finder 22.32 Modular Contactor 25A Instructions

June 6, 2024
finder

finder 22.32 Modular Contactor 25A

MODULAR CONTACTORS 25 A

Contact gap ≥ 3 mm for NO contacts only; NC contacts ≥ 1.5 mm. Compliant with EN 61095: 2009. AC/DC silent coil (with varistor protection

CONNECTION DIAGRAM

finder 22.32 Modular Contactor 25A
1

OUTLINE DRAWINGS

FRONT VIEW

022.33 2 NO (DPST- NO)
022.35 1 NO (SPST- NO) + 1 NC (SPST- NC)

finder 22.32 Modular Contactor 25A 53| Ith 6 A

AC15 700 VA

(230 V AC)

A = Selector (22.32.0.xxx.xx40)

The three-position manual selector has the following functions:

  • ON position
    The contacts are latched in the operating state (NO contacts -closed and NC contacts – open), the mechanical indicator is visible in its window, the LED is not illuminated.

  • AUTO position
    The state of contacts, mechanical indicator and LED follow the coil supply voltage.

  • OFF position
    Even if terminals A1 – A2 are supplied with rated voltage, the coil is not energized, and so the contacts remain in the non-operated state, the mechanical indicator is not visible and the LED is not illuminated.

    • B = LED
    • C = Mechanical indicator

ACCESSORIES

22.32.0.xxx.xxx0

| UN (12 – 24 – 48 – 60 – 120 – 230)V AC (50/60 Hz) / DC Umin– Umax (0.8-1.1)UN

P 2 VA / 2.2 W

finder 22.32 Modular Contactor 25A 53

|

22.32…x3x0

|

22.32…x5x0         22.32…x4x0

25 A 440 V AC (EN 61095)
AC1/ AC-7a (250 V)| 6250 VA
AC3/ AC-7b| 10 A
AC5a (250 V)| 15 A
AC15 (230 V AC)| 1800 VA
M (230 V AC)| 1 kW
DC1 (30 /110/ 220)V| (25/5 /1)A
AC-7c| –          (10 A – 22.324xx0 )
| 800 W (2000 W – 22.32…4xx0 )
| 300 W (800 W – 22.32…4xx0 )
CFL–LED| 100 W (200 W – 22.32…4xx0 )
|

(–20…+50)°C

IP20

  • Auxiliary contact module available, “Quick assembly” with the main contactor 022.33/022.35
  • It is not possible to assemble the auxiliary module on 22.32.0.xxx.x4x0 (2 NC versions)

OTHER DATA
It is suggested an air gap of 9 mm between adjacent relays for installations and working conditions close to the limit (that is, ambient temperature 40°C, coil operated for a prolonged period of time, all contacts loaded with current

20 A).

LIST

  • Open Type Device – Pollution degree 2 Installation Environment
  • Maximum Surrounding Air Temperature 50°C
  • The minimum distance among modular contactors 9 mm
    • Field Wiring Terminals:
    • Use 60/75°C copper conductor only and wire ranges
    • No. 10-12-18-24 AWG, Solid only
    • Terminal tightening torque 7.0 lb.in. (0.8 Nm)
  • Suitable for use on a circuit capable of delivering not more than 5000 ARMS Symmetrical, 240 V ac, when protected by Listed Cartridge Fuses, rated K5 Class (No Current Limiting, Non-Time Delay, max 600 Vac, 30 A, 50 kA A.I.C.) or RK5
    • Class (Current Limiting, Time Delay, max 600 Vac, 15 A, 50 kA A.I.C.) or equivalent
  • For use in a circuit protected by Type1 or Type2 Surge Protective Devices with “Max Voltage Protection” rating of 3.7 kVpk and
    • “Minimum Nominal Discharge Current” of 5 kA (at 6 kV)

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals