Carrier Split-System Air Conditioners Instruction Manual

June 6, 2024
Carrier

CA13NA 018–060
CA14NA 018–060
CA15NA 018–060
*CA16N 018–061
SPLIT–SYSTEM AIR CONDITIONERS
WITH R–410A REFRIGERANT**

Installation Instructions

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance, or use can cause an explosion, fire, electrical shock, or other conditions which may cause death, personal injury,  or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in the literature and attached to the unit. Consult local building codes and current editions of the National  Electrical Code (NEC) NFPA 70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.

Recognize safety information. This is the safety–alert symbol **When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.  Understand these signal words; DANGER, WARNING , and CAUTION. These words are used with the safety–alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE** is used to highlight suggestions that will result in enhanced installation,  reliability, or operation.

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing the system, the main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lockout and tag switch with a suitable warning label.
WARNING

| EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.

GENERAL

NOTE: In some cases, noise in the living area has been traced to gas pulsations from improper installation of equipment.

  1. Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer.
  2. Ensure that vapor and liquid tube diameters are appropriate for unit capacity.
  3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
  4. Leave some slack between structure and unit to absorb vibration.
  5. When passing refrigerant tubes through the wall, seal the opening with RTV or other pliable silicon-based caulk (see Fig. 1).
  6. Avoid direct tubing contact with water pipes, ductwork, floor joists, wall studs, floors, and walls.
  7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing (see Fig. 1).
  8. Ensure that tubing insulation is pliable and completely surrounds the vapor tube.
  9. When necessary, use hanger straps that are 1 in. (25.4 mm) wide and conform to the shape of tubing insulation (see Fig. 1).
  10. Isolate hanger straps from insulation by using metal sleeves bent to conform to the shape of insulation.

NOTE: Avoid contact between tubing and structure
Fig. 1 — Piping Installation

For proper unit operation, check refrigerant charge using the charging information located on the control box cover and/or in the Check Charge section of this instruction.
IMPORTANT: Maximum liquid–line size is 3/8–in. OD for all residential applications including long line. Refer to Residential Piping and Longline Guideline for further information.
IMPORTANT: Always install the factory–supplied liquid–line filter drier. If replacing the filter drier, refer to Product Data Digest for an appropriate part number. Obtain replacement filter driers from your distributor or branch.

INSTALLATION

IMPORTANT: Effective January 1, 2015, all split systems and packaged air conditioners must be installed pursuant to applicable regional efficiency standards issued by the  Department of Energy.

CAUTION

CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.

Check Equipment and Job Site
UNPACK UNIT
Move to the final location. Remove carton taking care not to damage the unit.
Inspect Equipment
File claim with shipping company prior to installation if the shipment is damaged or incomplete. Locate unit rating plate on unit corner panel. It contains information needed to properly install the unit. Check rating plate to be sure unit matches job specifications.
Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit to be attached to the pad, tie- down bolts should be used and fastened through knockouts provided in the unit base pan. Refer to the unit mounting pattern in Fig. 2 to determine base pan size and knockout hole location. For hurricane tie-downs, contact the local distributor for details and PE (Professional Engineer)  certification, if required by local authorities.
On rooftop applications, mount on a level platform or frame. Place unit above a load-bearing wall and isolate unit and tubing set from the structure. Arrange supporting members to adequately support the unit and minimize transmission of vibration to the building. Consult local codes governing rooftop applications. Roof-mounted units exposed to winds may require wind baffles. Consult the Application Guideline and Service Manual -Residential Split System Air Conditioners and Heat Pumps for wind baffle construction.
NOTE: Unit must be level to within ±2 (±3/8 in./ft,.±9.5 mm/m) per compressor manufacturer specifications.
Clearance Requirements
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm) clearance to service end of unit and 48 in. (1219.2  mm) (above unit. For proper airflow, a 6–in. (152.4 mm) clearance on 1 side of the unit and 12–in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24  in. (609.6 mm) between units or 18 in. (457.2 mm) if no overhang within 12 ft. (3.66 m) Position so water, snow, or ice from roof or eaves cannot fall directly on the unit.
NOTE: 18” (457.2 mm) clearance option described above is approved for outdoor units with wire grille coil guard only. Units with louver panels require 24” (609.6  mm) between units.
On rooftop applications, locate a unit at least 6 in. (152.4 mm) above roof surface.
Operating Ambient
The minimum outdoor operating ambient in a cooling mode without accessory is 55_F (12.78_C). The maximum outdoor operating ambient in cooling mode is 125_F (51.7_C)  for non–13 SEER models and 115_F (46.11_C) for 13 SEER models.
Make Piping Connections

