nuaire AVS-NC Indoor Use Single Fans with No Control
SAFETY INFORMATION
- The provision of the electrical supply and the connection of the unit to the electrical supply must be carried out by a qualified electrician.
- Isolate from power supply before removing any covers. During installation / maintenance ensure all covers are fitted before switching on the mains supply.
- All-pole disconnection from the mains as shown in the wiring diagram must be incorporated within the fixed wiring and shall have a minimum contact separation of 3mm in accordance with latest edition of the wiring regulations.
- This unit must be earthed.
- Ducting must be securely fixed with screws to the spigot to prevent access to live parts. Duct runs terminating close to the fan must be adequately protected by suitable guards.
- This appliance should not be used by children or persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge, unless they have been given supervision or instruction concerning the safe use of the appliance by a person responsible for their safety. Children shall not play with the appliance. Cleaning and user maintenance shall not be carried out by children.
Symbols
-
GENERAL WARNING
Signifies a general warning regarding hazard specified by supplementary information. -
ELECTRIC SHOCK
This unit must be completely electrically isolated before any panels are removed. Check mains supply and control connections. -
ROTATING PARTS
This unit contains fast moving rotational parts which may start automatically. It is the sole responsibility of the installer to adequately guard these components. -
REFER TO INSTRUCTION MANUAL
Read and understand the installation and maintenance manual before installing, operating or maintaining this product.
Important Information
This manual contains important information on the safe and appropriate
assembly, transport, commissioning, operation, maintenance, disassembly and
simple troubleshooting of the product.
While the product has been manufactured according to the accepted rules of
current technology, there is still a danger of personal injury or damage to
equipment if the following general safety instructions and the warnings
contained in these instructions are not complied with.
- Read these instructions completely and thoroughly before working with the product.
- Keep these instructions in a location where they are accessible to all users at all times.
- Always include the operating instructions when you pass the product on to third parties.
Personal Protective Equipment
The following minimum Personal Protective Equipment (PPE) is recommended when
interacting with Nuaire product:
- Protective Steel Toed Shoes – when handling heavy objects.
- Full Finger Gloves (Marigold PU800 or equivalent) – when handling sheet metal components.
- Semi Fingerless Gloves (Marigold PU3000 3DO or equivalent)
- when conducting light work on the unit requiring tactile dexterity.
- Safety Glasses – when conducting any cleaning/cutting operation or exchanging filters.
- Reusable Half Mask Respirators – when replacing filters which have been in contact with normal room or environmental air.
Nuaire would always recommend a site specific risk assessment by a competent person to determine if any additional PPE is required.
INTRODUCTION
AVS units are rectangular in section and shall be double skinned with 35mm
infill panels and shall be manufactured from heavy gauge, corrosion resistant
Aluzinc steel, internally lined with acoustic material. Four matching mounting
feet are supplied with the unit. Units have circular rigid spigots at each
end. The spigot ends are fully detachable for relocation onto matching
attenuators. The fan should be with an
‘inline assembly’, positioned in series for optimum performance.
Units incorporate fully detachable top or bottom panels for maintenance and
inspection purposes. AVS 1 units have a loose control module for surface
mounting up to 1 metre away from main unit. AVS 8 and 9 units incorporate
split access panels.
Code Description:
1 | 2 | 3 | – | 4 |
---|---|---|---|---|
AV | S | 1 | – | NC |
- Range: Aire-Volve
- Fan Type: S = Single Fan
- Unit Size: 1, 2, 3, 4, 4L, 5, 6, 7, 8, 9
- Control Type NC = No Control
HANDLING
Upon receipt of the equipment, an inspection should be made. Before
commencement of lifting, ensure that normal equipment safety checks have been
carried out.
A unit / module should be removed from the vehicle using a fork lift or crane.
Always handle with care to avoid damage and distortion, and where lifting
slings are employed use spreaders to ensure slings do not come into contact
with the unit case, or control pack. Correctly position slings to avoid
twisting of the unit case and observe the centre of gravity before the final
lift is made. The weight of the unit is available on the unit rating plate.
Dependent on model and size, units may be supplied in single or multi-modular
sections. Handle each section individually do not stack for lifting or
storage.
MECHANICAL INSTALLATION
Installation must be completed by competent persons, in accordance with good
industry practice and should conform to all governing and statutory bodies
i.e. IEE, CIBSE, etc.
The units are supplied for installation into In-line ductwork (internal)
applications only. All ductwork connections must be airtight to prevent loss
of performance.
The unit has an external case side mounted control module / terminal box and
is supplied ready for connection into the electrical supply. Typically the
control is mounted on the side of the unit as standard (AVS2-9).
The method of mounting used is the responsibility of the installer. The units
can be mounted in any attitude enabling alternative control positions. Access
to the blower for maintenance can still be achieved for annual maintenance
once orientation is changed, however if the motor requires replacing, the unit
will have to be lowered to ground level if installed in non-standard
configuration.
Surface Mounting Control Module (AVS1 Only)
The fan unit control module/terminal box is supplied loose for mounting up to
1 metre away from main unit (Figure 4). The unit must be mounted on a secure,
vibration free vertical surface away from direct heat sources or water spray.
Surface Mounted Units
Utilising four matching anti-vibration (AV) mounting feet (Figure 1). AV
mounts isolate the fan only, silencers / back draught dampers and other
“significant mass” accessories should form part of the fixed ductwork after
the flexible connection.
Units Suspended With Drop Rods
From the ceiling or in the ceiling void using four AV mounting feet supplied,
with access panel positioned for underside access (Figure 2 & 3).
Vertically Wall Mounted (Rigid) Units
Utilising the Aire-Volve Vertical Hanging Bracket kit that includes wall
hanging brackets and hinges (Figures 5 and 6). The unit case has captive M8
nuts which can be used after removing the M8 ‘plugging’ screws. Units should
always be positioned with sufficient space to allow the access panel to extend
forward. Only suitable for topside and underside detachable access panel units
mounted indoors.
Aire-Volve Unit Size | Aire-Volve Vertical Hanging Bracket Kit |
---|---|
1 | AVT1-VK |
2 | AVT2-VK |
3 | AVT3-VK |
4 | AVT4-VK |
4L | AVT4L-VK |
5 | AVT5-VK |
6 | AVT6-VK |
Anti-Vibration (AV) Mounts
AV mounts should not be fitted to a fan/silencer assembly unless there are
flexible connectors fitted between the assembly and associated duct work. AV
mounts should be installed with the matched mounting feet and positioned such
that they carry an equal proportion of the assembly weight. This is
particularly important where fans and silencers are installed on suspension
rods. Suspension rods and fixing screws are not supplied.
Resilient rubber anti-vibration mounting kits (NAV) are available, the correct
selection and type employed will depend on the accurate calculation of the
weight of the assembly to be supported.
The large round washers included with the NAV(2-5) are for fitting above or
below the resilient mounting as required to safeguard the installation against
the break-up of, or damage to, a mounting. In the event of a resilient
mounting failure, the washer will support the weight of the unit. Fans using
size NAV 6 upwards require supporting steelwork to be designed (by others) for
suspended applications. AV mounts must only be subjected to compressional
forces and MUST NOT be used in a configuration that places these parts under
tension or shear force.
7 | NAV2-5 Dimensions |
---|
Anti-Vibration Mounting Kit| A (mm)| B (mm)| Max. Supporting
Weight (kg)
NAV2| 40| 75| 80
NAV3| 40| 75| 180
NAV4| 40| 75| 260
NAV5| 40| 75| 130
8| Correctly Installed NAV(2-5) – Suspended Application
9| Correctly Installed NAV(2-5) – Suspended Application
**10** Incorrectly Installed NAV(2-5) – Suspended Application
Dimensions (mm) & Weights (kg)
AVS Units
**12** AVS Dimensions
Unit| A †| A1| B ‡| B1| C| D|
Weight
Code| | (Bracket| | (Bracket| | | (kg)
| | Centre| | Centre| | |
| | Points)| | Points)| | |
AVS1| 580| 344| 535*| 576| 246| 200| 27
AVS2| 615| 380| 535| 646| 281| 200| 24
AVS3| 745| 510| 672| 713| 329| 250| 43
AVS4| 788| 553| 672| 713| 373| 315| 47
AVS4L| 914| 678| 818| 860| 391| 315| 67
AVS5| 914| 678| 818| 860| 428| 315| 66
AVS6| 1087| 851| 911| 953| 541| 400| 90
AVS7| 1180| 942| 1008| 1050| 571| 400| 106
AVS8| 1338| 1101| 1233| 1275| 611| 500| 157
AVS9| 1338| 1101| 1233| 1275| 611| 500| 141
- Add 85mm for unit + spigot length.
- Add 108mm for unit width.
- AVS1 control supplied loose from unit with umbilical cord.
