nuaire XBC 75 Ecosmart Classic Basic Control Instruction Manual

June 6, 2024
Nuaire

Nuaire XBC 75 Ecosmart Classic Basic Control

SAFETY INFORMATION

  • The provision of the electrical supply and the connection of the unit to the electrical supply must be carried out by a qualified electrician.
  • Isolate from the power supply before removing any covers. During installation/maintenance ensure all covers are fitted before switching on the mains supply.
  • All-pole disconnection from the mains as shown in the wiring diagram must be incorporated within the fixed wiring and shall have a minimum contact separation of 3mm in accordance with the latest edition of the wiring regulations.
  • This unit must be earthed.
  • Ducting must be securely fixed with screws to the spigot to prevent access to live parts. Duct runs terminating close to the fan must be adequately protected by suitable guards.
  • This appliance should not be used by children or persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning the safe use of the appliance by a person responsible for their safety. Children shall not play with the appliance. Cleaning and user maintenance shall not be carried out by children.

General Warning
Signifies a general warning regarding hazard specified by supplementary information.
Electric Shock
This unit must be completely electrically isolated before any panels are removed. Check mains supply and control connections.
Rotating Parts
This unit contains fast-moving rotational parts which may start automatically. It is the sole responsibility of the installer to adequately guard these components.
Refer To The Instruction Manual
Read and understand the installation and maintenance manual before installing, operating, or maintaining this product.

Important Information

This manual contains important information on the safe and appropriate assembly, transport, commissioning, operation, maintenance, disassembly and simple troubleshooting of the product. While the product has been manufactured according to the accepted rules of current technology, there is still a danger of personal injury or damage to equipment if the following general safety instructions and the warnings contained in these instructions are not complied with.

  • Read these instructions completely and thoroughly before working with the product.
  • Keep these instructions in a location where they are accessible to all users at all times.
  • Always include the operating instructions when you pass the product on to third parties.

Personal Protective Equipment

The following minimum Personal Protective Equipment (PPE) is recommended when interacting with Nuaire products:

  • Protective Steel Toed Shoes – when handling heavy objects.
  • Full Finger Gloves (Marigold PU800 or equivalent) – when handling sheet metal components.
  • Semi Fingerless Gloves (Marigold PU3000 3DO or equivalent) – when conducting light work on the unit requiring tactile dexterity.
  • Safety Glasses – when conducting any cleaning/cutting operation or exchanging filters.
  • Reusable Half Mask Respirators – when replacing filters that have been in contact with a normal room or environmental air. Nuaire would always recommend a site-specific risk assessment by a competent person to determine if any additional PPE is required.

INTRODUCTION

The information contained in this document provides details of installation, operation, and maintenance for installers and users of the XBOXER XBC75 & 85 Supply and Extract Ventilation Units with Heat Recovery. This supply and extract air handling unit range comprises a combination of high-efficiency centrifugal fans with EC motors, a counterflow design plate heat exchanger, filters, optional heaters (LPHW and Electric), and a casing with high mass acoustic treatment. The one-piece ventilation unit shall be constructed with double skinned Aluzinc panels on an aluminum Pentapost frame with integral acoustic mineral fiber ensuring low breakout noise levels. The unit shall incorporate a high-efficiency aluminum counterflow plate heat exchanger matrix with a thermal efficiency of up to 92%, fitted with a segmented 100% bypass facility and actuator (patent app. for) operating under automatic control.

  • A range of matched, side by side internal and external attenuators
  • (Horizontal units) and double-deck internal and external attenuators (Vertical units) with a similar construction method to that of the unit are available.
  • General information regarding performance and specifications for the equipment may be obtained from our Technical Literature, and/or project-specific documentation.

XBC Unit Code Description

1| 2| | 3| | 4| 5| | 7| | 8
---|---|---|---|---|---|---|---|---|---|---
XBC| 75| | H| | L| ES| | R| | WP

  • Range: XBOXER
  • Unit Size: 75, 85
  • Unit Layout: H = Horizontal  V = Vertical
  • Heating Type: E = Electric  L = LPHW  N = No Heating
  • Control Type: BC = Basic  ES = Ecosmart
  • Unit Handing: No Affix = Left Hand Arrangement R = Right Hand Arrangement
  • Unit Roof: No Suffix = Standard Unit (No Roof)  WP = Twin Pitched Roof (Factory Fitted)

Matched Attenuator Code Description

1 2 3 4 5 6
XBC 75 H SIL 900 WP
  • Range: XBOXER
  • Unit Size: 75, 85
  • Unit Layout: H = Horizontal V = Vertical
  • Ancillary Type: SIL = Attenuator
  • Attenuator Length: 900 = 900mm
  • Unit Roof: No Suffix = Standard Unit (No Roof)
  • WP = Twin Pitched Roof (Factory Fitted)

DELIVERY

Receiving Equipment

All equipment is inspected prior to despatch and leaves the factory in good condition. Upon receipt of the equipment, an inspection should be made and any damage indicated on the delivery note.

Particulars of damage and/or incomplete delivery should be endorsed by the driver delivering the goods before offloading by the purchaser. No responsibility will be accepted for damage sustained during the offloading from the vehicle or on the site thereafter. All claims for damage and/or incomplete delivery must be reported to Nuaire within two days of receipt of the equipment.

Vehicle Offloading / Equipment Handling

XBC unit sections will be delivered to the site in one section. The weight of the unit modules and palletized items is displayed on the unit rating plate or on the packaging. Some of the modules have an ‘uneven’ weight distribution, and this will be indicated by labeling where appropriate. Ensure that lifting and handling equipment is adequately rated. Offloading and positioning of the equipment is the responsibility of the purchaser.

Spreaders should be used when lifting with slings to avoid damage to the casings. Care must be taken to ensure that slings are correctly positioned to avoid crushing and twisting of the unit castings. Where channels and/or support frames are bolted to the underside of the unit casing, slings or fork- lift arms should be positioned to locate in the apertures in the channels. If Lifting Eyes have been supplied/fitted it is recommended that they are used. CAUTION: The XBC75 & 85 fan units have an uneven weight distribution, please refer to the unit labeling before Lifting / offloading the unit.

nuaire XBC 75 Ecosmart Classic Basic Control-Fig1

Storage

The equipment must be stored in a dry, internal location. Ductwork connection apertures shall be sealed against the ingress of dust, water, and vermin. If the storage period is to exceed two months, contact Nuaire for guidance on the appropriate “mothballing” procedures. Do not stack units, modules, or components.

DIMENSIONS & WEIGHTS

Horizontal Units (XBC75-H, XBC85-H)

The unit is designed for side access as standard and must be installed with a minimum clearance of 650mm from a wall or barrier This will provide access to filters, coil, fan, heat exchanger, condensate tray, and pump. All models: The weather roof is part of the unit code and is factory fitted only. Example: XBC85-V-LATWP. Note: Codes with ‘R’ i.e. (XBC75-G4B-HR) refer to right-hand unit versions.

Horizontal Unit (XBC75-H, XBC85-H) Ancillaries

Weather Kits

Ref. No.

|

XBC Ancillary Code

|

Description

| Dimensions (mm)|

Weight (kg)

---|---|---|---|---
Width| Height| Length
2| XBC75-H-RT| Weather Terminal For Horizontal XBC75 Units| 940| 740| 700| 10
2| XBC85-H-RT| Weather Terminal For Horizontal XBC85 Units| 940| 740| 700| 10

Filter Module Options

Ref. No.|

XBC Ancillary Code

|

Description

| Dimensions (mm)| Weight (kg)
---|---|---|---|---
Width| Height| Length
3| XBC75-F7B/G4P-H| F7 Bag / G4 Panel For Horizontal XBC75 Units| 2000| 876| 600| 115
3| XBC85-F7B/G4P-H| F7 Bag / G4 Panel For Horizontal XBC85 Units| 2000| 876| 600| 115
3| XBC75-F7B/G4P-HR| F7 Bag / G4 Panel For Right Handed Horizontal XBC75 Units| 2000| 876| 600| 115
3| XBC85-F7B/G4P-HR| F7 Bag / G4 Panel For Right Handed Horizontal XBC85 Units| 2000| 876| 600| 115
3| XBC75-G4B-H| G4 Bag For Horizontal XBC75 Units| 2000| 1001| 600| 115
3| XBC85-G4B-H| G4 Bag For Horizontal XBC95 Units| 2000| 1001| 600| 115
3| XBC75-G4B-HR| G4 Bag For Right Handed Horizontal XBC75 Units| 2000| 1001| 600| 115
3| XBC85-G4B-HR| G4 Bag For Right Handed Horizontal XBC85 Units| 2000| 1001| 600| 115
3| XBC75-F7B/G4P-HWP| F7 Bag / G4 Panel With Twin Pitched Roof For Horizontal XBC75 Units| 2000| 876| 600| 117
3| XBC85-F7B/G4P-HWP| F7 Bag / G4 Panel With Twin Pitched Roof For Horizontal XBC85 Units| 2000| 876| 600| 117
3| XBC75-F7B/G4P-HRWP| F7 Bag / G4 Panel With Twin Pitched Roof For Right Handed Horizontal XBC75 Units| 2000| 876| 600| 117
3| XBC85-F7B/G4P-HRWP| F7 Bag / G4 Panel With Twin Pitched Roof For Right Handed Horizontal XBC85 Units| 2000| 876| 600| 117
3| XBC75-G4B-HWP| G4 Bag with weather roof For Horizontal XBC75 Units| 2000| 1001| 600| 117
3| XBC85-G4B-HWP| G4 Bag with weather roof For Horizontal XBC85 Units| 2000| 1001| 600| 117
3| XBC75-G4B-HRWP| G4 Bag with weather roof For Right Handed Horizontal XBC75 Units| 2000| 1001| 600| 117
3| XBC85-G4B-HRWP| G4 Bag with weather roof For Right Handed Horizontal XBC75 Units| 2000| 1001| 600| 117

Dampers

Ref. No.|

XBC Ancillary Code

|

Description

| Dimensions (mm)| Weight (kg)
---|---|---|---|---
Width| Height| Length
4| XBC75-H-MD24V| Motorized dampers 24V for Horizontal XBC75 Ecosmart model (ES) Units| 840| 700| 165| 20
4| XBC85-H-MD24V| Motorized dampers 24V for Horizontal XBC85 Ecosmart model (ES) Units| 840| 700| 165| 20
4| XBC75-H-MD-NC| Damper no actuator with extended spindle for Horizontal XBC75 Units| 840| 700| 165| 20
4| XBC85-H-MD-NC| Damper no actuator with extended spindle for Horizontal XBC85 Units| 840| 700| 165| 20

Matching Attenuator Pairs (Side By Side, Supplied As One Piece)

Ref. No.|

XBC Ancillary Code

|

Description

| Dimensions (mm)| Weight (kg)
---|---|---|---|---
Width| Height| Length
5| XBC75-H-SIL900| Side by side silencer with base frame for Horizontal XBC75 Units| 2000| 876| 900| 180
5| XBC85-H-SIL900| Side by side silencer with base frame for Horizontal XBC85 Units| 2000| 876| 900| 190
5| XBC75-H-SIL900-WP| Side by side silencer with base frame and weather roof for Horizontal XBC75 Units| 2000| 1001| 900| 180
5| XBC85-H-SIL900-WP| Side by side silencer with base frame and weather roof for Horizontal XBC85 Units| 2000| 1001| 900| 190

Frost Coils (Side By Side, Supplied As One Piece)

Ref. No.|

XBC Ancillary Code

|

Description

| Dimensions (mm)| Weight (kg)
---|---|---|---|---
Width| Height| Length
5| XBC75-FCL-LNC-H| LPHW side by side module with base frame for basic control units (BC)| 2000| 876| 600| 113
5| XBC85-FCL-RNC-H| LPHW side by side module with base frame for basic control units (BC)| 2000| 876| 600| 113
5| XBC75-FCL-LES-H| LPHW side by side module with base frame for Ecosmart control units (ES)| 2000| 876| 600| 155
5| XBC85-FCL-LES-H| LPHW side by side module with base frame for Ecosmart control units (ES)| 2000| 876| 600| 155
5| XBC75-FCE-LNC-H| Electric side by side module with base frame for basic control units (BC)| 2000| 876| 600| 113
5| XBC85-FCE-RNC-H| Electric side by side module with base frame for basic control units (BC)| 2000| 876| 600| 113
5| XBC75-FCE-LES-H| Electric side by side module with base frame for Ecosmart control units (ES)| 2000| 876| 600| 121
5| XBC85-FCE-LES-H| Electric side by side module with base frame for Ecosmart control units (ES)| 2000| 876| 600| 121

Vertical Units (XBC75-V, XBC85-V)

The unit is designed for side access as standard and must be installed with a minimum clearance of 650mm from a wall or barrier. This will provide access to filters, coil, fan, heat exchanger, condensate tray, and pump. All models: The weather roof is part of the unit code and is factory fitted only. Example: XBC85-V-LATWP. Note: Codes with ‘R’ i.e. (XBC75-G4B-HR) refer to right hand unit versions.

Vertical Units (XBC75-V, XBC85-V) Ancillaries

Weather Kits

Ref. No.|

XBC Unit Code

|

Description

| Dimensions (mm)| Weight (kg)
---|---|---|---|---
Width| Height| Length
1| XBC75-V--WP| Vertical XBC75 Unit With Twin Pitched Roof| 954| 1476| 2500| 630
1| XBC75-V-
-R-WP| Right Handed Vertical XBC75 Unit With Twin Pitched Roof| 954| 1476| 2500| 630
1| XBC85-V--WP| Vertical XBC85 Unit With Twin Pitched Roof| 1000| 1741| 3000| 780
1| XBC85-V-
-R-WP| Right Handed Vertical XBC85 Unit With Twin Pitched Roof| 1000| 1741| 3000| 780

Weather Terminals

Ref. No.

|

XBC Ancillary Code

|

Description

| Dimensions (mm)|

Weight (kg)

---|---|---|---|---
Width| Height| Length
2| XBC75-RT| Weather Terminal For Vertical XBC75 Units| 842| 570| 610| 8
2| XBC85-RT| Weather Terminal For Vertical XBC85 Units| 940| 740| 700| 10

Filter Module Options

Ref. No.|

XBC Ancillary Code

|

Description

| Dimensions (mm)| Weight (kg)
---|---|---|---|---
Width| Height| Length
3| XBC75-F7B/G4P| F7 Bag / G4 Panel For Vertical XBC75 Units| 954| 1416| 600| 90
3| XBC85-F7B/G4P| F7 Bag / G4 Panel For Vertical XBC85 Units| 1000| 1676| 600| 105
3| XBC75-F7B/G4P-R| F7 Bag / G4 Panel For Right Handed Vertical XBC75 Units| 954| 1416| 600| 90
3| XBC85-F7B/G4P-R| F7 Bag / G4 Panel For Right Handed Vertical XBC85 Units| 1000| 1676| 600| 105
3| XBC75-G4B| G4 Bag For Vertical XBC75 Units| 954| 1416| 600| 90
3| XBC85-G4B| G4 Bag For Vertical XBC95 Units| 1000| 1676| 600| 105
3| XBC75-G4B-R| G4 Bag For Right Handed Vertical XBC75 Units| 954| 1416| 600| 90
3| XBC85-G4B-R| G4 Bag For Right Handed Vertical XBC85 Units| 1000| 1676| 600| 105
3| XBC75-F7B/G4P-WP| F7 Bag / G4 Panel With Twin Pitched Roof For Vertical XBC75 Units| 954| 1476| 600| 92
3| XBC85-F7B/G4P-WP| F7 Bag / G4 Panel With Twin Pitched Roof For Vertical XBC85 Units| 1000| 1741| 600| 107
3| XBC75-F7B/G4P-RWP| F7 Bag / G4 Panel With Twin Pitched Roof For Right Handed Vertical XBC75 Units| 954| 1476| 600| 92
3| XBC85-F7B/G4P-RWP| F7 Bag / G4 Panel With Twin Pitched Roof For Right Handed Vertical XBC85 Units| 1000| 1741| 600| 107
3| XBC75-G4B-WP| G4 Bag with weather roof For Vertical XBC75 Units| 954| 1476| 600| 92
3| XBC85-G4B-WP| G4 Bag with weather roof For Vertical XBC85 Units| 1000| 1741| 600| 107
3| XBC75-G4B-RWP| G4 Bag with weather roof For Right Handed Vertical XBC75 Units| 954| 1476| 600| 924
3| XBC85-G4B-RWP| G4 Bag with weather roof For Right Handed Vertical XBC75 Units| 1000| 1741| 600| 107

Dampers

Ref. No.|

XBC Ancillary Code

|

Description

| Dimensions (mm)| Weight (kg)
---|---|---|---|---
Width| Height| Length
4| XBC75-V-MD24V| Motorized dampers 24V for Vertical XBC75 Ecosmart model (ES) Units| 620| 560| 165| 14
4| XBC85-V-MD24V| Motorized dampers 24V for Vertical XBC85 Ecosmart model (ES) Units| 840| 700| 165| 20
4| XBC75-V-MD-NC| Damper no actuator with extended spindle for Vertical XBC75 Units| 620| 560| 165| 14
4| XBC85-V-MD-NC| Damper no actuator with extended spindle for Vertical XBC85 Units| 840| 700| 165| 20

Matching Attenuator Pairs (Double Deck, Supplied As One Piece)

Ref. No.|

XBC Ancillary Code

|

Description

| Dimensions (mm)| Weight (kg)
---|---|---|---|---
Width| Height| Length
5| XBC75-V-SIL900| Double-deck silencer with base frame for Horizontal XBC75 Units| 954| 1416| 900| 180
5| XBC85-V-SIL900| Double-deck silencer with base frame for Horizontal XBC85 Units| 1000| 1676| 900| 200
5| XBC75-V-SIL900-WP| Double-deck silencer with base frame and weather roof for Horizontal XBC75 Units| 954| 1476| 900| 185
5| XBC85-V-SIL900-WP| Double-deck silencer with base frame and weather roof for Horizontal XBC85 Units| 1000| 1741| 900| 205

Frost Coils (Double Deck, Supplied As One Piece)

Ref. No.|

XBC Ancillary Code

|

Description

| Dimensions (mm)| Weight (kg)
---|---|---|---|---
Width| Height| Length
5| XBC75-FCL-LNC-V| LPHW double-deck module with base frame for basic control units (BC)| 954| 1416| 600| 115
5| XBC85-FCL-RNC-V| LPHW double-deck module with base frame for basic control units (BC)| 1000| 1676| 600| 120
5| XBC75-FCL-LES-V| LPHW double-deck module with base frame for Ecosmart control units (ES)| 954| 1416| 600| 115
5| XBC85-FCL-LES-V| LPHW double-deck module with base frame for Ecosmart control units (ES)| 1000| 1676| 600| 120
5| XBC75-FCE-LNC-V| Electric double-deck module with base frame for basic control units (BC)| 954| 1416| 600| 100
5| XBC85-FCE-RNC-V| Electric double-deck module with base frame for basic control units (BC)| 1000| 1676| 600| 105
5| XBC75-FCE-LES-V| Electric double-deck module with base frame for Ecosmart control units (ES)| 954| 1416| 600| 100
5| XBC85-FCE-LES-V| Electric double-deck module with base frame for Ecosmart control units (ES)| 1000| 1676| 600| 105

ACCESS CONCEPTS

In this product range, several unique concepts have been implemented with a view to simplifying the installation design. Isolate before removing any panels

  • The unit must be installed with at least 650mm clearance from a wall/barrier. With this absolute minimum clearance, the unit may be connected to the power supply and control connection. 1000mm clearance is required to remove the LPHW coil and electric heater.
  • With this clearance, unit filters may be changed, and the fans coils, heat exchanger, and condensate tray may be inspected and cleaned if necessary.
  • The LPHW and Electrical heater settings, coil bleed and drain, and all other control adjustments are similarly accessible.
  • Side access, where possible, is preferred in all cases in terms of safe working access to the equipment under the CDM regulations.
  • Note, however, that access in the situation is difficult and additional time should be allocated. For convenience, it is preferred that wherever possible, this minimum access provision is not adopted, and it is recommended that a minimum of around 600mm clearance (as stated in ADF 2010) is allowed.
  • Where these arrangements are not suitable, the Consultant’s and Contractor’s project-specific requirements will always be accommodated where possible.

Horizontal Unit Access

Horizontal Unit Overview With Lid Removed Showing Air Paths

Vertical Unit Access

9 Vertical Unit Overview With Lid Removed Showing Air Paths

MECHANICAL INSTALLATION

  • Installation must be completed by competent persons, in accordance with good industry practice, and should conform to all governing and statutory bodies i.e. IEE, CIBSE, etc.
  • The unit will be labeled with the direction of airflow. The direction convention must be observed during installation.
  • The unit may only be operated in its intended horizontal installation plane. The unit MUST be fully leveled during installation (this is essential to ensure that condensate drains correctly).
  • The units are heavy and should be mounted using suitable methods of support. The supporting structure must be assessed for structural suitability.
  • If these units are being fitted into a ceiling void a suitable support structure must be provided under each unit, the base frame provided is NOT suitable for this purpose.
  • LPHW Coils, if fitted, are tested during manufacture to 16 Bar (using dry compressed air). Coil and valve assemblies are similarly tested to 10 Bar. Operation of standard equipment is rated at PN6,
  • if the intended system requires higher operating pressures; please contact the Nuaire Technical department for advice.
  • Electrical connections to the unit shall be made in accordance with the appropriate product; and installation wiring diagrams, and shall use appropriately sized and rated cables.
  • Only the prepared apertures in the unit casing may be used for cable entry. Do not drill or cut the unit casing for this purpose. Cable access points are provided at the ends of the control enclosure.
  • If the control is rotated to aid the connection of cables, please ensure that sufficient flexibility is provided in the final connection run.
  • To avoid conflict with the unit access panels, it is recommended that electrical and plumbing service connections to the unit are run at 90 degrees to the main airflow axis.
  • Control circuit connections must be segregated (i.e. routed separately) from power connections.
  • The unit rating label shows the maximum electrical load of the equipment. Connections to the unit may include single-phase supply connections and a variety of control circuits.
  • Only the prepared apertures in the unit casing may be used for cable entry. Do not drill or cut the unit casing for this purpose.
  • The equipment must be earthed and earth-bonded. Means of local isolation for maintenance purposes are generally required (by others). Ensure that all mains connections are isolated.
  • Heat recovery components and modules that incorporate cooling coils may produce condensation during use. An insulated drip tray and condensate pump is provided. The drain connection must be connected to a suitable drainage point (Figures 11 & 12).

Condensate Pump

The condensate pump incorporates an alarm function. If the water level in the condensate tray exceeds a maximum level (for example, as a result of the discharge tube becoming blocked or frozen), the alarm contact will open. This contact is internally connected to the heat exchanger bypass actuator, and the unit will automatically be placed into bypass mode, preventing further condensate production. The unit operation will otherwise be unaffected.

  • Maximum flow rate = 12 l/h
  • Maximum head = 20m Vertical, 100m Horizontal
  • Pipe Connection size (Condensate) XBOXER XBC = 8 mm

COMMISSIONING

Not all of the components listed here are necessarily included with the equipment supplied.

Filters

  • Remove filter access panels (observe and note airflow direction labels), inspect filters for contamination with construction debris, and replace them as necessary. Replace access panels.
  • Filter pressure drops will depend on the actual flow rate and condition. Observe and record filter pressure drops after performance commissioning. Typically, the filter “dirty” condition occurs when the initial filter “clean” readings have been increased by 125Pa.
  • If filter manometers, pressure switches, or indicators have been fitted, they should be set or adjusted to reflect the commissioned system operation.

Heating Coils LPHW

  • Observe the Flow and Return connection labels on the unit. Drain and bleed valves are located on the coil. Other valves may be required in the system pipe-work depending on the installation (by others).
  • Where the wet system is at risk of frost damage, the addition of a proprietary anti-freeze solution to the water is recommended. Note that any frost protection offered by the unit’s integral control system will not operate if the power supply to the unit is interrupted.
  • Ecosmart frost protection is activated on any Ecosmart unit fitted with LPHW heating, when the outlet air temperature is 4ºC or below. The unit reacts by shutting down the fan to prevent a ‘wind chill’ effect reducing the temperature to a point whereby the coil could freeze and burst. The unit will also drive open the LPHW valve to a fully open position to allow full water flow through the
  • coil and the main PCB will close the ‘Heat demand’ contacts. These contacts could be used to send a signal to activate the boiler and/or valve to open to provide heat if not already doing so.
  • Piped connections should be made to the unit using appropriate techniques, and all pipework must be independently supported. No hot work is permitted within one metre of the unit.
  • Ensure that installed pipework runs do not prevent or restrict access to the unit at any point.
  • The completed installation (including the connections within the unit, as these may be disturbed during installation) shall be pressure tested to the project engineer’s specification (This is a condition of the unit warranty).

Electric Heaters

  • Heater Capacity:
  • XBC75 – 3ph,
  • 12Kw XBC85 – 3ph, 18Kw

The Electric Heater requires a 3ph supply which is independent of the main unit supply. Connections are to be made through the low-level fixed panel. The Electric Heater may be withdrawn to allow access to the Heater Controller without the need for wiring to be disconnected (Ensure the mains supply is isolated before removing any access panels and any adjustments are made to the Heater Controller).

Fan Sections

Access to the fan section is via lift-off panels (Section 5.0). For non- Ecosmart units, wiring to the fan motor/unit terminal box should be mechanically protected and in made in accordance with the details on the motor nameplate and diagram attached to the unit.
With the unit electrically isolated, rotate the fan impeller/drive manually, checking that it spins freely. Check that all fixings are secure.
Units must not be operated without all access panels in place – damage to equipment or injury to personnel may result. Units must not be operated unless control interlocks are in place – damage to equipment may result.
Test run motor for condition and correct rotation. Check that the correct current overloads are fitted and that the current being drawn does not exceed the motor nameplate value. Excessive current normally indicates that the ductwork system resistance is different from to design.

Motorized Dampers

If Nuaire matched silencers (Horizontal: XBC75-H-SIL900, Vertical: XBC75-V-SIL900) are being fitted to the fan unit, the motorised damper (Horizontal: XBC75-H-MD230V, Vertical: XBC75-V-MD230V ) needs to be fitted after the silencer.
This ensures that breakout noise levels are kept to a minimum.

  • Fully interlocking parallel blades, half-inch diameter electroplated mild steel spindle.
  • Nylatron bushes and external nylon/aluminum blade interconnection linkage.
  • Fitted with Belimo SM230A-S drive open/drive close actuator complete with switch.
  • Motorized damper wiring will require connection on-site and possible extension of the cable looms.

Constant Pressure Range (CP) – Controlling Static Pressure at Fan Inlet

  • Ecosmart constant pressure extract fans are supplied to control the static pressure at the fan inlet.
  • This setup is suitable for the majority of applications. When ancillaries with high-pressure losses are fitted to the inlet side of the fan, the low-pressure tapping must be moved from the fan chamber to a location upstream of the ancillaries, as shown below in Figure 14.
  • Failure to do this will result in excessive pressure being applied to the dampers in the rooms when the system is running in trickle mode.

ELECTRICAL INSTALLATION

Before commencing work, make sure that the unit, switched live and Nuaire control are electrically isolated from the mains supply. All interconnections between circuit boards, blowers, and sensors are made at the factory. This diagram only shows the essential field-wiring points for clarity.

Ecosmart Control (ES) Units

  • Remove link wire if switched live signal, an enabler or BMS signal is connected.
  • If a damper is not fitted, connect (Factory Fitted) a link wire from OP to RET. This will cancel the delay. Independent speed control can be achieved by removing the net link connection between supply and extract control boards.

Volt Free Contacts

  • Volt-free contacts are not fused. If these are used to power any external equipment, the installer must provide adequate fusing or other protections. These contacts are rated at 5 A resistive, 0.5 A inductive.
  • Run Connections – Contacts: closed when fan running.
  • Fault Connections – Contacts: closed when no-fault, open when fault. Heat Demand – Contacts: Closed when heating selected.

Wiring – ES Control, No Heating

nuaire XBC 75 Ecosmart Classic Basic Control-Fig-15

Wiring – ES Control, LPHW Heating

nuaire XBC 75 Ecosmart Classic Basic Control-Fig-16

Wiring – ES Control, Electric Heating

nuaire XBC 75 Ecosmart Classic Basic Control-Fig-17

Basic Control (BC) Units

The Basic (BC) Control units described in this manual are supplied without any controls. It is the installer’s responsibility to select and install suitable controller(s) and circuit(s) to produce the desired output from the units while remaining within the unit’s safe performance envelope.

  • Any electric heater must be connected to a suitable control circuit with an adequate safety interlock to fan operation. Including an over-temperature safety device rated at 80°C maximum. The fans should remain running for at least 4 minutes after the electric element is turned off to ensure the unit does not overheat.
  • Do not wire the power supply directly into the heating elements.
  • A control circuit such as a thyristor controller must be used to regulate heater power.
  • The alarm relay on condensate may require the use of a contactor if the host equipment supply is switched.
  • Do not wire the power supply to the motor via the motor alarm relay as terminals are only closed after the motor is energized.
  • Any heating or cooling coils fitted are supplied without a control valve and actuator.
  • The wiring illustrations below are for the fans, bypass damper, and electric heater XBC units with basic control. All wiring is terminated in junction boxes fitted to the unit.

Wiring – BC Control

nuaire XBC 75 Ecosmart Classic Basic Control-Fig-18

FROST COIL ANCILLARY (IF SUPPLIED)

All interconnections between circuit boards, blowers, and sensors are made at the factory. This diagram only shows the essential field-wiring points for clarity.

LPHW Frost Coils

The heater requires a 230V~50Hz single-phase supply connection to power the thermostat and valve actuator. Remove the top cover from the terminal box by rotating the four fixing screws half a turn, revealing the terminal block marked LEN.

Setting ‘Frost Condition’ Temperature

The LPHW heater frost coil is only enabled if the frost stat reads a ‘frost condition’. A ‘frost condition’ temperature adjustment dial is provided as part of the frost coil controls. The ‘frost condition’ temperature is easily adjustable from -10 to +10°C by inserting a small screwdriver into the adjuster aperture and rotating the spindle clockwise or anticlockwise. It is recommended that the ‘frost condition’ temperature is set at 4°C.

Electric Frost Coils

Wiring

  • The heater requires two connections; the SELV communications cable link up and the 400V~50Hz three-phase supply connection to power the heater element. Remove the top cover from the terminal box by rotating the four fixing screws half a turn, revealing the terminal block.
  • The communications cable (supplied) can now be plugged into the socket marked Ecosmart NET inside the box. The other end of the SELV cable should be plugged into the connection box of the associated supply fan in the system.

Setting ‘Frost Condition’ Temperature

  • The electric heater frost coil is only enabled if the frost stat reads a ‘frost condition’, the over-temperature cut-out is healthy AND a 24vac fan run signal is received from the main control panel. A ‘frost condition’ temperature adjustment dial is provided as part of the frost coil controls. The ‘frost condition’ temperature is easily adjustable from -10 to +10°C by inserting a small screwdriver into the adjuster aperture and rotating the spindle clockwise or anticlockwise. Once enabled the electric heater frost coil will provide its maximum heat output to achieve the ‘frost condition’ temperature set by the frost stat. It is recommended that the ‘frost condition’ temperature is set at 4°C.

CONTROLS

Test Button

The test button allows the individual blowers within the unit to be checked for its operation. If the fan is running already, press the button once to stop the fan, press again to switch on the fan. The fan will return to normal operation after 30 seconds.

LED Indication

  • PWR GREEN: Power on & OK.
  • Standby LED on when the fan is not running.
  • Fan 1 GREEN: Fan 1 is running, RED: Fan 1 is faulty.
  • Fan 2 GREEN: Fan 2 is running, RED: Fan 2 is faulty.
  • Heating* GREEN: Heating selected RED: Heating faulty
  • Cooling* Not applicable. See note.
  • Fault LED on when a fault is present on the unit.
  • Frost* Not applicable. See note.
  • TX LED on when the controller is transmitting data.
  • RX LED on when the controller is receiving data.

*The control panel is common to all the Ecosmart products and will have indicators for functions that are not available in this particular fan. However, these indicators will not be illuminated.

BMS Inputs

The system’s response to a 0-10V dc BMS signal is given in the following table. The BMS signal will override any sensors and user control connected to the system. The voltage tolerance is +/- 125mV and is measured at the fan’s terminal.

| Ventilation Mode| Cooling Mode| Heating Mode
---|---|---|---
Local Control| 0.00| –| –
OFF/ Trickle| 0.25| –| –
Speed 1| 0.50| 0.75| 1.00
Speed 2| 1.50| 1.75| 2.00
Speed 3| 2.50| 2.75| 3.00
Speed 4| 3.50| 3.75| 4.00
Speed 5| 4.50| 4.75| 5.00
Speed 6| 5.50| 5.75| 6.00
Speed 7| 6.50| 6.75| 7.00
Speed 8| 7.50| 7.75| 8.00
Speed 9| 8.50| 8.75| 9.00
Speed 10| 9.50| 9.75| 10.00

Settings

Maximum Airflow

  • Ensure the power supply is switched off and that a link wire is connected from the supply L to the SL terminal. Unplug all items connected to the ‘Net‘ connectors.
  • Switch on the power supply.
  • Wait for the fan to complete its self-test operation.

Measure the airflow using standard commissioning instruments at a suitable point in the ductwork. If adjustment is required, rotate the pot marked ‘MAX’ to obtain the desired airflow.

Trickle Ventilation Facility

Slide the ‘trickle’ switch 0 = Off, 1 = On. With ’trickle’ on and power to the unit, the fan will run at minimum speed until the switch live signal activates it to boost.

Minimum Trickle Airflow (Nominal 40%)

  • Repeat the same procedure for maximum airflow above but without the link wire between supply L and SL terminal. Ensure the trickle switch is in the ‘ON’ position. The adjustment must be made on the pot marked ‘Min’.
  • The minimum setting (nominally 40%) must be below
    the maximum setting; otherwise, the minimum setting will be automatically set to be the same as the maximum.

Overrun Time

A switched live of 100-230V at terminal SL will activate the fan. When the switched live signal is removed the fan will overrun for the period set by the dial ‘SL run on’ – adjust the desired overrun time by rotating clockwise.

‘Air Off’ Temperature

The adjustment knob is located in the control pack and must be set to the desired ‘air off’ temperature.

MAINTENANCE

It is important that maintenance checks are recorded and that the schedule is always adhered to, in all cases, the previous report should be referred to.
Before commencing work, make sure that the unit and Nuaire control are electrically isolated from the main supply. In some Ecosmart units and in some third-party controls, variable speed drives (inverters) are used to provide fan speed control. After the fan is isolated, allow at least 5 minutes for the capacitors in the inverter to discharge before commencing any work on the unit.

Routine Maintenance

  • Clean all areas of the unit and treat any areas of corrosion.
  • Check all access doors for leakage and if necessary locks should be adjusted and any replacement gasket materials should be replaced as required.
  • Any drain trays should be cleaned and repaired if necessary.

Every 3 Months

  • Check filters and change/clean if required, failure to do so may impair the performance and energy efficiency of this unit. Typically filters should be changed when the filters experience a 125 Pa increase above the clean filter resistance for the largest commissioned airflow rate.
  • Ensure condensate drains are cleaned clear and that water can flow freely from unit.
  • Check fin coil banks and heat exchangers. If necessary clean with a soft brush or vacuum. Check for signs of contamination.

Annually

  • Thoroughly inspect the unit and its components for corrosion, acting immediately to treat/restore any damaged areas.
  • All electrical terminals within the unit should be tightened.
  • Check all earth connections.
  • Check control dampers blades.
  • Check operation of damper actuators and linkages and adjust as necessary.
  • Coil faces should be inspected and any dust removed.
  • Check any thermal wheel belt, motor, bearings, or seals and if necessary clean with a soft brush or vacuum cleaner.

WARRANTY

  • A 5-year warranty on Ecosmart Control models, Basic Control models have a 2 year warranty. The warranty starts from the day of delivery and includes parts and labour for the first year. The remaining period covers replacement parts only.
  • This warranty is void if the equipment is modified without authorisation, is incorrectly applied, misused, disassembled, or not installed, commissioned and maintained in accordance with the details contained in this manual and general good practice.
  • The product warranty applies to the UK mainland and in accordance with Clause 14 of our Conditions of Sale. Customers purchasing from outside of the UK should contact Nuaire International Sales office for further details.
  • Failure to maintain the unit as recommended will invalidate the warranty.

END-OF-LIFE AND RECYCLING

Where possible Nuaire uses components that can be largely recycled when the product reaches its end of life

  • Fans, motors, controls, actuators, cabling, and other electrical components can be segregated into WEEE recycling streams.
  • Sheet metal parts, aluminum extrusion, heating/cooling coils, and other metallic items can be segregated and fully recycled.
  • EPP, plastic ducting, nylon corner pieces, plastic heat exchangers, packaging material, and other plastic components can be segregated into mixed plastic and widely recycled.
  • Cardboard packaging, wood, used filters and other paper components can be largely recycled or fully processed in energy from waste centers.
  • The remaining items can be further segregated and processed in accordance with the zero waste hierarchy. Please call After Sales Support for further information on items not listed above.

Ensure that Nuaire product is made safe from any electrical / water/refrigerant supplies before dismantling commences. This work should only be undertaken by a qualified person in accordance with local authority regulations and guidelines, taking into account all site-based risks.

AFTER-SALES AND REPLACEMENT PARTS

For technical assistance or further product information, including spare parts and replacement components, please contact the After Sales Department.
If ordering spares please quote the serial number of the unit together with the part number, if the part number is not known please give a full description of the part required. The serial number will be found on the identification plate attached to the unit casing.

Part Number Description
XBC75-V-FILTER KIT XBC75 Replacement G4 Panel Filters x4
776187 XBC75 Replacement Blower Assembly x1 (18kg)
XBC75-H-FILTER KIT XBC85 Replacement G4 Panel Filters x4
776188 XBC85 Replacement Blower Assembly x1 (37kg)

Blower Replacement
Remove 4x fixings and slide the blower out of the unit to replace it. Caution: Blowers are heavy, see description above for weight.

Filter Replacement

Remove the retaining plate and slide filters out of the unit to replace them.

nuaire XBC 75 Ecosmart Classic Basic Control-Fig-23

Information For Safe Installation, Operation, And Maintenance Of Nuaire Ventilation Equipment

To comply with EC Council Directives 2006/42/EC Machinery Directive and 2014/30/EU (EMC). To be read in conjunction with the relevant product documentation (see 2.1)

GENERAL

The equipment referred to in this Declaration of Incorporation is supplied by Nuaire to be assembled into a ventilation system which may or may not include additional components.
The entire system must be considered for safety purposes and it is the responsibility of the installer to ensure that all of the equipment is installed in compliance with the manufacturer’s recommendations and with due regard to current legislation and codes of practice.

INFORMATION SUPPLIED WITH THE EQUIPMENT

Each item of equipment is supplied with a set of documentation that provides the information required for the safe installation and maintenance of the equipment.
This may be in the form of a Datasheet and/or Installation and Maintenance instruction. Each unit has a rating plate attached to its outer casing. The rating plate provides essential data relating to the equipment such as serial number, unit code, and electrical data. Any further data that may be required will be found in the documentation.
If any item is unclear or more information is required, contact Nuaire.
Where warning labels or notices are attached to the unit the instructions given must be adhered to.

TRANSPORTATION, HANDLING, AND STORAGE

Care must be taken at all times to prevent damage to the equipment. Note that shock to the unit may result in the balance of the impeller being affected.
When handling the equipment, care should be taken with corners and edges, and the weight distribution within the unit is considered. Lifting gear such as slings or ropes must be arranged so as not to bear on the casing.
Equipment stored on-site prior to installation should be protected from the weather and steps taken to prevent ingress of contaminants.

OPERATIONAL LIMITS

It is important that the specified operational limits for the equipment are adhered to e.g. operational air temperature, air borne contaminants, and unit orientation. Where installation accessories are supplied with the specified equipment eg. wall mounting brackets. They are to be used to support the equipment only.
Other system components must have separate provisions for support. Flanges and connection spigots are provided for the purpose of joining ductwork systems. They must not be used to support the ductwork. Local Environment – Humidity. Ambient humidity (the humidity at the unit’s installed location) shall be within the range: of 10 to 95% (for controls, non-condensing).
Air humidity (the humidity of the air passing through the unit) shall be within the range: of 10 to 95% (for controls, non-condensing).

INSTALLATION REQUIREMENTS

In addition to the particular requirements given for the individual product, the following general requirements should be noted.
Where access to any part of the equipment that moves, or can become electrically live is not prevented by the equipment panels or by fixed installation detail (e.g. ducting), then guarding to the appropriate standard must be fitted.
The electrical installation of the equipment must comply with the requirements of the relevant local electrical safety regulations.
For EMC all control and sensor cables should not be placed within 50mm or on the same metal cable tray as 230V switched live, lighting or power cables and any cables not intended for use with this product.

COMMISSIONING REQUIREMENTS

  • General pre-commissioning checks relevant to safe operation consist of the following: Ensure that no foreign bodies are present within the fan or casing.
  • Check electrical safety. e.g. Insulation and earthing.
  • Check to guard of system.
  • Check operation of Isolators/Controls.
  • Check fastenings for security.
  • Other commissioning requirements are given in the relevant product documentation.

OPERATIONAL REQUIREMENTS

Equipment access panels must be in place at all times during the operation of the unit and must be secured with the original fastenings. If failure of the equipment occurs or is suspected then it should be taken out of service until a competent person can effect repair or examination. (Note that certain ranges of equipment are designed to detect and compensate for fan failure).

MAINTENANCE REQUIREMENTS

  • Specific maintenance requirements are given in the relevant product documentation.
  • It is important that the correct tools are used for the various tasks required.
  • If the access panels are to be removed for any reason the electrical supply to the unit must be isolated.
  • A minimum period of two minutes should be allowed after electrical disconnection before access panels are removed. This will allow the impeller to come to rest.
  • NB: Care should still be taken however since airflow generated at some other point in the system can cause the impeller to “windmill” even when power is not present. Care should be taken when removing and storing access panels in windy conditions.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Nuaire User Manuals

Related Manuals