WARNING

PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all flow–control devices, including solenoid valves. Federal regulations require that you do not vent refrigerant into the atmosphere. Recover during system repair or final unit disposal.
CAUTION

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
If ANY refrigerant tubing is buried, provide a 6–in (152.4 mm). vertical rise at service valve. Refrigerant tubing lengths up to 36–in (914.4 mm). may be buried without further special consideration. Do not bury lines more than 36–in. (914.4 mm).

UNIT BASE PAN
Dimension in. (mm)| TIEDOWN KNOCKOUT LOCATIONS in. (mm)
---|---
A| B| C
23 —1/2 X 23 —1/2 (596.9 X 596.9)| 7 —13/16 (198.4)| 4–7/16 (112.7)| 18–1/16 (458.8)
26 X 26 (660.4 X 660.4)| 9–1/8 (231.8)| 4–7/16 (112.7)| 21–1/4 (539.8)
31–1/2 X 31–1/2 (800.1 X 800.1)| 9–1/8 (231.8)| 6–9/16 (166.7)| 24–11/16 (627.1)
35 X 35 (889 X 889)| 9–1/8 (231.8)| 6–9/16 (166.7)| 28–7/16 (722.3)

Fig. 2 — Tiedown Knockout Locations A05177

Outdoor units may be connected to indoor section using accessory tubing package or field–supplied refrigerant grade tubing of correct size and condition. Rated tubing diameters shown in Table 1 are recommended up to 80 ft. (24.38 m). See Product Data for acceptable alternate vapor diameters and associated capacity losses. For tubing requirements beyond 80 ft. (24.38 m), substantial capacity and performance losses can occur. Following the recommendations in the Longline Guideline will reduce these losses.  Refer to Table 1 for field tubing diameters. Refer to Table 6 for accessory requirements.

There are no buried–line applications greater than 36–in. (914.4 mm) allowed.
If refrigerant tubes or indoor coils are exposed to the atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.

Outdoor Unit Connected to Factory Approved Indoor Unit
The outdoor unit contains correct system refrigerant charge for operation with factory approved AHRI rated indoor unit when connected by 15 ft. (4.57 m) of field-supplied or factory–accessory tubing, and factory supplied filter drier. Check refrigerant charge for maximum efficiency.
Refrigerant Tubing Connection Outdoor
Connect vapor and liquid tubes to fittings on vapor and liquid service valves (see Table 1). Use refrigerant grade tubing
Sweat Connection

CAUTION

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Service valves must be wrapped in a heat–sinking material such as a wet cloth while brazing.

Use refrigeration-grade tubing. Service valves are closed from the factory and ready for brazing. After wrapping the service valve with a wet cloth, braze sweat connections using industry-accepted methods and materials. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.

Table 1 – Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)


UNIT SIZE

| LIQUID| **RATED VAPOR*
---|---|---
Connection & Max. tube diameter| Connection Diameter| Tube Diameter**

CA13NA, CA14NA, CA15NA, CA16NA, CA16NW

18, 24| 3/8| 3/4| 3/4
30| 3/8| 3/4| 3/4
36| 3/8| 7/8| 7/8
42, 48| 3/8| 7/8| 7/8
60| 3/8| 7/8| 1 —1/8

CA16NA Models Only

37, 49| 3/8| 7/8| 7/8
61| 3/8| 7/8| 1 —1/8

CA16NW Models Only

43| 3/8| 7/8| 7/8
54, 61| 3/8| 7/8| 1 —1/8

  • Units are rated with 25 ft. (7.6 m) of lineset. See Product Datasheet for performance data when using different size and length line sets.
    Notes:

    1. Do not apply capillary tube to these units.
    2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length), refer to the  Residential Piping and Longline Guide line— Air Conditioners and Heat Pumps using Puron refrigerant.
    3. For alternate liquid line options on 18—42 size units, see Product Data or Residential Piping and Application Guideline

Install Liquid–Line Filter Drier Indoor

CAUTION

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.

  1. Installation of filter drier in liquid line is required.
  2. Filter drier must be wrapped in a heat–sinking material such as a wet cloth while brazing.

Refer to Fig. 3 and install filter drier as follows:

  1. Braze 5–in. liquid tube to the indoor coil.
  2. Wrap filter drier with a damp cloth.
  3. Braze filter drier to above 5–in. (127 mm) liquid tube. Flow arrow must point towards the indoor coil.
  4. Connect and braze the liquid refrigerant tube to the filter drier.

Fig. 3 — Liquid Line Filter Drier

Evacuate Refrigerant Tubing and Indoor Coil

CAUTION

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated ystem is free of air and liquid water. A tight dry system will hold a vacuum of 1000 microns after approximately 7  minutes. See Fig. 4.

Fig. 4 — Deep Vacuum Graph A95424

Final Tubing Check
IMPORTANT: Check to be certain factory tubing on both indoor and outdoor units has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal or wires. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
Installing with Indoor
Piston Outdoor Unit Connected to Factory Approved Indoor Unit

Check piston size shipped with the indoor unit to see if it matches the required indoor piston size. If it does not match, replace the indoor piston with the correct piston size. Refer to Product Data for piston size.

NOTE: Correct pistons are shipped with select outdoor units in the accessory bag and are only for use in certain qualified and approved fan coils, i.e. FB4C. (See Product Data  for a list of approved fan coils that use accessory pistons.)
The piston included with the FFMANP and FPMAN fan coils are unique to those products and CANNOT be replaced with the piston shipped with the outdoor unit. Refer to the AHRI Directory to check if a certain combination can use a piston or requires an accessory TXV.
When changing the indoor pistons, use a backup wrench. Hand tighten hex nut, then tighten with wrench 1/2 turn. Do not exceed 30 ft−lbs. The indoor piston contains a Teflon ring (or seal) which is used to seat against the inside of the distributor body and must be installed properly to ensure proper seating. See Fig 5.

Fig. 5 — Indoor (Cooling) Piston

Units with Cooling Mode TXV
Units installed with cooling mode TXV require charging by the subcooling method.

  1. Operate unit a minimum of 15 minutes before checking charge.
  2. Measure liquid service valve pressure by attaching an accurate gauge to the service port.
  3. Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to the liquid line near the outdoor coil.
  4. Refer to unit rating plate for required subcooling temperature.
  5. Refer to Table 2 — Rating Plate (required) Subcooling Temperature. Find the point where the required subcooling temperature intersects measured liquid service valve pressure.
  6. To obtain the required subcooling temperature at specific liquid line pressure, add refrigerant if liquid line temperature is higher than indicated or reclaim refrigerant if the temperature is lower. Allow a tolerance of ±3_F(±1.7_C).

NOTE: If conditions are not favorable see Check Charge instructions on page 8.

Units with Indoor Piston
Units installed with indoor pistons require charging by the superheat method.
The following procedure is valid when indoor airflow is within± 21 percent of its rated CFM.

  1. Operate unit a minimum of 15 minutes before checking charge.
  2. Measure suction pressure by attaching an accurate gauge to the suction valve service port.
  3. Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to the suction line at the service valve.
  4. Measure outdoor air dry–bulb temperature with a thermometer.
  5. Measure indoor air (entering indoor coil) wet–bulb temperature with a sling psychrometer.
  6. RefertoTable3–Superheat Charging — AC Only.Find outdoor temperature and evaporator entering air wet–bulb temperature. At this intersection, note superheat. Where a dash (—-) appears on the table, do not attempt to charge system under these conditions, or refrigerant slugging may occur. The charge must be weighed in, adding or removing  0.6 oz/ft of 3/8 liquid line above or below 15 feet (4.6m) respectively.
  7. Refer to Table 4 — Required Suction–Line Temperature. Find superheat temperature (from #6 above) and suction pressure. At this intersection, note suction line temperature.
  8. If the unit has a higher suction line temperature than charted temperature, add refrigerant until the charted temperature is reached.
  9. If the unit has a lower suction line temperature than charted temperature, reclaim the refrigerant until the charted temperature is reached.
  10. When adding refrigerant, charge in liquid form into suction service port using a flow–restricting device.
  11. If outdoor air temperature or pressure at suction valve changes, charge to new suction line temperature indicated on the chart.
  12. Optimum performance will be achieved when the operating charge produces 6_F suction superheat at suction service valve with 95_F(35_C) outdoor ambient and  0_F(27_C) dry-bulb (67_F/19_C) wet bulb) indoor temperature (DOE “A” test conditions) at rated airflow.

Table 2 – Rating Plate (required) Subcooling Temperatures

Measure Liquid Pressure (PSIG)| R– 410A Required Liquid Line Temperature _F (_C)
---|---
ºF| (ºC)| ºF| (ºC)| ºF| (ºC)| ºF| (ºC)| ºF| (ºC)| ºF| (ºC)
6| 3| 8| 4| 10| 6| 12| 7| 14| 8| 16| 9
251| 78| 26| 76| 24| 74| 23| 72| 22| 70| 21| 68| 20
259| 80| 27| 78| 26| 76| 24| 74| 23| 72| 22| 70| 21
266| 82| 28| 80| 27| 78| 26| 76| 24| 74| 23| 72| 22
274| 84| 29| 82| 28| 80| 27| 78| 26| 76| 24| 74| 23
283| 86| 30| 84| 29| 82| 28| 80| 27| 78| 26| 76| 24
291| 88| 31| 86| 30| 84| 29| 82| 28| 80| 27| 78| 26
299| 90| 32| 88| 31| 86| 30| 84| 29| 82| 28| 80| 27
308| 92| 33| 90| 32| 88| 31| 86| 30| 84| 29| 82| 28
317| 94| 34| 92| 33| 90| 32| 88| 31| 86| 30| 84| 29
326| 96| 36| 94| 34| 92| 33| 90| 32| 88| 31| 86| 30
335| 98| 37| 96| 36| 94| 34| 92| 33| 90| 32| 88| 31
345| 100| 38| 98| 37| 96| 36| 94| 34| 92| 33| 90| 32
364| 104| 40| 102| 39| 100| 38| 98| 37| 96| 36| 94| 34
374| 106| 41| 104| 40| 102| 39| 100| 38| 98| 37| 96| 36
384| 108| 42| 106| 41| 104| 40| 102| 39| 100| 38| 98| 37
395| 110| 43| 108| 42| 106| 41| 104| 40| 102| 39| 100| 38
406| 112| 44| 110| 43| 108| 42| 106| 41| 104| 40| 102| 39
416| 114| 46| 112| 44| 110| 43| 108| 42| 106| 41| 104| 40
427| 116| 47| 114| 46| 112| 44| 110| 43| 108| 42| 106| 41
439| 118| 48| 116| 47| 114| 46| 112| 44| 110| 43| 108| 42
450| 120| 49| 118| 48| 116| 47| 114| 46| 112| 44| 110| 43
462| 122| 50| 120| 49| 118| 48| 116| 47| 114| 46| 112| 44
474| 124| 51| 122| 50| 120| 49| 118| 48| 116| 47| 114| 46

Table 3 – Superheat Charging — AC Only

OUTDOOR TEMP  ( F)| EVAPORATOR ENTERING AIR TEMPERATURE ( F WB)
---|---
50| 52| 54| 56| 58| 60| 62| 64| 67| 68| 70| 72| 74| 76
55| 9| 12| 14| 17| 20| 23| 26| 29| 32| 35| 37| 40| 42| 45
60| 7| 10| 12| 15| 18| 21| 24| 27| 30| 33| 35| 38| 40| 43
65| —| 6| 10| 13| 16| 19| 21| 24| 27| 30| 33| 36| 38| 41
70| —| —| 7| 10| 13| 16| 19| 21| 24| 27| 30| 33| 36| 39
75| —| —| —| 6| 9| 12| 15| 18| 21| 24| 28| 31| 34| 37
80| —| —| —| —| 5| 8| 12| 15| 18| 21| 25| 28| 31| 35
85| —| —| —| —| —| —| 8| 11| 15| 19| 22| 26| 30| 33
90| —| —| —| —| —| —| 5| 9| 13| 16| 20| 24| 27| 31
95| —| —| —| —| —| —| —| 6| 6| 14| 18| 22| 25| 29
100| —| —| —| —| —| —| —| —| 8| 12| 15| 20| 23| 27
105| —| —| —| —| —| —| —| —| 5| 9| 13| 17| 22| 26
110| —| —| —| —| —| —| —| —| —| 6| 11| 15| 20| 25
115| —| —| —| —| —| —| —| —| —| —| 8| 14| 18| 23

*Optimum performance point, 95 º F(35 º C) outdoor ambient and (80 º F/27 º C dry bulb), (67 º F/19 º C wet bulb) indoor conditions. (DOE A Test Conditions)
Where a dash (— — ) appears do not attempt to charge the system under these conditions or refrigerant slugging may occur. The charge must be weighed in.
Note: Superheat º F is at low—side service port, Allow a tolerance of ±3 º F(±1.7 º C)
Note: Indoor dry bulb between 70
º Fand80 º F(21 º Cand27_ º C)

Table 4 – Required Suction–Line Temperature


SUPERHEAT TEMP ( _ F)

| SUCTION PRESSURE AT SERVICE PORT (PSIG)
---|---
107.8| 112.2| 116.8| 121.2| 126| 130.8| 138.8| 140.8| 145.8
0| 35| 37| 39| 41| 43| 45| 47| 49| 51
2| 37| 39| 41| 43| 45| 47| 49| 51| 53
4| 39| 41| 43| 45| 47| 49| 51| 53| 55
6| 41| 43| 45| 47| 49| 51| 53| 55| 57
8| 43| 45| 47| 49| 51| 53| 55| 57| 59
10| 45| 47| 49| 51| 53| 55| 57| 59| 61
12| 47| 49| 51| 53| 55| 57| 59| 61| 63
14| 49| 51| 53| 55| 57| 59| 61| 63| 65
16| 51| 53| 55| 57| 59| 61| 63| 65| 67
18| 53| 55| 57| 59| 61| 63| 65| 67| 69
20| 55| 57| 59| 61| 63| 65| 67| 69| 71
22| 57| 59| 61| 63| 65| 67| 69| 71| 73
24| 59| 61| 63| 65| 67| 69| 71| 73| 75
26| 61| 63| 65| 67| 69| 71| 73| 75| 77
28| 63| 65| 67| 69| 71| 73| 75| 77| 79
30| 65| 67| 69| 71| 73| 75| 77| 79| 81
32| 67| 69| 71| 73| 75| 77| 79| 81| 83
34| 69| 71| 73| 75| 77| 79| 81| 83| 85
36| 71| 73| 75| 77| 79| 81| 83| 85| 87
38| 73| 75| 77| 79| 81| 83| 85| 87| 89
40| 75| 77| 79| 81| 83| 85| 87| 89| 91

Make Electrical Connections

Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to the system is within limits shown on the unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.
NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install the unit in a system where voltage may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from the unit, per  Section 440–14 of NEC.
Route Ground and Power Wires
Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into the unit control box.

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.

Connect Ground and Power Wires
Connect the ground wire to the ground connection in the control box for safety. Connect power wiring to contactor as shown in Fig. 6.

Fig. 6 — Line Connections

Connect Control Wiring
Route 24–v control wires through control wiring grommet and connect leads to control wiring (See Fig. 8). Refer to Installation Instructions packaged with thermostat. Use No.  18 AWG color-coded, insulated (35_C minimum) wire. If the thermostat is located more than 100 ft. (30.48 m) from the unit, as measured along the control voltage wires, use No.  16 AWG color-coded wire to avoid excessive voltage drop. All wiring must be NEC Class 2 and must be separated from incoming power leads.
Use furnace transformer, fan coil transformer, or accessory transformer for control power, 24v/40va minimum.
NOTE: The use of available 24v accessories may exceed the minimum 40va power requirement. Determine total transformer loading and increase the transformer capacity or split the load with an accessory transformer as required.

Final Wiring Check
IMPORTANT : Check factory wiring and field wire connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing,  sheet metal, etc.

CompressorCrankcaseHeater
When equipped with a crankcase heater, furnish power to the heater a minimum of 24 hr before starting the unit. To furnish power to heater only, set thermostat to OFF and close electrical disconnect to the outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than 80 ft. (24.38 m). Refer to the Residential Piping and Longline Guideline and Service Manual Longline Section– Residential Split–System Air Conditioners and Heat Pumps.

Install Electrical Accessories
Refer to the individual instructions packaged with kits or accessories when installing.
Start-Up

CAUTION

UNIT OPERATION AND SAFETY HAZARD
Failure to follow this caution may result in personal injury, equipment damage or improper operation.

  • Do not overcharge the system with refrigerant.
  • Do not operate the unit in a vacuum or at negative pressure.
  • Compressor dome temperatures may be hot.

CAUTION

PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when handling refrigerant and observe the following:
Front seating service valves are equipped with Schrader valves.

Follow these steps to properly start-up system:

  1.  After the system is evacuated, fully open liquid and vapor service valves.
  2.  Unit is shipped with valve stem(s) front seated (closed) and caps installed. Replace stem caps after the system is opened to refrigerant flow. Replace caps finger–tight and tighten with wrench an additional 1/12 turn.
  3. Close electrical disconnects to energize the system.
  4.  Set room thermostat at the desired temperature. Be sure the setpoint is below indoor ambient temperature.
  5. Set room thermostat to COOL and fan control to ON or AUTO mode, as desired. Operate the unit for 15 minutes.  Check system refrigerant charge.

3–Phase Monitor
In 3–phase units a small circuit board is factory installed to monoline voltage. A small led will flash if a phase problem exists. See code descriptions on the monitor. If LED is flashing, disconnect power to the unit and interchange 2 fields–wiring leads on the unit contactor.

Fig. 7 — 3–Phase Monitor Control (Applies to 3–Phase Units Only)
Table 5 – Three–Phase Monitor LED Indicators

LED

|

STATUS

---|---
OFF| No call for compressor operation
FLASHING| Reversed-phase
ON| Normal

**CAUTION**

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Ensure compressor rotation is correct.

S 3 phase scroll compressors are rotation sensitive.

S A flash LED on phase monitor indicates reverse rotation. (See Table 5)

This will not allow the contractor to be energized.

S Disconnect power to unit and interchange 2 field wiring leads on the unit contactor.

Sequence of Operation
Turn on power to indoor and outdoor units. The transformer is energized.
On a call for cooling, the thermostat makes circuits R–Y and R–G. Circuit R–Y energizes contactor, starting outdoor fan motor and compressor circuit. R–G energizes indoor unit blower relay, starting indoor blower motor on high speed.
When the thermostat is satisfied, its contacts open, de-energizing contactor and blower relay. Compressor and motors stop. If the indoor unit is equipped with a time–delay relay circuit, the indoor blower will run an additional 90 seconds to increase system efficiency.

Check Charge
The factory charge amount and desired subcooling are shown on the unit rating plate. The charging method is shown on the information plate inside the unit. To properly check or adjust charge, conditions must be favorable for subcooling charging. Favorable conditions exist when the outdoor temperature is between 70_F and 100_F (21.11_C and 37.78_C), and the indoor temperature is between 70_F and 80_F (21.11_C and 26.67_C). Follow the procedure below:

Adjust charge by adding or removing 0.6 oz/ft of 3/8 liquid line above or below 15ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow the system to operate in cooling mode at least 15 minutes. If conditions are favorable, check system charge by subcooling method. If any adjustment is necessary, adjust the charge slowly and allow the system to operate for 15 minutes to stabilize before declaring a properly charged system.

If the indoor temperature is above 80_F (26.67_C), and the outdoor temperature is in the favorable range, adjust the system charge by weight based on line length and allow the indoor temperature to drop to 80_F (26.67_C) before attempting to check system charge by subcooling method as described above.

If the indoor temperature is below 70_F (21.11_C), or the outdoor temperature is not in the favorable range, adjust the charge for line set length above or below 15ft (4.57 m) only. The charge level should then be appropriate for the system to achieve rated capacity. The charge level could then be checked at another time when both indoor and outdoor temperatures are in a more favorable range.
NOTE : If the line length is beyond 80 ft (24.38 m) or greater than 35 ft (10.7 m) vertical separation, See Long Line Guideline for special charging requirements.

Final Checks
IMPORTANT
: Before leaving job, be sure to do the following:

  1. Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub–through or wire pinching.
  2.  Ensure that all wiring and tubing are secure in the unit before adding panels and covers. Securely fasten all panels and covers.
  3.  Tighten service valve stem caps to 1/12–turn past finger tight.
  4.  Leave the Owner’s Manual with the owner. Explain system operation and periodic maintenance requirements outlined in the manual.
  5. Fill out the Dealer Installation Checklist and place it in the customer file.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible equipment failure, periodic maintenance must be performed on this equipment.
Frequency of maintenance may vary depending upon geographic areas, such as coastal applications. See Owner’s Manual for information.
Table 6 – Accessory Usage

ACCESSORY| REQUIRED FOR LOW– AMBIENT COOLING APPLICATIONS

(Below 55 ° F/12.8_C)

| REQUIRED FOR LONG LINE **APPLICATIONS*| REQUIRED FOR SEACOAST APPLICATIONS**

(Within 2 miles/3.22 km)

---|---|---|---
Ball Bearing Fan Motor| Yes{| No| No
Compressor Start Assist Capacitor and Relay| Yes| Yes| No
Crankcase Heater| Yes| Yes| No
Evaporator Freeze Thermostat| Yes| No| No
Hard Shut Off TXV| Yes| Yes| Yes
Liquid Line Solenoid Valve| No| No| No
Motor Master   or Low– ambient Pressure Switch| Yes]| No| No
Support Feet| Recommended| No| Recommended
Winter Start Control| Yes| No| No

  • For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 35 ft. (10.7 m) vertical differential, refer to Residential Piping and Longline Guideline.
    Additional requirement for Low—Ambient Controller (full modulation feature) MotorMasterr Control.
    If the unit equipped with an ECM OD motor, both motor and fan need to be replaced per unit accessory guide to work properly. The unit will not meet AHRI rated efficiency once motor and fan are replaced to use this accessory. Fig. 8 — Generic Wiring Diagrams (See Thermostat Installation Instruction for specific unit combinations)

PURON (R–410A) REFRIGERANT QUICK REFERENCE GUIDE

  • Puron refrigerant operates at 50–70 percent higher pressures than R–22. Be sure that servicing equipment and replacement
    components are designed to operate with Puron refrigerant

  • Puron refrigerant cylinders are rose-colored.

  •  Recovery cylinder service pressure rating must be 400 PSIG, DOT 4BA400, or DOT BW400.

  •  Puron refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating

  •  Manifold sets should be 700 psig high side and 180 PSIG low side with 550 psig low–side retard.

  • Use hoses with a 700 psig service pressure rating.

  • Leak detectors should be designed to detect HFC refrigerant.

  •  Puron refrigerant, as with other HFCs, is only compatible with POE oils.

  • Vacuum pumps will not remove moisture from oil.

  • Do not use liquid–line filter driers with rated working pressures less than 600 psig.

  •  Do not leave Puron suction line filter driers in line longer than 72 hours.

  •  Do not install a suction–line filter drier in the liquid line.

  •  POE oils absorb moisture rapidly. Do not expose oil to the atmosphere.

  • POE oils may cause damage to certain plastics and roofing materials

  •  Wrap all filter driers and service valves with a wet cloth when brazing.

  •  A factory-approved liquid–line filter drier is required on every unit.

  • Do NOT use an R–22 TXV.

  •  Never open the system to the atmosphere while it is under a vacuum.

  • When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter driers.
    Evacuate to 500 microns prior to recharging.

  • Do not vent Puron refrigerant into the atmosphere.

  • Do not use capillary tube coils.

  • Observe all warnings, cautions, and bold text.

Copyright 2017 Carrier Corp.
S 7310 W. Morris St.
S Indianapolis, IN 46231
Edition Date: 03/17
Catalog No: CA13NA—16NW—07SI
The manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Replaces: CA13NA—16NW—06SI

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals