Hard Head 014100 Wireless Smoke Detector Instruction Manual
- June 6, 2024
- Hard Head
Table of Contents
Hard Head 014100 Wireless Smoke Detector
OPERATING INSTRUCTIONS
Important! Read the user instructions carefully before use. Save them for future reference. (Translation of the original instructions)
SAFETY INSTRUCTIONS
Carefully read the instructions before use! Save these instructions for future reference.
- Do not use the product in damp, dusty or smoky environments.
- Do and not sound install are the blocked. product so that light level
- When the smoke battery detector capacity will reach emit an a low audio seconds to prompt indicate approximately that the battery every 43/60 needs to be replaced.
- Store the smoke detector and packaging
- If materials several out connected of the reach products of are children. installed, make sure that no objects obstruct
- The alarm communication. the function must only be tested not with use the any test another button test on the method. product. Test theDo alarm correct function functionality. every week, to verify
- The alarm might not be noticed by all l is persons strong, in so the that it building. will be The easily alarm noticed signs are when several danger exists. circumstances Nevertheless that can there prevent the example alarm strong signal from background being noise detected, indoors for or outdoors, deep sleep, hearing, or influence of alcohol diminished or drugs. and Alarm adapted devices to must such and therefore other be chosen alarm conceivable signal. lffor difficulties example in a detecting person the in the and therefore household can has be diminished expected to hearing special difficulty in alarms detecting with light the alarm and/or signal, have vibration or signals effective death, must protection be smoke installed. from detector To personal must provide be injury heard very quickly.
SYMBOLS
- Read the instructions.
- Approved in accordance with the relevant directives.
- Recycle discarded product in accordance with local regulations.
TECHNICAL DATA
NB2831 Jula AB, Box 363, SE-532 24 SKARA, SWE DEN Item No.014100 DoP reference No. DOP442055 Can be downloaded from www.jula.com EN 14604:2005/AC:2008 Smoke alarm device. Intended for Fire Safety and installed in buildings. Essential Characteristic 1-8: pas. CPR NO 2831-CPR-F1066.
- Standard EN 14604-2005/AC:2008
- Frequency 433.92 MHz
- Sound level for alarm <‘. 85 dB/3 m
- Range 80 m
- Size H4.8 x (/)12.5 cm
- Operating temperature -10 to 40° C
- Ambient humidity,:; 95% RH (non-condensing)
NOTE:
The optical smoke detector can be wirelessly interconnected with up to 22 optical smoke detectors.
DESCRIPTION
- Photoelectric smoke detection
- High sensitivity
- Low power consumption
- Can be connected to unlimited number of other units
PARTS
Front
- Casing
- Alarm status light (red LED)
- Test button
- Buzzer
- Status light connection/learning (red/green LED)
- Learn button
Back
- Base
- Slot
- Compartment for 9 V battery
- Compartment for 1.5 V battery
Mounting plate
- Mounting plate
- Screw hole
- Hook
INSTALLATION
- Choose a suitable place to install within range of the other units.
- Use the mounting plate as a template and mark out and drill holes in the ceiling. Insert plugs in the holes.
- Screw on the mounting plate.
- Align the two hooks on the mounting plate to the slots in the base. Turn the base clockwise so that the hooks slot in place.
- Carry out a communication test after completing the installation.
INSERTING BATTERIES
- Unpack the product, turn the mounting plate anticlockwise and remove the batteries (9 V and 1.5 V). Remove the protective film from the batteries.
- Insert the 9 V battery with the polarity shown in the battery compartment.
- Turn the locking arm inward and insert the 1.5 V batteries with the polarity shown in the battery compartment.
- Align the two hooks on the mounting plate to the slots in the base and turn the plate clockwise so that the hooks slot in place.
HOW TO USE
TESTING/CONNECTINCi/REMOVINCi
When the smoke detector has started a red alarm status light flashes at 43-second intervals.
TEST
Press the test button. A loud audio signal is heard and the red alarm status light starts flashing. The red/green status light for connecting/learning mode flashes and a wireless alarm signal is given at the same time to all the connected smoke detectors within range. This shows that the smoke detector is working properly. You can also do a test with artificial smoke.
SETTING/CONNECTING
Setting as host unit: When two or more smoke detectors are connected, press the learn button once. The red/green status light changes colour once. Set host units to the mode for green status light. Setting as slave: Set slave units to the mode for red status light.
CONNECTED
- When the correct setting is made, keep the test button on the host unit pressed until the red alarm status light and the red/green status light for connection/learn flash continuously and a wireless alarm signal is given.
- When a slave unit receives a signal from the host unit the status light for learn mode flashes continuously and an alarm is given at the same time by all the connected units. The red status light goes off.
- When the required units are connected, press the test button on one of the alarm units. The other connected smoke detectors give an alarm and the status lights flash continuously.
REMOVAL
Press the learn button on the unit to be removed, to put the unit in the mode for green status light. Press the test button to activate normal alarm mode. The red status light for alarm and the red/green status light for connection/learn flash continuously to show that the smoke detector has been removed.
FIRE DRILLS
- When an alarm sounds everyone must know what to do. Prepare yourself and others in the building by establishing evacuation plans, and practice regularly. 1. Let everyone hear the alarm signal and ensure that they all know what it means.
- Establish two exits from each room and one evacuation route from the building for each of these two exits.
- Teach everyone to feel doors before opening them. If the door is warm it must not be opened – choose an alternative exit.
- Explain that smoke and fumes rise to the ceiling – creep along the floor if evacuation must take place through smoke filled rooms.
- Establish an assembly area outside the building.
IN CASE OF FIRE
- Stay calm – panic is your worst enemy.
- Evacuate the building as quickly as possible. Feel all doors before opening them, and do not open warm doors. Choose an alternative exit if necessary. Creep along the floor and never stop to try to take something with you.
- Assemble in previously agreed place outside the building.
- Alarm the fire brigade when you are outside the building.
- Never go back into a burning building. Wait until the fire brigade arrives.
NOTE:
These guidelines increase the chances of the involved parties to manage in the event of a fire, but to work they must be practiced regularly!
MAINTENANCE
- Test the smoke detector every week.
- Clean the smoke detector every month. Remove the batteries before cleaning. Check the connection with the test button after cleaning.
- If the smoke detector is not working properly, check the batteries.
- Only replace the batteries with new batteries of the same type.
TROUBLESHOOTING
Nothing happens when the test button is pressed.
| ****
9 V battery not properly inserted.
| Insert the 9 V battery with the
polarity shown in the battery compartment.
---|---|---
Nothing happens when the learn button is pressed.
| ****
15 V batteries not properly inserted.
| Insert 3 x 15 V batteries with the polarity shown in the battery
compartment.
An audio signal is given at 43-second intervals.| ****
9 V battery discharged.
| ****
Replace the 9 V battery.
An audio signal is given at 60-second intervals.| ****
15 V batteries discharged.
| ****
Replace the 3 x 15 V batteries.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>