HYTRONIK HMW31 High Bay Microwave Motion Sensor Instruction Manual
- June 6, 2024
- HYTRONIK
Table of Contents
HMW31 High Bay Microwave Motion Sensor
Instruction Manual
Technical Specifications
Product type | Tri-level control microwave motion sensor |
---|---|
Operating voltage | 120~277VAC 50/60Hz |
Rated load | Capacitive: 400VA@120V; 800VA@220~277V |
Resistive: 800W@120V; 1600W@220~277V
Power consumption| < 0.5W
Detection angle| 360°
Detection area (Max.)*| Installation Height : 20m (forklift) 15m (person)
Detection Range (Ø) :20m
Detection range| 10% / 50% / 75% / 100%
Hold time| 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time| 0s / 10s / 1min / 5min / 10min / 30min / 1h / + ∞
Stand-by dimming level| 10% / 20% / 30% / 50%
Daylight threshold| 2 ~ 500Lux, Disable
Warming up time| 20s
Operating temperature| – 20ºC ˜ +50°C
IP rating| IP65
Note: We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.
Installation
Warnings:
- Installation of the sensor involves connecting it to the main supply. This work must be carried out by a specialist in accordance with electrotechnical regulations.
- Disconnect power supply before installing.
A. Ceiling mount
B. Screw to the Luminaire by conduit
C. Attach to the shade by clamp
Rotary Switch Settings
A rotary switch is built inside the sensor for scene selection / fast programming. Total of 16 channels available:
Channel| Detection range| Hold time| Stand-by time|
Stand-by dimming level| Daylight threshold
---|---|---|---|---|---
0| 100%| 5s| 10s| 10%| Disable
1| 100%| 1min| 5min| 10%| 2Lux
2| 100%| 5min| 10min| 10%| 10Lux
3| 100%| 5min| 30min| 10%| 30Lux
4| 100%| 5min| 0s| Disable| 10Lux
5| 100%| 5min| #NAME?| 10%| 30Lux
6| 100%| 5min| #NAME?| 30%| Disable
7| 100%| 10min| 10min| 10%| 2Lux
8| 100%| 10min| 30min| 10%| 10Lux
9| 100%| 10min| #NAME?| 10%| 30Lux
A| 100%| 10min| #NAME?| 30%| Disable
B| 75%| 10min| #NAME?| 10%| 30Lux
C| 50%| 10min| #NAME?| 10%| 10Lux
D| 100%| 30min| #NAME?| 10%| 50Lux
E| 100%| 30min| #NAME?| 30%| Disable
F| 100%| 5s| 10s| 10%| 2Lux
Functions
Tri-level Control (Corridor Function)
Hytronik builds this function inside the motion sensor to achieve tri-level
control, for some areas it requires a light change notice before switch-off.
It offers 3 levels of light: 100%–>dimmed light–>off; and 2 periods of
selectable waiting time: motion hold-time and stand-by period; Selectable
daylight threshold and freedom of detection area.
Lux Off Function
The built-in daylight sensor can read ambient natural light and switch off
the fixture automatically whenever artificial light is unnecessary (natural
light lux level exceeds daylight threshold).
Note: if the stand-by time is preset at “+∞”, the fixture never switches
off even when natural light is sufficient.
Load Indication
The light will flash ONCE rapidly after receiving the command from the
remote controller.
Note: There is no load indication (the light will not flash) when the
button ON/OFF, POWER 100% or POWER 80% is pressed.
Wiring Diagram
Detection Pattern
Ceiling mounted detection pattern (m)
- For a single person walking across, the detection range is reduced by 1/3.
Descriptions of the Button Functions (remote control HRC-11)
Permanent ON/OFF [button (1)]
Press button (1) to select permanent ON or permanent OFF mode.
- Press button (2)/(3) to resume automatic operation.
The mode will change to AUTO Mode after power failure.
RESET [ button (2) ]
Press button (2), all settings go back to the rotary switch settings.
Shift [ button (3) ]
Press button (3 ), the LED on the top left corner is on for indication.
All values/settings in RED are valid for 20 seconds.
Auto Mode [ button (4)]
Press button (4) to initiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF.
Note: the function of Semi-auto is disabled.
Power output [ button (5) ]
Press button (5) , the light output shifts between 80% and 100%.
Note: the function of “Sensor off” and “Twilight” are disabled.
Brightness +/- [ button ( 6) ]
Press button (6) to adjust the light brightness between 10%~100%.
Scene prog. [ zone 7 ] (One-key-commissioning)
- Press the button “Start” to program.
- Select the buttons in ( 8 )”Detection range”, ( 9)/(10) “Daylight threshold”, ( 11)” Hold time”, ( 12) “Stand-by time”, ( 13) “Stand-by dimming level” to set all parameters.
- Press the button “Memory” to save all the settings programmed in the remote control.
- Press the button “Apply” to set the settings to each sensor unit(s). For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +∞, stand-by dimming level 30%, the steps should be as follows: Press button ( 7) Start, button ( 8) 100%,( 10) Disable, ( 3) Shift,( 12 )5min, ( 3 )Shift, ( 3 )+∞, ( 13) 30%, (7) Memory. By pointing to the sensor unit(s) and pressing ( 7) Apply, all settings are passed on the sensor(s).
Detection range [ zone 8 ]
Press buttons in zone 8 to set detection range at 100% / 75% / 50% / 10%.
Daylight threshold [ zone 9 ]
Press buttons in zone (9) to set the daylight sensor at 2Lux / 10Lux / 50Lux / 100Lux / 300Lux / 500Lux or Disable. Note: To set daylight sensor at 100Lux / 300 Lux / 500Lux, press button (3) Shift at first.
Ambient daylight threshold [ button (10)]
- Press button (3) Shift, the red LED is on for indication.
- Press button (10) , the ambient lux level is sampled and set as the new daylight threshold.
Hold time [ zone (11)]
Press buttons in zone (11) to set the hold time at 2s / 30s / lmin / 5min
/ 10min / 15min / 20min / 30min. Note: 1.To set hold-time at 30s / 5min /
15min / 30min, press button (3) Shift at first. 2. 2s is for testing
purpose only, stand-by period and daylight sensor settings are disabled in
this mode.
*To exit from Test mode, press button (2) or any button in zone (11)
Stand-by time [ zone (13)]
Press buttons in zone (13) to set the stand-by period at Os / lOs / 1min /
5min / 10min / 30min / 1h / +00. Note: “Os” means on/off control; “+00” means
bi-level control, 100% on when motion detected, and remains at the stand-by
dimming level when no presence is detected after hold-time.
Dual tech & RF mode [ zone (14) ] All buttons in zone (14) are disabled
Trouble Shooting
MALFUNCTION CAUSE REMEDY | CAUSE | REMEDY |
---|---|---|
The fixture does not light up | Incorrect daylight threshold setting | Adjust |
daylight threshold setting
Faulty fixture| Replace fixture
No power supply| Check power to the sensor
Detection zone not targeted| Check detection area setting
The fixture is always on| Continous movement in the detection zone| Check
detection area setting
The fixture is on when it should not| Sudden change in temperature due to
weather (wind, rain, snow) or air expelled from fans, open windows| Adjust
zone, change installation site
Hytronik Industrial Ltd. |
www.hytronik.com
3rd Floor, Block C, complex building, 155#, Bai’gang road south,
Bo’gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023
Tel: 86-752-2772020 Fax: 86-752-2777877
Documents / Resources
|
HYTRONIK HMW31 High Bay Microwave Motion
Sensor
[pdf] Instruction Manual
HMW31, High Bay Microwave Motion Sensor, HMW31 High Bay Microwave Motion
Sensor, Microwave Motion Sensor, Motion Sensor, Sensor
---|---
|
HYTRONIK HMW31 High Bay Microwave Motion
Sensor
[pdf] Instruction Manual
HMW31 High Bay Microwave Motion Sensor, HMW31, High Bay Microwave Motion
Sensor
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>