ground Fault Circuit Interrupter (GFCI) device.
  • Keep motor and wiring dry.
  • Do not attempt to repair the unit. For Authorized Service Centers, contact Dri-Eaz.

NOTICE: Do not use in environments where corrosive chemicals are present, such as chlorine.

BEFORE YOU BEGIN

Warranty registration
Visit warranty.LegendBrandsRestoration.com to register your purchase. Registration allows us to better assist you with using, maintaining or servicing your equipment and to contact you in case we have important safety information concerning your Dri-Eaz product. If you determine service is required, have your equipment model, serial number, and original proof of purchase available and call your distributor for assistance with obtaining a return material authorization (RMA).

PARTS IDENTIFICATION

INTRODUCTION

How LGR dehumidifiers work
Dri-Eaz LGR (low-grain refrigerant) dehumidifiers operate by pulling moist air in across a very cold evaporator core. The moisture in the air condenses on the coil. In certain conditions, the machine operates in defrost mode, warming any frost that has accumulated on the evaporator coil back into the water. The water collects in a tray and is pumped out through a hose.
Onboard sensors continually monitor environmental conditions and system operations of the dehumidifier, including temperature and relative humidity, which can be viewed on the display panel.
LGR dehumidifiers have better heat exchange and defrost abilities than regular refrigerant dehumidifiers, and are able to continue removing moisture in drier environments.

POSITIONING A DEHUMIDIFIER

For best results, operate your dehumidifiers in an enclosed area, as this creates a drying chamber. Close all doors and windows that open to the outside to maximize the unit’s water removal efficiency. Also, keep traffic through the drying chamber to a minimum. Place your dehumidifier against a wall, away from obstructions, and keep it away from anything that could block airflow into and out of the unit.

OPERATING YOUR DEHUMIDIFIER

Set unit upright
NOTICE: If you transport an i-Series dehumidifier in a horizontal position, set it upright and let it stand for at least 30 minutes before you turn it on. When the machine is horizontal, the oil from the compressor flows into the refrigerant coils reducing the ability of the dehumidifier to function. Letting the unit stand upright for 30 minutes allows the oil to flow back into the compressor.
Set up drain hose
This unit automatically pumps out water on a regular basis. This dehumidifier is equipped with a quick-connect fitting for attachment to the provided 40 ft. (12 m) drain hose located in the side pocket. Unwrap the entire hose and place the open end in a sink, drain, bucket or outdoors – anywhere that water can drain out safely. If you use a bucket or other container for water collection, check it regularly to prevent overflows.

NOTE: Uncoil and straighten the entire drain hose. Do not leave any part of the hose coiled on the unit and do not place the end of the hose higher than 20 ft. (6 m) above the top of the unit. Also, check for kinks or obstructions that would restrict the flow of water. Failure to do so may cause a water backup in the pump resulting in leakage.
Plugin the electrical cord
The i-Series dehumidifier should be plugged into a GFCI-protected 115 volt outlet rated for at least 15 amps. Remove the cord from its storage pocket and uncoil it. Always plug the cord firmly into the unit first, and then plug the other end into a suitable outlet.

HOW TO USE THE CONTROL PANEL

The i-Series Controller provides comprehensive dehumidifier controls and detailed real-time data about the drying environment as well as job hours, self-diagnosis messages, maintenance reminders and operating status.
For detailed information and additional instructions, please visit the i-Series Controller page at Controller.LegendBrandsRestoration.com

Home Screen Views
Unit OFF
Unit must be plugged in.
Top display bar:
Job hours, current time
Press MENU to access settings and configuration controls
Press PURGE to pump out the condensate tank
Press ON/OFF to turn the unit on.

Unit ON
Press ON/OFF key to switch unit on.
Top display bar:
Job hours, current time
Information display:
Inlet/Outlet temp, %RH and GPP
Current GPP removal
Bottom menu bar:

Quick-Reference Inlet GPP.
1: < 60 GPP; 2: 60–90 GPP; 3: > 90 GPP
Press MENU to access settings and configuration controls
Press PURGE to pump out the condensate tank
Press ON/OFF to turn the unit off.

For detailed control panel instructions, please visit the i-Series Controller product page at Controller.LegendBrandsRestoration.com

ERRORS AND WARNINGS

If the control system detects a problem, it will display an “Alert” symbol in the upper right corner of the screen. Press ON/OFF to view the message and OK to clear the message. NOTE: In the case of an error, the unit will not operate until the problem is resolved. Refer to the explanations and solutions shown below. If these solutions do not fix the problem, contact your local authorized service center for further assistance.

CONTROL PANEL
MESSAGE| EXPLANATION AND SOLUTION
---|---
ER4 Error
Defrost Thermistor Connect
—or—
ER4 Error
Outlet Thermistor Connect| The temp sensor is open, missing, or shorted. Check that temp sensors are installed correctly on the control panel. If the error persists, contact the service.
ER5 Error
Inlet RH1 Temp/RH Sensor| Inlet Temp/RH sensor is open, missing, or shorted. Check that inlet temp/RH sensor is installed correctly on the control panel and inlet shroud. If the error persists, contact the service.
ER5 Error
Inlet RH1 Temp/RH Sensor| Inlet Temp/RH sensor is open, missing, or shorted. Check that inlet temp/RH sensor is installed correctly on the control panel and inlet shroud. If the error persists, contact the service.
ER6 Error
Current Sensor Failure| Current sensor failure. If the error persists, contact the service.
ER9 Error
Pump Blocked| Check for obstructions in the drain hose. Check the pump.
W1
Low BATTERY| Replace coin cell battery (3V, CR2032) on the control panel.
W2
BLE Error
W3
Flash Reset
W4
WDT Reset| Cycle power to the dehumidifier. If the warning persists, contact service.

AT THE END OF THE JOB

To reduce the possibility of drips when moving the unit, follow these additional steps to ensure that all water is removed from the unit.
NOTICE: The unit will complete the defrost cycle even if the unit is turned off but still plugged in. If the unit is unplugged during the defrost cycle, excessive water may accumulate in the unit and may drip out when you move the unit.
NOTICE: To ensure the condensate tank empties completely while purging, make sure the unit is placed upright on a horizontal surface.

  1. Do not turn unit off or move it until it has returned to normal operating mode.
  2. Gently rock the machine to ensure any water remaining on interior surfaces falls into the sump area.
  3.  Press the PURGE key. When the purge cycle is complete, turn the unit off.
  4. Disconnect the external drain hose, drain it carefully, coil it, and secure it in the pocket or the strap provided with your unit.

MAINTENANCE

WARNING! ELECTRIC SHOCK HAZARD.
Unplug the dehumidifier before performing any maintenance.

Before each use
Inspect the electrical cord for damage. Look for fraying, cuts, etc. Do not use the unit if you find any damage. Call Dri-Eaz for the nearest Service Center at 800-932-3030.
Inspect filter. Replace if the accumulation of dust and debris is visible.
NOTICE: Replace used filters only with a new  Dri-Eaz filter #121708 (F584). Other filter types do not provide adequate filtration or airflow.
Monthly
Check coils. Dirty coils can cause the unit to overheat.
Clean when visibly dirty.
Check heat exchange block.
Clean out with compressed air only. Take care not to damage the block.
Inspect and clean the pump. To remove the condensate pump unit:
SERVICING THE PUMP AND DRAIN PAN
To maintain proper operation, the pump and drain pan assembly should be periodically removed and cleaned follow these steps to clean the pump and drain pan assembly:
Tools Needed
Philips screwdriver
Flat blade screwdriver ⅜ in. and 15∕16 in. sockets and driver
Cleaning cloths

DISASSEMBLY AND CLEANING

  1. Unplug the unit, then remove the power cord from the socket at the base of the unit. Remove pump house at quick-connect.
  2. Remove filter.
  3. Remove the two bolts from the upper front cover.
  4. Remove one bolt each from the upper back corner of side covers A and B (see Fig. A)
  5. Remove four bolts from the lower back panel. The back/top panel may now be removed.
  6. Remove lower back metal panel (unscrew the five attachment screws).
  7. Place firm support under the base of the unit so that the left wheel may be removed.
  8. Using the flat blade screwdriver, carefully pry the center hub cap loose from the left wheel. Use the 15 ∕16 in. sockets to remove the retaining nut and slide the wheel off. See Fig. E, #1.
  9. Remove the two electric box retaining screws (see Fig. E, #2.).
  10. Tilt the bottom of the electric box to the right and slide outward (Fig. F). It is not necessary to disconnect any electrical cables.
  11. Remove drain hose from pump assembly and slide pump and tray assembly out of the unit.
  12. Lift pump body out of plastic catch tray.
  13. Wipe or rinse off all surfaces of the plastic catch tray with a damp cloth.
  14. Remove the pump assembly from the pump tray and set the pump aside. Wipe or rinse out the pump tray and wipe dry.
  15. Remove the pump-out hose from the check valve outlet.
  16. Unscrew check valve. Using needle-nose pliers, carefully remove the bottom of check valve assembly by inserting one side of pliers approximately ⅛ in. into hole, grasp and pull out carefully. A small ball bearing should fall out so be careful not to lose it. Inspect assembly for debris in assembly and clean accordingly. Reinstall the ball bearing and reinstall the check valve assembly. Reassemble in reverse order. The dehumidifier is now ready for use.

Annually
Have the pump system inspected by a qualified service center.

TRANSPORTATION AND STORAGE

IMPORTANT: Before moving, transporting or storing, purge unit and stow hose and power cord as described in the “At the End of the Job” section above. NOTICE: Handle the unit carefully. Do not drop, throw or place the unit where it could fall. Rough treatment can damage the dehumidifier and may create a hazardous condition or void the warranty.

  • Do not expose the control panel to moisture, snow or rain.
  • Store and transport securely to avoid any damaging impact to internal parts.
  • Secure during transport to prevent sliding and possible injury to vehicle occupants.
  1. After placing firm support under the base of the unit, remove the center hub cap and remove the axle nut. The wheel will now slide off.
  2. Remove the two screws (shown in the circles above) to detach the electric junction box.
  3. Do not transport or store the unit on its front, sides or back. This will help to prevent any remaining moisture from escaping from the unit or flowing into areas outside the sump.

CLEANING COILS AND HEAT EXCHANGE BLOCK

WARNING! Unplug unit before servicing.
To help keep the unit operating efficiently, keep the coils and the air-to-air heat exchange block clean. Access these components by removing the side and rear covers:

  1. Unplug unit.
  2. Unplug the power cord from the socket at the base of the unit. Remove pump house at quick-connect.
  3. Remove filter.
  4. Remove both sides covers A and B (unscrew two bolts shown for each panel).
  5. Remove back cover (unscrew the four bolts shown on the back and the two bolts on the upper front panel).
  6. Remove the heat exchange block.

Inspect the heat exchange block carefully. If necessary, use compressed air to clear the channels of the block, taking care not to damage the block.
NOTICE: The unit is fitted with sensitive electronic sensors. Protect the sensors from impact and do not expose them to water or cleaning solutions.
Vacuum or use compressed air on both sides of the upright (condenser) coil until it is clean. Take care not to let the nozzle touch the fins; as this may damage the fins. A coil cleaner product may be used on the horizontal cold (evaporator) coil only. Follow instructions on the product label. Take care not to spray or wipe the product on or near any electrical components or sensors. To
clean the vertical (condenser) coil, contact Service for instructions.
To reassemble, follow the above steps in reverse. Be sure to reinstall the heat exchange block in the original orientation. When installing the rear cover, carefully thread the pump hose through the hole in the back pocket before putting the cover in place.

After removing attachment screws (Fig. E), tilt the bottom of the electrical box to the right and slide it out. Set aside. It is not necessary to disconnect any electrical cables.
NOTICE: Rubber strips are attached to the outside edges of the evaporator and condenser coils to provide an airtight seal around the heat exchange block. When reinstalling the block, make sure the seals are in place and are not kinked or folded.

TROUBLESHOOTING

FAULT CAUSE SOLUTION
Water drips out when moving unit Unit was unplugged before purging was
complete. Purge unit before moving. See “At the End of the Job.”
Unit does not operate Unit not switched on. No power to the machine. Switch

unit on.
Plug-in unit; check power cord connection at wall outlet and at base of the unit.
Unit operating, but room not dry| Not enough time to dry.
Poor air movement in room. Excessive moist air infiltration.| Make sure “Humidistat” is OFF.
Allow more time for drying.
Increase air movement with air movers. Seal off area to reduce infiltration.
Unit collects too little water| Room air is dry.
The room temperature is too low. The filter is full.
Coils are clogged.| Make sure “Humidistat” is OFF.
Confirm humidity level with a hygrometer. Increase room temperature.
Check filter. Replace as necessary. Check coils. Clean as necessary.
If the problem you are experiencing is not listed here, call your local distributor or contact our Service Department at 800-932-3030 for further assistance.

SPECIFICATIONS

Model LGR 2800i #110128 (F410) LGR 3500i #110133 (F411)
Use weight 156 lbs. 1 70.8 kg 158 lbs. 1 71.2 kg

Dimensions
(H x D x w)| 40.5 x 23 x 24 in. 103 x 58 x 61 cm| 40.5 x 23 x 24 in. 103 x 58 x 61 cm
Power| 8.0 amps, 120 volts| 11.2 amps, 120 volts
Water removal AHAM (80°F/60% RH)| 130 pts. 1 61.5 liters / day| 170 pts. 1 80.4 liters / day
Water removal max. (90°F190% RH)| 200 pts. 1 94.6 liters / day| 240 pts. 1 113.6 liters / day
Water removal 80°F/20% RH| 20 pls. ! 9.5 liters / day| 24 pts. 1 11.4 liters / day
Max process air| 400 CFM 1 679.7 CMH’| 400 CFM 1 679.7 CMH
Operating range| 33°F-125°F 1°C-52°C| 33°F-100°F 1°C-38°C
Construction| Rotomolded shell| Rotomolded shell
Safety| ETL certified to CSA 22.2 no. 92| ETL certified to CSA 22.2 no. 92
Specifications are subject to change without notice. Some values may be approximate.
Automatic variable speed for optimized performance.

PARTS INCLUDED
40 ft. (12 m) of drain hose with quick-connect fitting.
25 ft. (7.6 m) detachable power cord.
4-PRO air filter. Reorder #121708 (F584) 24 pk.
ACCESSORIES
VMax Adaptor #100694 (F422)
Sto&Go Ducting #113260 (F405)
FOR PARTS AND SERVICE CALL YOUR LOCAL DISTRIBUTOR or Dri-Eaz at 800-932-3030. Visit
warranty.LegendBrandsRestoration.com and registeryour purchase to ensure you receive any important product releases.

WARNING: This product may expose you to chemicals, including lead and phthalates, known to the State of California to cause cancer, birth defects, or other reproductive harm. For more information, go to P65Warnings.ca.gov
Legend Brands, Inc.

Documents / Resources

| DRI- EAZ 110128 F410 2800i Portable Dehumidifier [pdf] Owner's Manual
LGR 2800i Portable Dehumidifier, 110128, F410, 110128 F410 2800i Portable Dehumidifier, Dehumidifier, LGR 3500i Portable Dehumidifier 110133 F411
---|---

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals