RCA RACE1011 Electric Window Air Conditioner Instruction Manual
- June 6, 2024
- RCA
Table of Contents
Models RACE1011-6COM
Electronic Window Air Conditioner
Operating Instructions
This product has been manufactured and sold under the responsibility of Curtis International Ltd. RCA, the RCA logo, the two dogs (Nipper and Chipper) logo, are registered trademarks or trademarks of Technicolor (S.A.) or its affiliates and are used under license by Curtis International Ltd. Any other product, service, company, trade or product name and logo referenced herein are neither endorsed nor sponsored by Technicolor (S.A.) or its Affiliates.
IMPORTANT SAFETY INSTRUCTIONS
Before installing and using your air conditioner, please read this owner’s
manual carefully. Store this manual in a safe place for future reference. Your
safety and the safety of others are very important to us. Please pay attention
to all safety messages outlined in this owner’s manual.
WARNING: To reduce the risk of fire, electrical shock, or injury when
using your air conditioner, follow the following basic precautions:
- Plug into a grounded 3 prong outlet.
- Do not remove the ground prong.
- Do not use a plug adapter.
- Do not use an extension cord.
- Unplug the air conditioner before servicing
- Use two or more people to move and install the air conditioner
****This is a safety alert symbol. This symbol alerts you to potential
hazards that can harm you or others or even cause death.
All safety messages will directly follow the safety alert symbol and/or the
words “DANGER” or “WARNING”.
**** Failure to immediately follow these instructions may cause serious
injury or even death.
All Safety messages alert you of potential hazards, how to reduce the chance
of injury, and what can happen if instructions are not followed correctly.
INTRODUCTION TO REFRIGERANTS R32
The refrigerants used for air conditioners are environmentally friendly
hydrocarbons R32. This kind of erant is combustible and odorless. Moreover, it
can bum and explode under certain conditions. However, there will be no risk
of burning and explosion if you comply with the following table to install
your air conditioner in a room with an appropriate area and use it correctly.
Compared with ordinary refrigerants, Refrigerant R32 is environmentally
friendly and does not destroy the ozone sphere and its value of greenhouse
effect is also very low.
Room area requests for an air conditioner with Refrigerant R32
Refrigerant | Capacity(Btu) | Room Area |
---|---|---|
R32 | ≤ 9K | Above 4m’ |
≤12K | Above 4m’ | |
≤18K | Above 15m’ | |
≤.24K | Above 25m’ |
Warnings
- Please read the manual before installation, use, maintenance.
- Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
- Do not pierce or bum the appliance.
- The appliance shall be stored in a room without continuously operating sources (for example open flames, an operating ignition gas appliance, or an operating electric heater.)
- Please contact the nearest after-sales service center when maintenance is necessary. At the time of maintenance, the maintenance personnel must strictly comply with the Operation Manual provided by the corresponding manufacturer, and any non-professional is prohibited to maintain the air conditioner.
- The handling, installation, storage, servicing, and disposal must comply with the provisions of gas-related national laws and regulations, and also national wiring regulation.
- It is necessary to clear away the refrigerant in the system when maintaining or scrapping an air conditioner. Be aware that refrigerants may not contain an odor.
This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or supervision or
instruction concerning use of the appliance by a person responsible for their
safety.
Children should be supervised to ensure that they do not play with the
appliance.
Unit operation limits: Outdoor side 61-110T, 80%0RH; indoor side 61-90 I:,
80%12H.
ELECTRICAL REQUIREMENTS
Electrical Shock Hazard Plug into a grounded 3 prong outlet. Do not remove the ground prong. Do not use an adapter Do not use an extension cord. Failure to follow these instructions can result in death, fire, or electrical shock
The electrical ratings for your air conditioner are listed on the model and
serial number label located on the front left side of the unit (when facing
the front).
Specific electrical requirements are listed in the chart below. Follow the
requirements below for the type of plug on the power supply cord.
Wiring Requirements
• 115 volts (103 min.-127 max)
• (6K-8K) 0-8 amps
• (6K-8K) 10-amp time-delay fuse or circuit breaker
• Use on single outlet circuit only
Power Supply Cord
Recommended Ground Method
For your personal safety, this air conditioner must be grounded. This air
conditioner is equipped with a 3 prong power supply cord with a grounded plug.
To minimize the possibility of electrical shock, the cord must be plugged into
a 3 prong outlet and grounded in accordance with all local codes and
ordinances. If a 3 prong outlet is not available, it is the customer’s
responsibility to have a properly grounded 3 prong outlet installed by a
qualified electrician.
It is the customer’s responsibility:
- To contact a qualified electrician
- To assure that the electrical installation is adequate and in conformance with the National Electrical Code, ANSI/NFPA 70 – latest edition, and all local codes and ordinances.
Copies of the standards listed may be obtained from
National Fire Protection Association
One Batterymarch Park
Quincy, Massachusetts 02269
LCD! Power Cord and Plug
This air conditioner is equipped with an LCDI (Leakage Current Detection and Interruption) power cord that is required by UL. This power supply cord contains state-of-the-art electronics that sense leakage current. If the cord is damaged and leakage occurs, power will be disconnected from the unit. The test and reset buttons on the LCDI Plug are used to check if the plug is functioning properly. To test the plug:
- Plug power cord into a grounded 3 prong outlet.
- Press RESET (on some units a green light will turn on).
- Press the TEST Button, The circuit should trip and cut all power to the air conditioner (on some units a green light may turn off.
- Press the RESET button for use. You will hear a click and the NC is ready for use.
NOTES:
- The RESET button must be engaged for proper use.
- The power supply cord must be replaced if it fails to trip when the TEST button is pressed and the unit fails to reset.
- Do not use the power supply cord as an ON/OFF switch. The power supply cord is designed as a protection device.
- A damaged power supply cord must be replaced with a new power supply cord.
- The power supply cord contains new user-serviceable parts. Opening the tamper-resistant case voids all warranty and performance claims.
NOTE: Your unit’s power cord and plug may differ from the one shown.
PACKING LIST
IMAGE
| PART|
QUANTITY
---|---|---
| Window Air Conditioner|
1
| Remote Control|
1
| Top Mounting Rail (With sponge)|
1
| Lock Frame|
2
| Filler Panels (With “Left” & “Right” remark on the front face)|
1
| Sash Lock(Two holes)|
1
| Window Sash Seal (Sponge)|
1
| 3/8″ Screws|
4
| 1/2″ Screws|
3
| 3/4″ Screws|
4
| Foam Top Window Gasket (Thin sponge for backup using)|
1
| Insulation strip(Sponge) (Only for A-star model)|
2
DISCLAIMER
ALL INFORMATION AND THE TECHNICAL SPECIFICATIONS PRESENTED IN THIS USER’S
MANUAL ARE THE PRESENTATIONS OF THE MANUFACTURER.
INSTALLATION & ASSEMBLY INSTRUCTIONS
Some assembly is required for your new air conditioner. Please read and follow
these instructions carefully.
- This air conditioner is designed to be installed in a standard double-hung window with a window width between 26″ and 36″ (660 mm – 914 mm).
- The air conditioner can be installed without the accordion panels to fit in a narrow window opening. See the window dimensions.
- The Lower Sash (the lower part of the window that moves up and down) must allow for 16″ of vertical clearance when open. (See FIG. 1).
- All supporting parts must be secured to firm wood, masonry, or metal.
- The electrical outlet must be within reach of the power cord.
NOTE: Save the product packaging and installation instructions for future reference. Store the air conditioner in the product box when not in use for an extended period of time.
Top Rail Assembly
The top rail must be assembled prior to installing the air conditioner in the
window.
Tools Needed: Phillips Screw Driver
Attaching the Top Rail to the Air Conditioner
- Remove the air conditioner from the box and place it on a hard flat surface.
- Remove top rail from the bottom of the packaging material as shown in FIG. A.
- Align the hole in the top rail with those in the top of the unit as shown in FIG. B.
- Secure the top rail to the unit with the 3/8″ screws as shown in FIG. C.
NOTE: For safety reasons, all 4 screws must be used to attach the top rail.
CAUTION
When handling the unit, be careful to avoid cuts from the sharp metal edges
and aluminum fins on the front and rear coils.
TOOLS NEEDED:
- Phillips Screw Driver
- Drill(If pilot holes are needed
CAUTION
When handling the unit, be careful to avoid cuts from the sharp metal edges
and aluminum fins on the front and rear coils.
How to Install
REWORD: Top Rail and Sliding Panels at each side are offset to provide the
proper pitch of 5/16″ to the rear of the air conditioner.
place unit on the floor, a bench, or a table. There is a Left and Right Window
Filler Panel – be sure to use the proper panel for each side. When installed
the flange for securing the panel in place to the window sill will be facing
into the room.
A. Hold the Accordion Panel in one hand and gently pull back the center to
free the open end. See Figure 3.
B. Slide the free end of the panel into the cabinet as shown in Figure 4. Slide the panel down. Be sure to leave enough space to slip the top and bottom of the frame into the rails on the cabinet.
C. Once the panel has been installed on the side of the cabinet, make sure it sits securely inside the frame channel by making slight adjustments. Slide the top and bottom ends of the frame into the top and bottom rails of the cabinet. Figure 5.
D. Slide the panel all the way in and repeat on the other side.
Keeping a firm grip on the air conditioner, carefully place the unit into the window opening so the bottom of the air conditioner frame is against the window sill (FIG. 6). Carefully close the window behind the top rail of the unit. (It is suggested to keep a downward angle so accumulated rainwater can drain out from the backside of the unit.) Extend the side panels out against the window frame (FIG. 7).
Place the frame lock between the frame extensions and the window sill as shown (Fig. 8). Drive 3/4″ (19 mm) locking screws through the frame lock and into the sill (FIG. 9). NOTE: To prevent window sill from splitting, drill 1/8″ (3 mm) pilot holes before driving screws.
Drive 1/2″ (12.7mm) locking screws through frame holes into window sash (FIG.10/11).
To secure lower sash in place, attach right angle sash lock with 3/4″ (19 mm)
screw as shown (FIG. 12).
Cut foam seal and insert in the space between the upper and lower sashes (FIG. 13).
If AC is Blocked by Storm Window
Add wood as shown in FIG. 14, or remove the storm window before the air conditioner is installed.
If the storm window frame must remain, be sure the drain holes or slots are not caulked or painted shut. Accumulated rainwater or condensation must be allowed to drain out.
Removing AC From Window
\* Turn AC off, and disconnect the power cord.
- Remove sash seal from between windows and unscrew safety lock.
- Remove screws installed through frame and frame lock.
- Close (slide) side panels into frame.
- Keeping a firm grip on the air conditioner, raise sash and carefully “rock” air conditioner backward to drain any condensate water in the base of the unit. Be careful not to spill any remaining water while lifting the unit from the window. Store parts WITH air conditioner.
AIR CONDITIONER USE
Operating your air conditioner properly helps you to obtain the best possible
results. This section explains proper air conditioner operation.
IMPORTANT:
■ If you turn off the air conditioner, wait at least 3 minutes before turning
it back on. This prevents the air conditioner from blowing a fuse or tripping
a circuit breaker.
■ Do not try to operate your air conditioner in the cooling mode when the
outside temperature is below 65°F (18°C). The inside evaporator coil will
freeze up, and the air conditioner will not operate properly.
NOTE: In the event of a power failure, your air conditioner will operate
at the previous settings when the power is restored.
INSTALLATION & ASSEMBLY INSTRUCTIONS Introduction to Refrigerants R32
- Before installing the appliance, you must read the manual carefully to get the safety information and notes.
- When filling the combustible refrigerant, any of your rude operations may cause serious injury or injuries to the human body or bodies and objects or objects.
- A leak test must be done after the installation is completed.
- It is a must to do a safety inspection before maintaining or repairing an air conditioner using combustible refrigerant in order to ensure that the fire risk is reduced to a minimum.
- It is necessary to operate the machine under a controlled procedure in order to ensure that any risk arising from the combustible gas or vapor during the operation is reduced to a minimum.
- Requirements for the total weight of filled refrigerant and the area of a room to be equipped with an air conditioner (are shown as in the following Tables GG.1 and GG.2)
The maximum charge and the required minimum floor area
= (4 m3) x LFL, m2= (26 m3)) x LFL, m,= (130 m3 )x LFL Where LFL is the lower
flammable limit in kg/ m3, R32 LFL is 0.306 kg/ m3.
For the appliances with a charge amount m, < M Cm2:
The maximum charge in a room shall be in accordance with the following:mmax=
2.5 x (LFL)(514)x hp x (A)112 The required minimum floor area Amin to install
an appliance with refrigerant charge M (kg) shall be in accordance with
following: Am, = (MI (2.5 x (LFL)(5/4)x hp)) 2
Where: Emax is the allowable maximum charge in a room, in kg;
M is the refrigerant charge amount in the appliance, in kg;
Amin is the required minimum room area, in m2;
A is the room area, in m2;
LFL is the lower flammable limit, in kg/m3;
hp is the installation height of the appliance, in meters for calculating MMA„
or Am,„ 1.8 m for wall mounted;
Table GG.1 Maximum charge (kg)
Category| LFL (kg/m3)| h o
(m)
| Floor area(m 2 )
---|---|---|---
4| 7| 10| 15| 20| 30| 50
R32| 0. 306| 0.6| 0.68| 0.9| 1.08| 1.32| 1.53| 1.87| 2.41
1| 1.14| 1.51| 1.8| 2.2| 2.54| 3.12| 4.02
1.8| 2.05| 2.71| 3.24| 3.97| 4.58| 5.61| 7.254
2.2| 2.5| 3.31| 3.96| 4.85| 5.6| 6.86| 8.85
Table GG.2 Minimum room area (m2)
Category| LFL (kg/m’)| h o(m)| Charge amount (M) (
kg) Minimum room area(m 2 )
---|---|---|---
R32| 0.306| | 1.224 kg| 1.836 kg| 2.448 kg| 3.672 kg| 4.896 kg| 6.12 kg| 7.956
kg
0.6| | 29| 51| 116| 206| 321| 543
1| | 10| 19| 42| 74| 116| 196
1.8| | 3| 6| 13| 23| 36| 60
2.2| | 2| 4| 9| 15| 24| 40
INSTALLATION & ASSEMBLY INSTRUCTIONS
Introduction to Refrigerants R32
-
Site Safety
-
Operation Safety
-
Installation Safety
**** • Refrigerant Leak Detector
•Appropriate Installation Location| the left picture is the schematic diagram of a refrigerant leak detector.
---|---
Please note that:
- The installation site should be in a well-ventilated condition.
- The sites for installing and maintaining an air conditioner using Refrigerant R32 should be free from open fire or welding, smoking, drying oven, or any other heat source higher than 548°C which easily produces open fire.
- When installing an air conditioner, it is necessary to take appropriate anti-static measures such as wearing anti-static clothing and/or gloves.
- It is necessary to choose the site convenient for installation or maintenance wherein the air inlets and outlets of the indoor and outdoor units should be not surrounded by obstacles or close to any heat source or combustible and/or explosive environment.
- If the indoor unit suffers a refrigerant leak during the installation, all the personnel should go out till the refrigerant leaks completely for 15 minutes. If the product is damaged, it is a must to carry such damaged product back to the maintenance station and it is prohibited to weld the refrigerant pipe or conduct other operations on the user’s site.
- It is necessary to choose the place where the inlet and outlet air of the indoor unit is even.
- It is necessary to avoid the places where there are other electrical products, power switch plugs, and sockets, kitchen cabinets, beds, sofa, and other valuables right under the lines on two sides of the indoor unit, and also prevent mechanical damage from occurring.
USING YOUR AIR CONDITIONER Electronic Control Panel & Remote Control
NOTE: This display always shows the room temperature in Fan Mode except
when setting the Timer.
NOTE: “*” means only available for VVIFI modes, For more information,
please see the VVIFI manual.
Normal Operating Sounds
- You may hear a pinging noise caused by water hitting the condenser, on rainy days, or when the humidity is high. This design feature helps remove moisture and improve efficiency.
- You may hear the thermostat click when the compressor cycles on and off.
- Water will collect in the base pan during rain or days of high humidity. The water may overflow and drip from the outside part of the unit.
- The fan may run even when the compressor is not on.
-
Digital Display: When the timer is not in use, the operation mode and the set temperature will be displayed. Time will be displayed under the timer setting.
-
—. ands Button: Use these buttons on the control panel and remote to increase or decrease the Set Temperature or Timer. Temperature range: 61T-88°F or 16°C-31°C.
-
Power Button: Turn the air conditioner on and off.
-
Mode Button: Press the mode button to cycle through the various modes: Cool, Dry, Fan, and Auto.
Cool Mode: The cooling function allows the air conditioner to cool the room and at the same time reduces air humidity. Press the MODE button to activate the cooling function. To optimize the function of the air conditioner, adjust the temperature and the speed by pressing the button indicated.
Dry Mode: This function reduces the humidity of the air to make the room more comfortable. Press the MODE button to set the DRY mode. An automatic function of alternating cooling cycles and air fan is activated.
Fan Mode: This function only works when the air conditioner is vented. Press the MODE button to set the FAN mode. With pressing the FAN SPEED button, the speed changes in the following sequence: Hi, Med, and Lo in FAN mode.
Auto Mode : In AUTO mode the unit automatically chooses the mode of operation (COOL, DRY, or FAN), In this mode, the temperature will be set according to the room temperature (tested by the temperature sensor which is incorporated in the indoor unit.). -
Timer Button : Use these buttons on the control panel and remote to set the Timer.
Timer Off: The timed stop is programmed by pressing the TIMER button. Set the rest time by pressing the button ” A ” or ” V ” until the rest time displayed is to your liking then press the TIMER button again.
Timer On: When the unit is off, press the TIMER button, set the temperature by pressing the button ” A ” or ” V “. Press the TIMER button a second time, set the rest time by pressing the button ” A ” or ” V “. Press the TIMER button a third time, confirm the setting, then will automatically switch on and will show on the display.
Note: It can be set to automatically turn off or on in 0.5-24 hour increments. Each press of the ” A ” ” V ” buttons will increase or decrease the timer. The Timer can be set in 0.5 hours increment below 10 hours and 1-hour increment for 10 hours or above.
The SET light will turn on while setting. To cancel the set function, press the TIMER button again.
USING YOUR AIR CONDITIONER Electronic Control Panel & Remote Control -
Eco Button: When the unit is in ECO mode, the light will turn on. In ECO mode, the unit will turn off once the room is cooled to the user set temperature. The fan will also be off at this point. The unit will turn back on when the room temperature rises above the user set temperature. Before the compressor starts, the fan motor will run for a while, then it will stop for a while, and will repeat to provide a much more comfortable feeling and save energy.
-
Sleep Button: Press the SLEEP button, all of the display lights will turn off after a while, but the Sleep light is always on. In SLEEP mode, the air conditioner will automatically adjust the temperature and fan speed to make the room more comfortable during the night. The set temperature will automatically raise every 30-60 minutes, and at most change six times until the set temperature is 81 or 82°F.
-
Fan Speed Button : Press the FAN SPEED button to choose the fan speed options. You can choose Hi, Med, Low, or auto speed in COOL mode or choose Hi, Med, Lo in FAN mode.
-
Filter Button: When the Filter Check light is off, it is not necessary to press the Filter Check button. When the Filter Check light is on, you can turn off the light by pressing the Filter Check button. After the fan motor works for 500 total hours, the Filter Check light will turn on to remind the user to clean the filter.
-
Directional Louvers : To direct the airflow, use the horizontal wheel to control the horizontal direction and use the air deflectors to control the vertical direction.
OPERATING YOUR AIR CONDITIONER
REMOTE CONTROL
- Power: Turn the air conditioner on and off.
- Cool: Press the COOL button to COOL mode.
- r\ and \./: Use these buttons on the control panel and remote to increase or decrease the Set Temperature or Timer. Temperature range: 61°F-88°F or 16’C -31t.
- Sleep: Press the SLEEP button, all of the display lights will turn off after a while, but the Sleep light is always on. In SLEEP mode, the air-conditioner will automatically adjust the temperature and fan speed to make the room more comfortable during the night. The set temperature will automatically raise every 30-60 minutes and at most change six times until the set temperature is 81 or 82°F.
- Timer: Use these buttons on the control panel and remote to set the Timer. Timer Off: The timed stop is programmed by pressing the TIMER button. Set the rest time by pressing the button ” A “or” V ” until the rest time displayed is to your demand then press the TIMER button again. Timer On: When the unit is off, press the TIMER button for the first time, set the temperature by pressing the button or” A “. Press the” V “TIMER button at the second time, set the rest time by pressing the button or” A “. Press” V “TIMER button at the third time, confirm the setting, then the rest time to next automatical switching-on could be read on the display of the machine. Note: It can be set to automatically turn off or on in 0.5-24 hours. Each press of the A ” ” V buttons will increase or decrease the timer. The Timer can be set in 0.5 hours increment below 10 hours and 1-hour increment for 10 hours or above. The SET light will turn on while setting. To cancel the set function, press the TIMER button again.
- Auto Mode: In AUTO mode the unit automatically chooses the mode of operation(COOL, DRY, or FAN). In this mode, the temperature will be set automatically according to the room temperature (tested by the temperature sensor which is incorporated in the indoor unit.).
- Fan Speed : Press the FAN SPEED button to choose the fan speed options. You can choose Hi, Med, Low, or auto speed in COOL mode and choose Hi, Med, Lo in FAN mode.
- Display: To press the DISPLAY button, it can switch off/on all lights or LED displays.
- Eco: When the unit is in ECO mode, the light will turn on. In ECO mode, the unit will turn off once the room is cooled to the user set temperature. The unit will turn back on when the room temperature rises above the user set temperature. Before the compressor starts, the fan motor will run for a while, then it will stop for a while, and will repeat to provide a much more comfortable feeling and save energy.
- Fan Only: Press the Fan Only button to FAN ONLY mode.
Battery Size: AAA – NOTE: Do not mix old and new batteries or different types of AAA batteries.
CARE AND CLEANING
Clean your air conditioner to keep it looking new and to minimize dust build-
up.
Air Filter Cleaning
The air filter should be checked at least once every month to see if it needs cleaning. Trapped particles and dust can build up in the filter and may decrease airflow as well as cause the cooling coils to accumulate frost. To clean the air filter:
- Remove the filter by pulling down the in-dents of the filter door on the front of the unit. (See FIG. 15)
- Wash the filter using liquid dish soap and warm water. Rinse the filter thoroughly. Gently shakes the filter to remove excess water.
- Let the filter dry completely before placing it into the air conditioner.
- If you do not wish to wash the filter, you may vacuum the filter to remove the dust and other particles.
Wear and Tear
To minimize wear and tear on the air conditioner, always wait at least 3
minutes before changing modes. This will help prevent the compressor from
overheating and the circuit breaker from tripping.
Cabinet Cleaning
To clean the air conditioner cabinet:
- Unplug the air conditioner to prevent shock or a fire hazard. The cabinet and front panel of the air conditioner may be dusted with an oil-free cloth or washed with a cloth dampened in a solution of warm water and mild liquid soap. Rinse thoroughly with a damp cloth and wipe dry.
- Never use harsh cleaners, wax or polish on the cabinet front.
- Be sure to wring excess water from the cloth before wiping around the controls. Excess water in or around the controls may cause damage to the air conditioner.
Winter Storage
To store the air conditioner when it is not in use for an extended period of time, remove it carefully from the window according to the installation instructions and cover it with plastic or place it in the original box.
TROUBLESHOOTING
PROBLEM | POSSIBLE CAUSES | SOLUTIONS |
---|---|---|
The Air Conditioner will not start | The air conditioner is unplugged. | · Make |
sure the air conditioner plug is pushed completely into the outlet.
The fuse is blown/circuit breaker is tripped.| · Check the house fuse/circuit
breaker box and replace the fuse or reset the breaker.
Power failure.| · The unit will automatically restart when power is
restored.
· There is a protective time delay (approx. 3 minutes) to prevent tripping of the compressor overload. For this reason, the unit may not start normal cooling for 3 minutes after it is turned back on.
The current interrupter device is tripped,| · Press the RESET button located on the power cord plug.
· If the RESET button will not stay engaged, discontinue use of the air conditioner and contact a qualified service technician.
The Air Conditioner does not cool as it should| Airflow is restricted.| ·
Make sure there are no curtains, blinds, or furniture blocking the front of
the air conditioner.
The temperature control may not be set correctly.| · Lower the set
thermostat temperature.
The air filter is dirty.| · Clean the filter. See the Cleaning and Care
section of the manual.
The room may be too warm.| · Please allow time for the room to cool down
after turning on the air conditioner.
Cold air is escaping.| · Check for open furnace registers and cold air
returns.
The cooling coils are frozen.| · See “Air Conditioner Freezing Up” below.
The Air Conditioner is freezing up| Ice blocks the airflow and stops the air
conditioner from cooling the room,| · Set the MODE dial to HIGH FAN
or HIGH COOL and set the thermostat to a higher temperature.
The Remote Control is not working| The batteries are inserted incorrectly. The
batteries may be dead.| · Check the position of the batteries.
· Replace the batteries.
PROBLEM | POSSIBLE CAUSES | SOLUTIONS |
---|---|---|
Water is dripping outside | Hot and humid weather. | · This is normal. |
Water is dripping inside the room | The air conditioner is not | |
correctly tilted outside. | · For proper water drainage, make sure the air |
conditioner is slightly tilted downward from the front of the unit to the
rear.
Water collects in the base pan| Moisture removed from the air is draining
into the base pan.| · This is normal for a short period in areas with low
humidity and normal for a longer period in areas with high humidity.
SPECIFICATION
RCA Model | RACE1011-6COM |
---|---|
Power supply | Ph-V-Hz |
Cooling | RATED Capacity |
RATED Input | W |
RATED Current | A |
Standby power | W |
Max. input consumption | W |
Max. current | A |
Starting current | A |
Refrigerant type (R32) | g |
Refrigerant type (R32) | ozs |
Design pressure(145psi=1MPa )(L/H) | psi |
Operation temp | indoor (cooling/heating) |
°F | 61T-884F |
outdoor (cooling/heating) | °C |
°F | 64°F-109°F |
Application area (Cooling EPA) | sp. ft |
Dimension(WDH) | mm |
in | 19.76×21.5×15.16 |
Packing (WDH) | mm |
in | 22.63×24.52×18.50 |
Net/Gross weight | Kg |
lbs | 61.7/73.9 |
LIMITED PRODUCT WARRANTY
AIR CONDITIONERS, DEHUMIDIFIERS
To make a warranty claim, do not return this product to the store. Please
email support@curtiscs.com or call
1-800-968-9853.
1 Year Warranty
This product is warranted to be free from defects in material and workmanship
for a period of one (1) year from the date of original purchase. During this
period, your exclusive remedy is repair or replacement of this product or
component found to be defective, at our option; however, you are responsible
for all costs associated with returning the product to us. If the product or
component is no longer available, we will replace it with a similar one of
equal or greater value. Prior to a replacement being sent, the product must be
rendered inoperable or returned to us.
This warranty does not cover glass, filters, wear from normal use, use not in
conformity with the printed directions., or damage to the product resulting
from accident, alteration, abuse, or misuse. This warranty extends only to the
original consumer purchaser or gift recipient. Keep the original sales
receipt, as proof of purchase, is required to make a warranty claim. This
warranty is void if the product is used for other than single-family household
use or subjected to any voltage and waveform other than as on the specified
rating on the label (e.g., 120V-60Hz).
We exclude all claims for special, incidental, and consequential damages
caused by a breach of express or implied warranty. All liability is limited to
the amount of the purchase price. Every implied warranty, including any
statutory warranty or condition of merchantability or fitness for a particular
purpose, is disclaimed except to the extent prohibited by law, in which case
such warranty or condition is limited to the duration of this written
warranty. This warranty gives you specific legal rights. You may have other
legal rights that vary depending on where you live. Some states or provinces
do not allow limitations on implied warranties or special, incidental, or
consequential damages, so the foregoing limitations may not apply to you.
For faster service, locate the model, type, and serial numbers on your
appliance.
The design and specifications are subject to change without prior notice for
product improvement. Consult with the sales agency or manufacturer for
details.