GE APPLIANCE RARWT Single Zone Smart Thermostat Owner’s Manual
- June 6, 2024
- GE APPLIANCE
Table of Contents
- GE APPLIANCE RARWT Single Zone Smart Thermostat
- IMPORTANT SAFETY INFORMATION
- Specifications
- Package Contents
- Installation Instructions
- Controls (RARWT )
- Control and Operating Functions (RAREC1A)
- Control and Operating Functions (RAREC2A)
- On Board Diagnostics (RARWT )
- On Board Diagnostics (RARWT )
- Fault Codes (RARWT )
- Wiring Diagrams
- Testing the Thermostat
- Troubleshooting Tips
- Thermostat Limited Warranty
- Consumer Support
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
- 1 selects between Cool only and Heat-Pump
- 2 is not used
- 3 is not used
- 4 is used to disable Furnace Mode selection.
GE APPLIANCE RARWT Single Zone Smart Thermostat
View all GE APPLIANCES thermostat manual
THANK YOU FOR MAKING GE APPLIANCES A PART OF YOUR RV.
Whether you grew up with GE Appliances, or this is your first, we’re happy to
have you in the family.
We take pride in the craftsmanship, innovation and design that goes into every
GE Appliances product, and we think you will too. Among other things,
registration of your appliance ensures that we can deliver important product
information and warranty details when you need them.
IMPORTANT SAFETY INFORMATION
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE
WARNING
- FIRE AND SHOCK HAZARD
- Always turn off power at the main power supply before installing, cleaning or removing the thermostat.
- Do not use on voltages over 12 VDC. Higher voltages will damage the thermostat and could cause shock or fire hazards.
- All wiring must conform to local and national electrical and building codes.
- Use this thermostat only as described in this manual.
Specifications
Electrical Rating:
12 VDC (Operating Range from 10.5 VDC – 15.5 VDC) Wall Thermostat
Terminations:
0V (GND), Signal (COMMS), +12VDC
Recommended Wire Sizes:
| COMMUNICATION CONNECTIONS|
---|---|---
Ceiling| GEA Smart| 5 Wire| RV-C| RV-C Room| Aux.| Auto Gen
Control| Wall| Analog Wall| Network| Sensor| Furnace| Start
| Thermostat| Thermostat| | Compatible| Connection| Connection
| (RARWT )| | | (RARES1)| |
RARMC2A| X| | | | X|
RAREC1A| X| | X| X| X| X
RAREC2A| X| X| | | X| X
WARNING ELECTRICAL SHOCK HAZARD
Turn off power by removing the fuse or switching the appropriate circuit
breaker to the OFF position before removing the existing thermostat.
Package Contents
- Thermostat on cover
- Thermostat base
- Screws
Tools Required
- Drill with 1/8” bit
- Ballpoint Pen
- Screwdriver
To Remove Existing Thermostat
- Turn off power to the heating and cooling system by removing the fuse or switching off the appropriate circuit breaker (115 VAC and 12VDC)
- Remove cover of old thermostat. This should expose the wires.
- Label the existing wires with the wire labels before removing wires.
- After labeling wires, remove wires from terminal block.
- Remove existing thermostat base from wall.
Installation Instructions
To Install Thermostat and Main Control
IMPORTANT: Thermostat installation must conform to local and national
building and electrical codes and ordinances.
NOTE: Mount the thermostat about five feet above the floor. Do not mount
the thermostat on an outside wall, in direct sunlight, behind a door or in an
area affected by a vent or duct.
-
Turn off power to the heating and cooling system by removing the fuse or switching off the appropriate circuit breaker. (115 VAC and 12VDC).
-
Mount main control box to the mounting template using four screws.
-
Remove three screws from the main control box, allowing the bottom section to hinge open. Control board is now visible and accessible.
-
Route the 115 VAC power cord through the strain relief of the control box. Tighten the strain relief, making sure not to damage the wires.
-
Using provided wire connectors, connect line to black, neutral to white, and ground to green.
-
Using electrical tape or wire nuts, secure the connectors to prevent any potential movement due to vehicle vibration.
-
Route the 6 pin connector through the opening of the hemmed strain relief of the control box. Mate 6 pin connector to the control box’s wire harness.
-
Mate the thermistors to the corresponding interconnects on the main board. These will be bundled with the 6-pin connector in the rooftop unit. For ARC models, one connection will need to be made (indoor coil sensor). For ARH models, an additional connection will need to be made (ambient/outdoor coil sensors).
-
Using provided wire connectors, connect 2 furnace wires (blue), 3 thermostat wires (red, yellow, black), and two 12 VDC battery wires (red and black).
-
Rotate lower section of control box upwards making sure not to crush any wires. Drive three screws, securing he control box closed. The main control install is now complete.
-
Remove the cover from the base by undoing the two plastic snaps on the bottom of the base. A small screwdriver or ballpoint pen can be used to gently depress one snap at a time (reference the figure on page 5).
-
Put thermostat base against the wall where you plan to mount it. Make sure wires will feed through the wire opening in the base of the thermostat.
-
With the base level, mark the placement of the mounting holes.
-
Ensure no other wires are affected by the drilling of 1/8” holes.
-
Using a 1/8” drill bit, drill pilot holes in the locations you have marked for the wood screws.
-
Align thermostat base with mounting holes and feed the control wires through the wire opening.
-
Use supplied screws to mount thermostat base to wall.
-
Insert stripped, labeled wires in matching wire terminals and tighten terminal screws once properly aligned. See the “Wiring Diagrams” section of this manual.|
CAUTION
Make sure exposed portion of wires does not touch other wires. -
Gently tug each wire to be sure of proper connection. Verfiy that each wire is connected to the proper terminal.
-
For Heat Pump models (ARH15AAC_), flip switch #1 to the “ON” position (see figure on page 12). Additionally, if your unit will not be connected to a furnace, furnace mode can be disabled by toggling switch #4 to the “on” position (see figure on page 12).
-
Reattach the thermostat cover by aligning the cover and snapping the bottom in place.
-
Turn on power to the system at the main service panel.
-
Test thermostat operation as described in the “Testing the thermostat” section.
Controls (RARWT )
-
Mode Button
Use this button to toggle between the following modes.
OFF – The air conditioner and RV’s furnace will not operate.
FAN ONLY – The fan will operate to circulate air.
COOL – The air conditioner will operate to lower the RV temperature
NOTE: only use HEAT-PUMP modes with outdoor model ARH15AAC (see RV Air- Conditioner Owner’s Manual).
Enable HEAT-PUMP modes by turning ON DIP switch #1 lo-cated on the back side of the thermostat (see Wiring Diagram)
**Controls and Operating Functions (RARWT )
HEAT PUMP ONLY – the unit will operate the heat-pump to raise the RV temperature. NOTE: if the outdoor ambient drops below 25°F (-4°C), the heat- pump will be disabled.
HEAT PUMP + FURNACE the unit will first operate the heat-pump to conserve propane. If the RV temperature drifts further than 3°F from the setpoint, then the RV’s furnace will be turned ON.
NOTE: the furnace will automatically turn ON, if the outdoor temperature drops below 25°F (-4°C) or if the Heat-Pump begins a defrost.
FURNACE ONLY –** the RV’s furnace will operate to raise the RV temperature. This mode can be disabled by toggling switch #4 on the thermostat to the “ON” position. -
Fan Button
Use this button to toggle between fan speeds and fan modes.
FAN ON – the fan will run even when the set point has been reached.
AUTO FAN _ the fan will turn off once the set point has been reached.
-
Temperature Selection Buttons
Use these buttons to raise and lower the set point. To change between Fahrenheit (°F) and Celsius (°C), hold both “TEMP +” and “TEMP –” at the same time for 2 seconds.
Control and Operating Functions (RAREC1A)
If Switch #5 is ON (RV-C Virtual T.Stat Method), an RARES1A room sensor kit will be required.
Control and Operating Functions (RAREC2A)
switch 1 specifies default fan speed in HP Mode if GL or GH is not specified
switch 2 specifies if a “Y” signal is required for HP Mode.
On Board Diagnostics (RARWT )
Low Voltage Detection:
****If the 12VDC drops below 10.5V, the thermostat will switch to “OFF” mode
and flash “Lo”.
When voltage exceeds 10.5V, the display will show a constant “Lo” and remain
in “OFF” mode until a different mode is reselected by the user.
A/C Freeze-Up Prevention:
In COOL mode, a flashing snowflake icon indicates that the indoor coil is near
freezing, and that the compressor was turned off.
Recommend increasing airflow by cleaning the filter and opening vents.
Heat-Pump Auto-Defrost:
In HEAT-PUMP modes, a flashing HEAT-PUMP icon indicates that the unit is
performing an auto-defrost.
In HEAT-PUMP+FURNACE mode, while auto-defrosting, the unit will use the
furnace.
