Technical Specifications

Product type Tri-level control microwave motion sensor
Operating voltage 120~277VAC 50/60Hz
Rated load Capacitive: 400VA@120V; 800VA@220~277V

Resistive: 800W@120V; 1600W@220~277V
Power consumption| < 0.5W
Detection angle| 360°
Detection area (Max.)*| Installation Height : 20m (forklift) 15m (person) Detection Range (Ø) :20m
Detection range| 10% / 50% / 75% / 100%
Hold time| 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time| 0s / 10s / 1min / 5min / 10min / 30min / 1h / + ∞
Stand-by dimming level| 10% / 20% / 30% / 50%
Daylight threshold| 2 ~ 500Lux, Disable
Warming up time| 20s
Operating temperature| – 20ºC ˜ +50°C
IP rating| IP65

Note: We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.

Installation

Warnings:

  1. Installation of the sensor involves connecting it to the main supply. This work must be carried out by a specialist in accordance with electrotechnical regulations.
  2. Disconnect power supply before installing.

A. Ceiling mount

HYTRONIK HMW31 High Bay Microwave Motion Sensor

B. Screw to the Luminaire by conduit

HYTRONIK HMW31 High Bay Microwave Motion Sensor -
conduit

C. Attach to the shade by clamp

HYTRONIK HMW31 High Bay Microwave Motion Sensor -
clamp

Rotary Switch Settings

A rotary switch is built inside the sensor for scene selection / fast programming. Total of 16 channels available:

Channel| Detection range| Hold time| Stand-by time| Stand-by dimming level| Daylight threshold
---|---|---|---|---|---
0| 100%| 5s| 10s| 10%| Disable
1| 100%| 1min| 5min| 10%| 2Lux
2| 100%| 5min| 10min| 10%| 10Lux
3| 100%| 5min| 30min| 10%| 30Lux
4| 100%| 5min| 0s| Disable| 10Lux
5| 100%| 5min| #NAME?| 10%| 30Lux
6| 100%| 5min| #NAME?| 30%| Disable
7| 100%| 10min| 10min| 10%| 2Lux
8| 100%| 10min| 30min| 10%| 10Lux
9| 100%| 10min| #NAME?| 10%| 30Lux
A| 100%| 10min| #NAME?| 30%| Disable
B| 75%| 10min| #NAME?| 10%| 30Lux
C| 50%| 10min| #NAME?| 10%| 10Lux
D| 100%| 30min| #NAME?| 10%| 50Lux
E| 100%| 30min| #NAME?| 30%| Disable
F| 100%| 5s| 10s| 10%| 2Lux

Functions

Tri-level Control (Corridor Function)
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas it requires a light change notice before switch-off. It offers 3 levels of light: 100%–>dimmed light–>off; and 2 periods of selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.

Lux Off Function
The built-in daylight sensor can read ambient natural light and switch off the fixture automatically whenever artificial light is unnecessary (natural light lux level exceeds daylight threshold).
Note: if the stand-by time is preset at “+∞”, the fixture never switches off even when natural light is sufficient.

Load Indication
The light will flash ONCE rapidly after receiving the command from the remote controller.
Note: There is no load indication (the light will not flash) when the button ON/OFF, POWER 100% or POWER 80% is pressed.

Wiring Diagram

Detection Pattern

Ceiling mounted detection pattern (m)

  • For a single person walking across, the detection range is reduced by 1/3.

Descriptions of the Button Functions (remote control HRC-11)

HYTRONIK HMW31 High Bay Microwave Motion Sensor - remote control
HRC

Permanent ON/OFF [button (1)]

Press button (1) to select permanent ON or permanent OFF mode.

  • Press button (2)/(3) to resume automatic operation.

The mode will change to AUTO Mode after power failure.

RESET [ button (2) ]

Press button (2), all settings go back to the rotary switch settings.

Shift [ button (3) ]

Press button (3 ), the LED on the top left corner is on for indication.

All values/settings in RED are valid for 20 seconds.

Auto Mode [ button (4)]

Press button (4) to initiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF.

Note: the function of Semi-auto is disabled.

Power output [ button (5) ]

Press button (5) , the light output shifts between 80% and 100%.

Note: the function of “Sensor off” and “Twilight” are disabled.

Brightness +/- [ button ( 6) ]
Press button (6) to adjust the light brightness between 10%~100%.

Scene prog. [ zone 7 ] (One-key-commissioning)

  1. Press the button “Start” to program.
  2. Select the buttons in ( 8 )”Detection range”, ( 9)/(10) “Daylight threshold”, ( 11)” Hold time”, ( 12) “Stand-by time”, ( 13) “Stand-by dimming level” to set all parameters.
  3. Press the button “Memory” to save all the settings programmed in the remote control.
  4. Press the button “Apply” to set the settings to each sensor unit(s). For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +∞, stand-by dimming level 30%, the steps should be as follows: Press button ( 7) Start, button ( 8) 100%,( 10) Disable, ( 3) Shift,( 12 )5min, ( 3 )Shift, ( 3 )+∞, ( 13) 30%, (7) Memory. By pointing to the sensor unit(s) and pressing  ( 7) Apply, all settings are passed on the sensor(s).

Detection range [ zone 8 ]

Press buttons in zone 8 to set detection range at 100% / 75% / 50% / 10%.

Daylight threshold [ zone 9 ]

Press buttons in zone (9) to set the daylight sensor at 2Lux / 10Lux / 50Lux / 100Lux / 300Lux / 500Lux or Disable. Note: To set daylight sensor at 100Lux / 300 Lux / 500Lux, press button (3) Shift at first.

Ambient daylight threshold [ button (10)]

  1. Press button (3) Shift, the red LED is on for indication.
  2. Press button (10) , the ambient lux level is sampled and set as the new daylight threshold.

Hold time [ zone (11)]
Press buttons in zone (11) to set the hold time at 2s / 30s / lmin / 5min / 10min / 15min / 20min / 30min. Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button (3) Shift at first. 2. 2s is for testing purpose only, stand-by period and daylight sensor settings are disabled in this mode.
*To exit from Test mode, press button (2) or any button in zone (11)

Stand-by time [ zone (13)]
Press buttons in zone (13) to set the stand-by period at Os / lOs / 1min / 5min / 10min / 30min / 1h / +00. Note: “Os” means on/off control; “+00” means bi-level control, 100% on when motion detected, and remains at the stand-by dimming level when no presence is detected after hold-time.

Dual tech & RF mode [ zone (14) ] All buttons in zone (14) are disabled

Trouble Shooting

MALFUNCTION CAUSE REMEDY CAUSE REMEDY
The fixture does not light up Incorrect daylight threshold setting Adjust

daylight threshold setting
Faulty fixture| Replace fixture
No power supply| Check power to the sensor
Detection zone not targeted| Check detection area setting
The fixture is always on| Continous movement in the detection zone| Check detection area setting
The fixture is on when it should not| Sudden change in temperature due to weather (wind, rain, snow) or air expelled from fans, open windows| Adjust zone, change installation site

HYTRONIK - logoHytronik Industrial Ltd. | www.hytronik.com
3rd Floor, Block C, complex building, 155#, Bai’gang road south,
Bo’gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023
Tel: 86-752-2772020 Fax: 86-752-2777877

Documents / Resources

| HYTRONIK HMW31 High Bay Microwave Motion Sensor [pdf] Instruction Manual
HMW31, High Bay Microwave Motion Sensor, HMW31 High Bay Microwave Motion Sensor, Microwave Motion Sensor, Motion Sensor, Sensor
---|---
| HYTRONIK HMW31 High Bay Microwave Motion Sensor [pdf] Instruction Manual
HMW31 High Bay Microwave Motion Sensor, HMW31, High Bay Microwave Motion Sensor

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

HYTRONIK User Manuals

Related Manuals