Carrier Split-System Air Conditioners Instruction Manual
- June 6, 2024
- Carrier
Table of Contents
CA13NA 018–060
CA14NA 018–060
CA15NA 018–060
*CA16N 018–061
SPLIT–SYSTEM AIR CONDITIONERS
WITH R–410A REFRIGERANT**
Installation Instructions
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use
can cause an explosion, fire, electrical shock, or other conditions which may
cause death, personal injury, or property damage. Consult a qualified
installer, service agency, or your distributor or branch for information or
assistance. The qualified installer or agency must use factory-authorized kits
or accessories when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work
gloves. Use quenching cloth for brazing operations. Have fire extinguisher
available. Read these instructions thoroughly and follow all warnings or
cautions included in the literature and attached to the unit. Consult local
building codes and current editions of the National Electrical Code (NEC)
NFPA 70. In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.
Recognize safety information. This is the safety–alert symbol **When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING , and CAUTION. These words are used with the safety–alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE** is used to highlight suggestions that will result in enhanced installation, reliability, or operation.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing the system, the main electrical
disconnect switch must be in the OFF position. There may be more than 1
disconnect switch. Lockout and tag switch with a suitable warning label.
WARNING
| EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury,
and/or property damage.
Never use air or gases containing oxygen for leak testing or operating
refrigerant compressors. Pressurized mixtures of air or gases containing
oxygen can lead to an explosion.
GENERAL
NOTE: In some cases, noise in the living area has been traced to gas pulsations from improper installation of equipment.
- Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer.
- Ensure that vapor and liquid tube diameters are appropriate for unit capacity.
- Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
- Leave some slack between structure and unit to absorb vibration.
- When passing refrigerant tubes through the wall, seal the opening with RTV or other pliable silicon-based caulk (see Fig. 1).
- Avoid direct tubing contact with water pipes, ductwork, floor joists, wall studs, floors, and walls.
- Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing (see Fig. 1).
- Ensure that tubing insulation is pliable and completely surrounds the vapor tube.
- When necessary, use hanger straps that are 1 in. (25.4 mm) wide and conform to the shape of tubing insulation (see Fig. 1).
- Isolate hanger straps from insulation by using metal sleeves bent to conform to the shape of insulation.
NOTE: Avoid contact between tubing and structure
Fig. 1 — Piping Installation
For proper unit operation, check refrigerant charge using the charging
information located on the control box cover and/or in the Check Charge
section of this instruction.
IMPORTANT: Maximum liquid–line size is 3/8–in. OD for all residential
applications including long line. Refer to Residential Piping and Longline
Guideline for further information.
IMPORTANT: Always install the factory–supplied liquid–line filter drier.
If replacing the filter drier, refer to Product Data Digest for an appropriate
part number. Obtain replacement filter driers from your distributor or branch.
INSTALLATION
IMPORTANT: Effective January 1, 2015, all split systems and packaged air conditioners must be installed pursuant to applicable regional efficiency standards issued by the Department of Energy.
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate
protective clothing and gloves when handling parts.
Check Equipment and Job Site
UNPACK UNIT
Move to the final location. Remove carton taking care not to damage the unit.
Inspect Equipment
File claim with shipping company prior to installation if the shipment is
damaged or incomplete. Locate unit rating plate on unit corner panel. It
contains information needed to properly install the unit. Check rating plate
to be sure unit matches job specifications.
Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit to be attached to the pad, tie-
down bolts should be used and fastened through knockouts provided in the unit
base pan. Refer to the unit mounting pattern in Fig. 2 to determine base pan
size and knockout hole location. For hurricane tie-downs, contact the local
distributor for details and PE (Professional Engineer) certification, if
required by local authorities.
On rooftop applications, mount on a level platform or frame. Place unit above
a load-bearing wall and isolate unit and tubing set from the structure.
Arrange supporting members to adequately support the unit and minimize
transmission of vibration to the building. Consult local codes governing
rooftop applications. Roof-mounted units exposed to winds may require wind
baffles. Consult the Application Guideline and Service Manual -Residential
Split System Air Conditioners and Heat Pumps for wind baffle construction.
NOTE: Unit must be level to within ±2 (±3/8 in./ft,.±9.5 mm/m) per
compressor manufacturer specifications.
Clearance Requirements
When installing, allow sufficient space for airflow clearance, wiring,
refrigerant piping, and service. Allow 24 in. (609.6 mm) clearance to service
end of unit and 48 in. (1219.2 mm) (above unit. For proper airflow, a 6–in.
(152.4 mm) clearance on 1 side of the unit and 12–in. (304.8 mm) on all
remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm)
between units or 18 in. (457.2 mm) if no overhang within 12 ft. (3.66 m)
Position so water, snow, or ice from roof or eaves cannot fall directly on the
unit.
NOTE: 18” (457.2 mm) clearance option described above is approved for
outdoor units with wire grille coil guard only. Units with louver panels
require 24” (609.6 mm) between units.
On rooftop applications, locate a unit at least 6 in. (152.4 mm) above roof
surface.
Operating Ambient
The minimum outdoor operating ambient in a cooling mode without accessory is
55_F (12.78_C). The maximum outdoor operating ambient in cooling mode is 125_F
(51.7_C) for non–13 SEER models and 115_F (46.11_C) for 13 SEER models.
Make Piping Connections
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final
unit disposal. Use all service ports and open all flow–control devices,
including solenoid valves. Federal regulations require that you do not vent
refrigerant into the atmosphere. Recover during system repair or final unit
disposal.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
If ANY refrigerant tubing is buried, provide a 6–in (152.4 mm). vertical rise
at service valve. Refrigerant tubing lengths up to 36–in (914.4 mm). may be
buried without further special consideration. Do not bury lines more than
36–in. (914.4 mm).
UNIT BASE PAN
Dimension in. (mm)| TIEDOWN KNOCKOUT LOCATIONS in. (mm)
---|---
A| B| C
23 —1/2 X 23 —1/2 (596.9 X 596.9)| 7 —13/16 (198.4)| 4–7/16 (112.7)| 18–1/16
(458.8)
26 X 26 (660.4 X 660.4)| 9–1/8 (231.8)| 4–7/16 (112.7)| 21–1/4 (539.8)
31–1/2 X 31–1/2 (800.1 X 800.1)| 9–1/8 (231.8)| 6–9/16 (166.7)| 24–11/16
(627.1)
35 X 35 (889 X 889)| 9–1/8 (231.8)| 6–9/16 (166.7)| 28–7/16 (722.3)
Fig. 2 — Tiedown Knockout Locations A05177
Outdoor units may be connected to indoor section using accessory tubing package or field–supplied refrigerant grade tubing of correct size and condition. Rated tubing diameters shown in Table 1 are recommended up to 80 ft. (24.38 m). See Product Data for acceptable alternate vapor diameters and associated capacity losses. For tubing requirements beyond 80 ft. (24.38 m), substantial capacity and performance losses can occur. Following the recommendations in the Longline Guideline will reduce these losses. Refer to Table 1 for field tubing diameters. Refer to Table 6 for accessory requirements.
There are no buried–line applications greater than 36–in. (914.4 mm) allowed.
If refrigerant tubes or indoor coils are exposed to the atmosphere, they must
be evacuated to 500 microns to eliminate contamination and moisture in the
system.
Outdoor Unit Connected to Factory Approved Indoor Unit
The outdoor unit contains correct system refrigerant charge for operation with
factory approved AHRI rated indoor unit when connected by 15 ft. (4.57 m) of
field-supplied or factory–accessory tubing, and factory supplied filter drier.
Check refrigerant charge for maximum efficiency.
Refrigerant Tubing Connection Outdoor
Connect vapor and liquid tubes to fittings on vapor and liquid service valves
(see Table 1). Use refrigerant grade tubing
Sweat Connection
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Service valves must be wrapped in a heat–sinking material such as a wet cloth
while brazing.
Use refrigeration-grade tubing. Service valves are closed from the factory and ready for brazing. After wrapping the service valve with a wet cloth, braze sweat connections using industry-accepted methods and materials. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.
Table 1 – Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)
UNIT SIZE
| LIQUID| **RATED VAPOR*
---|---|---
Connection & Max. tube diameter| Connection Diameter|
Tube Diameter**
CA13NA, CA14NA, CA15NA, CA16NA, CA16NW
18, 24| 3/8| 3/4| 3/4
30| 3/8| 3/4| 3/4
36| 3/8| 7/8| 7/8
42, 48| 3/8| 7/8| 7/8
60| 3/8| 7/8| 1 —1/8
CA16NA Models Only
37, 49| 3/8| 7/8| 7/8
61| 3/8| 7/8| 1 —1/8
CA16NW Models Only
43| 3/8| 7/8| 7/8
54, 61| 3/8| 7/8| 1 —1/8
-
Units are rated with 25 ft. (7.6 m) of lineset. See Product Datasheet for performance data when using different size and length line sets.
Notes:- Do not apply capillary tube to these units.
- For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length), refer to the Residential Piping and Longline Guide line— Air Conditioners and Heat Pumps using Puron refrigerant.
- For alternate liquid line options on 18—42 size units, see Product Data or Residential Piping and Application Guideline
Install Liquid–Line Filter Drier Indoor
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
- Installation of filter drier in liquid line is required.
- Filter drier must be wrapped in a heat–sinking material such as a wet cloth while brazing.
Refer to Fig. 3 and install filter drier as follows:
- Braze 5–in. liquid tube to the indoor coil.
- Wrap filter drier with a damp cloth.
- Braze filter drier to above 5–in. (127 mm) liquid tube. Flow arrow must point towards the indoor coil.
- Connect and braze the liquid refrigerant tube to the filter drier.
Fig. 3 — Liquid Line Filter Drier
Evacuate Refrigerant Tubing and Indoor Coil
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated ystem is free of air and liquid water. A tight dry system will hold a vacuum of 1000 microns after approximately 7 minutes. See Fig. 4.
Fig. 4 — Deep Vacuum Graph A95424
Final Tubing Check
IMPORTANT: Check to be certain factory tubing on both indoor and outdoor
units has not shifted during shipment. Ensure tubes are not rubbing against
each other or any sheet metal or wires. Pay close attention to feeder tubes,
making sure wire ties on feeder tubes are secure and tight.
Installing with Indoor
Piston Outdoor Unit Connected to Factory Approved Indoor Unit
Check piston size shipped with the indoor unit to see if it matches the
required indoor piston size. If it does not match, replace the indoor piston
with the correct piston size. Refer to Product Data for piston size.
NOTE: Correct pistons are shipped with select outdoor units in the
accessory bag and are only for use in certain qualified and approved fan
coils, i.e. FB4C. (See Product Data for a list of approved fan coils that use
accessory pistons.)
The piston included with the FFMANP and FPMAN fan coils are unique to those
products and CANNOT be replaced with the piston shipped with the outdoor unit.
Refer to the AHRI Directory to check if a certain combination can use a piston
or requires an accessory TXV.
When changing the indoor pistons, use a backup wrench. Hand tighten hex nut,
then tighten with wrench 1/2 turn. Do not exceed 30 ft−lbs. The indoor piston
contains a Teflon ring (or seal) which is used to seat against the inside of
the distributor body and must be installed properly to ensure proper seating.
See Fig 5.
Fig. 5 — Indoor (Cooling) Piston
Units with Cooling Mode TXV
Units installed with cooling mode TXV require charging by the subcooling
method.
- Operate unit a minimum of 15 minutes before checking charge.
- Measure liquid service valve pressure by attaching an accurate gauge to the service port.
- Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to the liquid line near the outdoor coil.
- Refer to unit rating plate for required subcooling temperature.
- Refer to Table 2 — Rating Plate (required) Subcooling Temperature. Find the point where the required subcooling temperature intersects measured liquid service valve pressure.
- To obtain the required subcooling temperature at specific liquid line pressure, add refrigerant if liquid line temperature is higher than indicated or reclaim refrigerant if the temperature is lower. Allow a tolerance of ±3_F(±1.7_C).
NOTE: If conditions are not favorable see Check Charge instructions on page 8.
Units with Indoor Piston
Units installed with indoor pistons require charging by the superheat method.
The following procedure is valid when indoor airflow is within± 21 percent of
its rated CFM.
- Operate unit a minimum of 15 minutes before checking charge.
- Measure suction pressure by attaching an accurate gauge to the suction valve service port.
- Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to the suction line at the service valve.
- Measure outdoor air dry–bulb temperature with a thermometer.
- Measure indoor air (entering indoor coil) wet–bulb temperature with a sling psychrometer.
- RefertoTable3–Superheat Charging — AC Only.Find outdoor temperature and evaporator entering air wet–bulb temperature. At this intersection, note superheat. Where a dash (—-) appears on the table, do not attempt to charge system under these conditions, or refrigerant slugging may occur. The charge must be weighed in, adding or removing 0.6 oz/ft of 3/8 liquid line above or below 15 feet (4.6m) respectively.
- Refer to Table 4 — Required Suction–Line Temperature. Find superheat temperature (from #6 above) and suction pressure. At this intersection, note suction line temperature.
- If the unit has a higher suction line temperature than charted temperature, add refrigerant until the charted temperature is reached.
- If the unit has a lower suction line temperature than charted temperature, reclaim the refrigerant until the charted temperature is reached.
- When adding refrigerant, charge in liquid form into suction service port using a flow–restricting device.
- If outdoor air temperature or pressure at suction valve changes, charge to new suction line temperature indicated on the chart.
- Optimum performance will be achieved when the operating charge produces 6_F suction superheat at suction service valve with 95_F(35_C) outdoor ambient and 0_F(27_C) dry-bulb (67_F/19_C) wet bulb) indoor temperature (DOE “A” test conditions) at rated airflow.
Table 2 – Rating Plate (required) Subcooling Temperatures
Measure Liquid Pressure (PSIG)| R– 410A Required Liquid Line
Temperature _F (_C)
---|---
ºF| (ºC)| ºF| (ºC)| ºF| (ºC)| ºF|
(ºC)| ºF| (ºC)| ºF| (ºC)
6| 3| 8| 4| 10| 6| 12| 7| 14|
8| 16| 9
251| 78| 26| 76| 24| 74| 23| 72| 22| 70| 21| 68| 20
259| 80| 27| 78| 26| 76| 24| 74| 23| 72| 22| 70| 21
266| 82| 28| 80| 27| 78| 26| 76| 24| 74| 23| 72| 22
274| 84| 29| 82| 28| 80| 27| 78| 26| 76| 24| 74| 23
283| 86| 30| 84| 29| 82| 28| 80| 27| 78| 26| 76| 24
291| 88| 31| 86| 30| 84| 29| 82| 28| 80| 27| 78| 26
299| 90| 32| 88| 31| 86| 30| 84| 29| 82| 28| 80| 27
308| 92| 33| 90| 32| 88| 31| 86| 30| 84| 29| 82| 28
317| 94| 34| 92| 33| 90| 32| 88| 31| 86| 30| 84| 29
326| 96| 36| 94| 34| 92| 33| 90| 32| 88| 31| 86| 30
335| 98| 37| 96| 36| 94| 34| 92| 33| 90| 32| 88| 31
345| 100| 38| 98| 37| 96| 36| 94| 34| 92| 33| 90| 32
364| 104| 40| 102| 39| 100| 38| 98| 37| 96| 36| 94| 34
374| 106| 41| 104| 40| 102| 39| 100| 38| 98| 37| 96| 36
384| 108| 42| 106| 41| 104| 40| 102| 39| 100| 38| 98| 37
395| 110| 43| 108| 42| 106| 41| 104| 40| 102| 39| 100| 38
406| 112| 44| 110| 43| 108| 42| 106| 41| 104| 40| 102| 39
416| 114| 46| 112| 44| 110| 43| 108| 42| 106| 41| 104| 40
427| 116| 47| 114| 46| 112| 44| 110| 43| 108| 42| 106| 41
439| 118| 48| 116| 47| 114| 46| 112| 44| 110| 43| 108| 42
450| 120| 49| 118| 48| 116| 47| 114| 46| 112| 44| 110| 43
462| 122| 50| 120| 49| 118| 48| 116| 47| 114| 46| 112| 44
474| 124| 51| 122| 50| 120| 49| 118| 48| 116| 47| 114| 46
Table 3 – Superheat Charging — AC Only
OUTDOOR TEMP ( F)| EVAPORATOR ENTERING AIR TEMPERATURE (
F WB)
---|---
50| 52| 54| 56| 58| 60| 62| 64|
67| 68| 70| 72| 74| 76
55| 9| 12| 14| 17| 20| 23| 26| 29| 32| 35| 37| 40| 42| 45
60| 7| 10| 12| 15| 18| 21| 24| 27| 30| 33| 35| 38| 40| 43
65| —| 6| 10| 13| 16| 19| 21| 24| 27| 30| 33| 36| 38| 41
70| —| —| 7| 10| 13| 16| 19| 21| 24| 27| 30| 33| 36| 39
75| —| —| —| 6| 9| 12| 15| 18| 21| 24| 28| 31| 34| 37
80| —| —| —| —| 5| 8| 12| 15| 18| 21| 25| 28| 31| 35
85| —| —| —| —| —| —| 8| 11| 15| 19| 22| 26| 30| 33
90| —| —| —| —| —| —| 5| 9| 13| 16| 20| 24| 27| 31
95| —| —| —| —| —| —| —| 6| 6| 14| 18| 22| 25| 29
100| —| —| —| —| —| —| —| —| 8| 12| 15| 20| 23| 27
105| —| —| —| —| —| —| —| —| 5| 9| 13| 17| 22| 26
110| —| —| —| —| —| —| —| —| —| 6| 11| 15| 20| 25
115| —| —| —| —| —| —| —| —| —| —| 8| 14| 18| 23
*Optimum performance point, 95 º F(35 º C) outdoor ambient and (80 º F/27 º C dry bulb), (67 º F/19 º C wet bulb) indoor conditions. (DOE A Test Conditions)
Where a dash (— — ) appears do not attempt to charge the system under these
conditions or refrigerant slugging may occur. The charge must be weighed in.
Note: Superheat º F is at low—side service port, Allow a tolerance
of ±3 º F(±1.7 º C)
Note: Indoor dry bulb between 70 º Fand80 º F(21 º Cand27_
º C)
Table 4 – Required Suction–Line Temperature
SUPERHEAT TEMP ( _ F)
| SUCTION PRESSURE AT SERVICE PORT (PSIG)
---|---
107.8| 112.2| 116.8| 121.2| 126| 130.8|
138.8| 140.8| 145.8
0| 35| 37| 39| 41| 43| 45| 47| 49| 51
2| 37| 39| 41| 43| 45| 47| 49| 51| 53
4| 39| 41| 43| 45| 47| 49| 51| 53| 55
6| 41| 43| 45| 47| 49| 51| 53| 55| 57
8| 43| 45| 47| 49| 51| 53| 55| 57| 59
10| 45| 47| 49| 51| 53| 55| 57| 59| 61
12| 47| 49| 51| 53| 55| 57| 59| 61| 63
14| 49| 51| 53| 55| 57| 59| 61| 63| 65
16| 51| 53| 55| 57| 59| 61| 63| 65| 67
18| 53| 55| 57| 59| 61| 63| 65| 67| 69
20| 55| 57| 59| 61| 63| 65| 67| 69| 71
22| 57| 59| 61| 63| 65| 67| 69| 71| 73
24| 59| 61| 63| 65| 67| 69| 71| 73| 75
26| 61| 63| 65| 67| 69| 71| 73| 75| 77
28| 63| 65| 67| 69| 71| 73| 75| 77| 79
30| 65| 67| 69| 71| 73| 75| 77| 79| 81
32| 67| 69| 71| 73| 75| 77| 79| 81| 83
34| 69| 71| 73| 75| 77| 79| 81| 83| 85
36| 71| 73| 75| 77| 79| 81| 83| 85| 87
38| 73| 75| 77| 79| 81| 83| 85| 87| 89
40| 75| 77| 79| 81| 83| 85| 87| 89| 91
Make Electrical Connections
Be sure field wiring complies with local and national fire, safety, and
electrical codes, and voltage to the system is within limits shown on the unit
rating plate. Contact local power company for correction of improper voltage.
See unit rating plate for recommended circuit protection device.
NOTE: Operation of unit on improper line voltage constitutes abuse and
could affect unit reliability. See unit rating plate. Do not install the unit
in a system where voltage may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch circuit disconnect of adequate size per NEC to
handle unit starting current. Locate disconnect within sight from and readily
accessible from the unit, per Section 440–14 of NEC.
Route Ground and Power Wires
Remove access panel to gain access to unit wiring. Extend wires from
disconnect through power wiring hole provided and into the unit control box.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have uninterrupted or unbroken ground to minimize
personal injury if an electrical fault should occur. The ground may consist of
electrical wire or metal conduit when installed in accordance with existing
electrical codes.
Connect Ground and Power Wires
Connect the ground wire to the ground connection in the control box for
safety. Connect power wiring to contactor as shown in Fig. 6.
Fig. 6 — Line Connections
Connect Control Wiring
Route 24–v control wires through control wiring grommet and connect leads to
control wiring (See Fig. 8). Refer to Installation Instructions packaged with
thermostat. Use No. 18 AWG color-coded, insulated (35_C minimum) wire. If the
thermostat is located more than 100 ft. (30.48 m) from the unit, as measured
along the control voltage wires, use No. 16 AWG color-coded wire to avoid
excessive voltage drop. All wiring must be NEC Class 2 and must be separated
from incoming power leads.
Use furnace transformer, fan coil transformer, or accessory transformer for
control power, 24v/40va minimum.
NOTE: The use of available 24v accessories may exceed the minimum 40va
power requirement. Determine total transformer loading and increase the
transformer capacity or split the load with an accessory transformer as
required.
Final Wiring Check
IMPORTANT : Check factory wiring and field wire connections to ensure
terminations are secured properly. Check wire routing to ensure wires are not
in contact with tubing, sheet metal, etc.
CompressorCrankcaseHeater
When equipped with a crankcase heater, furnish power to the heater a minimum
of 24 hr before starting the unit. To furnish power to heater only, set
thermostat to OFF and close electrical disconnect to the outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than 80 ft.
(24.38 m). Refer to the Residential Piping and Longline Guideline and Service
Manual Longline Section– Residential Split–System Air Conditioners and Heat
Pumps.
Install Electrical Accessories
Refer to the individual instructions packaged with kits or accessories when
installing.
Start-Up
CAUTION
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this caution may result in personal injury, equipment damage
or improper operation.
- Do not overcharge the system with refrigerant.
- Do not operate the unit in a vacuum or at negative pressure.
- Compressor dome temperatures may be hot.
CAUTION
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when handling refrigerant
and observe the following:
Front seating service valves are equipped with Schrader valves.
Follow these steps to properly start-up system:
- After the system is evacuated, fully open liquid and vapor service valves.
- Unit is shipped with valve stem(s) front seated (closed) and caps installed. Replace stem caps after the system is opened to refrigerant flow. Replace caps finger–tight and tighten with wrench an additional 1/12 turn.
- Close electrical disconnects to energize the system.
- Set room thermostat at the desired temperature. Be sure the setpoint is below indoor ambient temperature.
- Set room thermostat to COOL and fan control to ON or AUTO mode, as desired. Operate the unit for 15 minutes. Check system refrigerant charge.
3–Phase Monitor
In 3–phase units a small circuit board is factory installed to monoline
voltage. A small led will flash if a phase problem exists. See code
descriptions on the monitor. If LED is flashing, disconnect power to the unit
and interchange 2 fields–wiring leads on the unit contactor.
Fig. 7 — 3–Phase Monitor Control (Applies to 3–Phase Units Only)
Table 5 – Three–Phase Monitor LED Indicators
LED
|
STATUS
---|---
OFF| No call for compressor operation
FLASHING| Reversed-phase
ON| Normal
**CAUTION**
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Ensure compressor rotation is correct.
S 3 – phase scroll compressors are rotation sensitive.
S A flash LED on phase monitor indicates reverse rotation. (See Table 5)
This will not allow the contractor to be energized.
S Disconnect power to unit and interchange 2 field – wiring leads on the unit contactor.
Sequence of Operation
Turn on power to indoor and outdoor units. The transformer is energized.
On a call for cooling, the thermostat makes circuits R–Y and R–G. Circuit R–Y
energizes contactor, starting outdoor fan motor and compressor circuit. R–G
energizes indoor unit blower relay, starting indoor blower motor on high
speed.
When the thermostat is satisfied, its contacts open, de-energizing contactor
and blower relay. Compressor and motors stop. If the indoor unit is equipped
with a time–delay relay circuit, the indoor blower will run an additional 90
seconds to increase system efficiency.
Check Charge
The factory charge amount and desired subcooling are shown on the unit rating
plate. The charging method is shown on the information plate inside the unit.
To properly check or adjust charge, conditions must be favorable for
subcooling charging. Favorable conditions exist when the outdoor temperature
is between 70_F and 100_F (21.11_C and 37.78_C), and the indoor temperature is
between 70_F and 80_F (21.11_C and 26.67_C). Follow the procedure below:
Adjust charge by adding or removing 0.6 oz/ft of 3/8 liquid line above or
below 15ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow the
system to operate in cooling mode at least 15 minutes. If conditions are
favorable, check system charge by subcooling method. If any adjustment is
necessary, adjust the charge slowly and allow the system to operate for 15
minutes to stabilize before declaring a properly charged system.
If the indoor temperature is above 80_F (26.67_C), and the outdoor temperature is in the favorable range, adjust the system charge by weight based on line length and allow the indoor temperature to drop to 80_F (26.67_C) before attempting to check system charge by subcooling method as described above.
If the indoor temperature is below 70_F (21.11_C), or the outdoor temperature
is not in the favorable range, adjust the charge for line set length above or
below 15ft (4.57 m) only. The charge level should then be appropriate for the
system to achieve rated capacity. The charge level could then be checked at
another time when both indoor and outdoor temperatures are in a more favorable
range.
NOTE : If the line length is beyond 80 ft (24.38 m) or greater than 35 ft
(10.7 m) vertical separation, See Long Line Guideline for special charging
requirements.
Final Checks
IMPORTANT: Before leaving job, be sure to do the following:
- Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub–through or wire pinching.
- Ensure that all wiring and tubing are secure in the unit before adding panels and covers. Securely fasten all panels and covers.
- Tighten service valve stem caps to 1/12–turn past finger tight.
- Leave the Owner’s Manual with the owner. Explain system operation and periodic maintenance requirements outlined in the manual.
- Fill out the Dealer Installation Checklist and place it in the customer file.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equipment failure,
periodic maintenance must be performed on this equipment.
Frequency of maintenance may vary depending upon geographic areas, such as
coastal applications. See Owner’s Manual for information.
Table 6 – Accessory Usage
ACCESSORY| REQUIRED FOR LOW– AMBIENT COOLING APPLICATIONS
(Below 55 ° F/12.8_C)
| REQUIRED FOR LONG LINE **APPLICATIONS*| REQUIRED FOR SEACOAST APPLICATIONS**
(Within 2 miles/3.22 km)
---|---|---|---
Ball Bearing Fan Motor| Yes{| No| No
Compressor Start Assist Capacitor and Relay| Yes| Yes| No
Crankcase Heater| Yes| Yes| No
Evaporator Freeze Thermostat| Yes| No| No
Hard Shut — Off TXV| Yes| Yes| Yes
Liquid Line Solenoid Valve| No| No| No
Motor Master or Low– ambient Pressure Switch| Yes]| No| No
Support Feet| Recommended| No| Recommended
Winter Start Control| Yes| No| No
- For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 35 ft. (10.7 m) vertical differential, refer to Residential Piping and Longline Guideline.
Additional requirement for Low—Ambient Controller (full modulation feature) MotorMasterr Control.
If the unit equipped with an ECM OD motor, both motor and fan need to be replaced per unit accessory guide to work properly. The unit will not meet AHRI rated efficiency once motor and fan are replaced to use this accessory. Fig. 8 — Generic Wiring Diagrams (See Thermostat Installation Instruction for specific unit combinations)
PURON (R–410A) REFRIGERANT QUICK REFERENCE GUIDE
-
Puron refrigerant operates at 50–70 percent higher pressures than R–22. Be sure that servicing equipment and replacement
components are designed to operate with Puron refrigerant -
Puron refrigerant cylinders are rose-colored.
-
Recovery cylinder service pressure rating must be 400 PSIG, DOT 4BA400, or DOT BW400.
-
Puron refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating
-
Manifold sets should be 700 psig high side and 180 PSIG low side with 550 psig low–side retard.
-
Use hoses with a 700 psig service pressure rating.
-
Leak detectors should be designed to detect HFC refrigerant.
-
Puron refrigerant, as with other HFCs, is only compatible with POE oils.
-
Vacuum pumps will not remove moisture from oil.
-
Do not use liquid–line filter driers with rated working pressures less than 600 psig.
-
Do not leave Puron suction line filter driers in line longer than 72 hours.
-
Do not install a suction–line filter drier in the liquid line.
-
POE oils absorb moisture rapidly. Do not expose oil to the atmosphere.
-
POE oils may cause damage to certain plastics and roofing materials
-
Wrap all filter driers and service valves with a wet cloth when brazing.
-
A factory-approved liquid–line filter drier is required on every unit.
-
Do NOT use an R–22 TXV.
-
Never open the system to the atmosphere while it is under a vacuum.
-
When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter driers.
Evacuate to 500 microns prior to recharging. -
Do not vent Puron refrigerant into the atmosphere.
-
Do not use capillary tube coils.
-
Observe all warnings, cautions, and bold text.
Copyright 2017 Carrier Corp.
S 7310 W. Morris St.
S Indianapolis, IN 46231
Edition Date: 03/17
Catalog No: CA13NA—16NW—07SI
The manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations.
Replaces: CA13NA—16NW—06SI
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>