Heat-Pump Lockout:
In HEAT-PUMP ONLY mode, a flashing HEAT-PUMP icon AND 25°F (-4°C) indicates
that the outdoor temperature dropped below 25°F (-4°C) and the Heat-Pump is
locked out.
Recommended when expecting temperatures below 25°F (-4°C) to use HEAT-
PUMP+FURNACE or FURANCE ONLY mode.
On Board Diagnostics (RARWT )
Heat-Pump Over Temperature:
In HEAT-PUMP modes, a flashing HEAT-PUMP icon AND 99°F (99°C) indicates that
the indoor coil reached a temperature above 135°F (58°C) and the compressor
was shut off.
Recommended to increase airflow by cleaning the filter and opening vents.
Fault Codes (RARWT )
Fault Codes
| Display Code| $ႇHFWHG
Sensor
| Potential Cause
All Models
| F1| Indoor Coil| Unplugged Sensor or Temp less than -22°F (-30°C)
F2| Indoor Coil| Shorted wires or temp greater than 149°F (65°C)
Heat Pump Models
| F3| Outdoor Coil| Unplugged Sensor or Temp less than -22°F (-30°C)
F4| Outdoor Coil| Shorted wires or temp greater than 149°F (65°C)
Dip Switch 1 ON
| F5| Outdoor Temp| Unplugged sensor, or Dip Switch 1 set to “ON” for AC only
model. Temp less than -22°F (-30°C)
F6| Outdoor Temp| Shorted wires or temp greater than 149°F (65°C)
| F7| Thermostat| Unplugged Sensor or Temp less
| | Room Sensor| than -22°F (-30°C)
All Models| F8| Thermostat Room Sensor| Shorted wires or temp greater than
149°F (65°C)
F9| Signal Wire| Thermostat signal wire is
| —| | unplugged or shorted (Not
| FC| | communicating to the main
| | | control)
Wiring Diagrams
Table 1: terminals for three wires 1-stage heat / 1-stage cool system.
RARWT_ _DIP Switches
-
1 selects between Cool only and Heat-Pump
-
2 is not used
-
3 is not used
-
4 is used to disable Furnace Mode selection.
This is for installs where a furnace is not connected to the RVAC control.
Testing the Thermostat
Once the thermostat is installed, it should be tested for functionality.
NOTE: Before testing the thermostat, press the Fan Auto/On button until
the display shows the Auto position.
Fan Test
- Toggle Mode button to Fan ON position.
- Fan turns on.
- Toggle between low and high fan speeds with the FAN button.
- Speed should adjust accordingly
Cool Test
- Toggle Mode button until Cool mode is on. Cool mode screen is displayed.
- Adjust set temperature so it is 5 degrees below room temperature.
- Air conditioning should come on within a few seconds.
- Adjust the set temperature so it is 2 degrees above the room temperature and the A/C should turn off. Note: There is a 3 minute time delay and a 3 minute minimum run time for the compressor when it turns on/off.
Heat Pump Test (ARH models only)
- Toggle Mode button until Heat Pump mode is on. Heat Pump screen is displayed.
- Adjust set temperature so it is 5 degrees above room temperature.
- Heating should come on within a few seconds.
- Adjust the set temperature so it is 2 degrees below the room temperature and the Heat Pump should turn off. NOTE: There is a 3 minute time delay and a 3 minute minimum run time for the compressor when it turns on/off.
Furnace Test
- Toggle mode button until furnace mode is active. Furnace mode screen is displayed.
- Adjust set temperature so it is 5 degrees above room temperature. Within a few seconds, the furnace should initiate its startup procedure.
- Adjust the set temperature so it is 2 degrees below the room temperature and the heat should turn off. Note: Depending on the model of furnace used, there may be a delay in engaging and disengaging the furnace.
Troubleshooting Tips
Problem | Solution |
---|---|
Display is blank | Check for 12VDC; display is blank when 12V is not present. |
All thermostat buttons are non-responsive | Verify that the 12VDC is present; |
the unit will not operate when the voltage is below 10.5V.
Fan and Compressor will not turn ON| Verify that 115VAC is present.
Fan does not turn ON, but the Compressor does turn ON| WITH POWER REMOVED,
verify
that nothing is obstructing the fan blade, that it spins freely.
Check the 5 amp Fuse on the board
Fan runs continuously| Check Fan Mode. If set to FAN ON, the fan will run
continuously.
Room Temperature does not match Setpoint when WKH XQLW VKXWV Rႇ| Verify proper
installation per installation instructions (pg. 5 … not on exterior wall or in
direct VXQOLJKW« «LQ DQ DUHD DႇHFWHG E\
a vent or duct…)
Compressor does not turn ON immediately when changing Modes or Setpoint| This is normal, there is a 3 minute OFF timer preventing the
compressor from being turned OFF and right back ON.
Fan does not turn ON immediately when changing Modes or Setpoint| In Heat-Pump
mode, if Auto Fan is selected, the fan will not turn ON until the compressor
turns ON after the 3 minute OFF timer.
F5 Flashes on the Wall Thermostat| With a Cool Only model, check that DIP
Switch #1 on the back side of the wall thermostat is turned OFF. (see Wiring
Diagram)
With a Heat-Pump model, check to see if the outdoor temperature sensor is unplugged or damaged.
Thermostat Limited Warranty
Staple your receipt here.
Proof of the original purchase date is needed to validate the warranty.
For The Period Of:
Two Years
From the date of the original purchase
GE Appliances Will Replace:
Full Replacement of the thermostat which fails due to a defect in materials or
workmanship.
What GE Appliances Will Not Cover:
- Service trips to your location.
- Improper installation. If you have an installation problem, contact your installer. You are responsible for providing adequate electrical connections to the product.
- Failure of the product resulting from modifications to the product or due to unreasonable use, including failure to provide reasonable and necessary maintenance.
- In commercial locations, labor necessary to move the unit, after it has been initially installed, to a location where it is accessible for service by an individual technician; or, if the instructions included in this manual have been disregarded.
- Replacement of location fuses or the resetting of circuit breakers.
- Damage to the product caused by improper power supply voltage, accident, fire, floods or acts of God.
- Incidental or consequential damage caused by possible defects with this thermostat.
EXCLUSION OF IMPLIED WARRANTIES— Your sole and exclusive remedy is product exchange as provided in this Limited Warranty. Any implied warranties, including the implied warranties of merchantability or fitness for a particular purpose, are limited to one year or the shortest period allowed by law.
This limited warranty is extended to the original purchaser and any succeeding
owner for products purchased for use within the USA and Canada. In Alaska, the
limited warranty excludes the cost of shipping or service calls to your site.
Some states or provinces do not allow the exclusion or limitation of
incidental or consequential damages. This limited warranty gives you specific
legal rights, and you may also have other rights which vary from state to
state or province to province. To know what your legal rights are, consult
your local, state or provincial consumer affairs office or your state’s
Attorney General.
Warrantor: GE Appliance, a Haier company. Louisville, KY 40225
Consumer Support
GE Appliances Website
Have a question or need assistance with your appliance? Try the GE Appliances
Website 24 hours a day, any day of the year! You can also shop for more great
GE Appliances products and take advantage of all our on-line support services
designed for your convenience. In the US:
GEAppliances.com
Register Your Appliance
Register your new appliance online at your convenience! Timely product
registration will allow for enhanced communication and prompt service under
the terms of your warranty, should the need arise. You may also mail in the
pre-printed registration card included in the packing material. In the US:
GEAppliances.com/register
Schedule Service
Call 1-877-540-7837 during normal
business hours.
Extended Warranties
Purchase a GE Appliances extended warranty and learn about special discounts
that are available while your warranty is still in effect. You can purchase it
on-line anytime. GE Appliances Services will still be there after your
warranty expires. In the US: GEAppliances.com/extended-
warranty or call 800.626.2224
during normal business hours.
Remote Connectivity
For assistance with wireless network connectivity (for models with remote
enable),
visit our website at GEAppliances.com/connected-home-smart-
appliances or call
800.220.6899 in the US.
Parts and Accessories
Individuals qualified to service their own appliances can have parts or
accessories sent directly to their homes
(VISA, MasterCard and Discover cards are accepted). Order on-line today 24
hours every day.
In the US: GEApplianceparts.com or by phone at
877.959.8688 during normal business hours.
Instructions contained in this manual cover procedures to be performed by any
user. Other servicing generally should be referred to qualified service
personnel. Caution must be exercised, since improper servicing may cause
unsafe operation.
Contact Us
If you are not satisfied with the service you receive from GE Appliances,
contact us on our Website with all the details including your phone number, or
write to:
General Manager, Customer Relations | GE Appliances, Appliance Park |
Louisville, KY 40225
GEAppliances.com/contact
GE APPLIANCE RARWT Single Zone Smart Thermostat Owner’s Manual
References
- Appliance Parts, Accessories & Water Filters | GE Appliances
- Contact Us or Get Help with Questions | GE Appliances
- Bodewell Care Protection Plans
- GEAppliances.com/register
- Appliance Repair Service and Support | GE Appliances
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>