Matched AVS Silencers
**13** AVS Matched Silencer Dimensions
Unit Code| Silencer Code| Size| A| B| C| Weight (kg)
AVS1
| AVS1-MSM| Mini| 500| 535| 250| 27
AVS1-MSS| Standard| 1000| 535| 250| 32
AVS1-MSL| Large| 1500| 535| 250| 45
AVS2
| AVS2-MSM| Mini| 500| 535| 285| 27
AVS2-MSS| Standard| 1000| 535| 285| 32
AVS2-MSL| Large| 1500| 535| 285| 45
AVS3
| AVS3-MSM| Mini| 500| 6672| 334| 27
AVS3-MSS| Standard| 1000| 672| 334| 39
AVS3-MSL| Large| 1500| 672| 334| 56
AVS4
| AVS4-MSM| Mini| 500| 672| 376| 34
AVS4-MSS| Standard| 1000| 672| 376| 39
AVS4-MSL| Large| 1500| 672| 376| 56
AVS4L
| AVS4L-MSM| Mini| 500| 822| 376| 34
AVS4L-MSS| Standard| 1000| 822| 376| 39
AVS4L-MSL| Large| 1500| 822| 376| 56
AVS5
| AVS5-MSM| Mini| 500| 822| 428| 43
AVS5-MSS| Standard| 1000| 822| 428| 64
AVS5-MSL| Large| 1500| 822| 428| 89
AVS6
| AVS6-MSM| Mini| 500| 915| 545| 43
AVS6-MSS| Standard| 1000| 915| 545| 64
AVS6-MSL| Large| 1500| 915| 545| 89
AVS7
| AVS7-MSM| Mini| 500| 1013| 575| 43
AVS7-MSS| Standard| 1000| 1013| 575| 41
AVS7-MSL| Large| 1500| 1013| 575| 98
AVS8
| AVS8-MSM| Mini| 500| 1237| 615| 51
AVS8-MSS| Standard| 1000| 1237| 615| 83
AVS8-MSL| Large| 1500| 1237| 615| 114
AVS9
| AVS9-MSM| Mini| 500| 1237| 615| 51
AVS9-MSS| Standard| 1000| 1237| 615| 92
AVS9-MSL| Large| 1500| 1237| 615| 125
Typical Underside View Of AVS1-6 Unit Access
Unit Code
| Access Panel Weight (kg)|
Unit Code
| Access Panel Weight (kg)
---|---|---|---
AVS1| 6| AVS5| 7
AVS2| 6| AVS6| 17
AVS3| 9| AVS7| 21
AVS4| 10| AVS8| 14 (per panel)
AVS4L| 7| AVS9| 14 (per panel)
Fitting Matched Silencers
Ensure that the attenuator pods are in the correct orientation (Figure 16). To
change orientation of attenuator pod just roll silencer over 180° before
fitting and use fixing brackets.
Correctly align fixing brackets halves (Figure 17) and assemble using M8 cap
head bolt and nut supplied with bracket. Tighten bolts to ensure a full seal
between silencer and unit is achieved (Figure 18).
ELECTRICAL INSTALLATION
Isolation – Before commencing work, make sure that the unit and Nuaire control
are electrically isolated from the mains supply.
Because the run and start currents depend upon the duty and associated
ductwork of an individual unit, run currents will be exceeded if the unit is
operated with its cover removed. It is therefore recommended that the unit is
not run for prolonged periods in this condition.
Unit Details
Unit details including Full Load Current, Voltage, fan speed etc. can be found
on the unit label.
Wiring Diagrams
The wiring illustrations below are for units without control. All wiring is
terminated in junction boxes fitted to the side of the unit. Local isolator
(by others)
Do not wire the power supply to motor via the motor alarm relay as terminals
are only closed after the motor is energized.
The alarm relay on condensate may require the use of a contactor if the host
equipment supply is switched.
CONTROLS
The No Control (NC) units described in this manual are supplied without any controls. It is the installer’s responsibility to select and install suitable controller(s) and circuit(s) to produce the desired output from the units while remaining within the units safe performance envelope.
MAINTENANCE
It is important that maintenance checks are recorded and that the schedule is always adhered to, in all cases, the previous report should be referred to.
Routine Maintenance
- Clean all areas of unit and treat any areas of corrosion.
- Check all access doors for leakage and if necessary locks should be adjusted and any replacement gasket materials should be replaced as required.
Annually
- Thoroughly inspect the unit and its components for corrosion, acting immediately to treat/restore any damaged areas.
- All electrical terminals within the unit should be tightened.
- Check all earth connections.
- Check control dampers blades.
- Check operation of damper actuators and linkages and adjust as necessary.
WARRANTY
The 2 year warranty starts from the day of delivery and includes parts and
labour for the first year. The remaining period covers replacement parts only.
This warranty is void if the equipment is modified without authorisation, is
incorrectly applied, misused, disassembled, or not installed, commissioned and
maintained in accordance with the details contained in this manual and general
good practice.
The product warranty applies to the UK mainland and in accordance with Clause
14 of our Conditions of Sale. Customers purchasing from outside of the UK
should contact Nuaire International Sales office for further details.
Failure to maintain the unit as recommended will invalidate the warranty.
END-OF-LIFE AND RECYCLING
Where possible Nuaire use components which can be largely recycled when the product reaches its end-of-life:
- Fans, motors, controls, actuators, cabling and other electrical components can be segregated into WEEE recycling streams.
- Sheet metal parts, aluminium extrusion, heating/cooling coils and other metallic items can be segregated and fully recycled.
- EPP, plastic ducting, nylon corner pieces, plastic heat exchangers, packaging material and other plastic components can be segregated into mixed plastic and widely recycled.
- Cardboard packaging, wood, used filters and other paper components can be largely recycled or fully processed in energy from waste centres.
- Remaining Items can be further segregated and processed in accordance with the zero waste hierarchy. Please call After Sales Support for further information on items not listed above.
Ensure that Nuaire product is made safe from any electrical / water / refrigerant supplies before dismantling commences. This work should only be undertaken by a qualified person in accordance with local authority regulations and guidelines, taking into account all site based risks.
AFTER SALES AND REPLACEMENT PARTS
For technical assistance or further product information, including spare parts
and replacement components, please contact the After Sales Department.
If ordering spares please quote the serial number of the unit together with
the part number, if the part number is not known please give a full
description of the part required. The serial number will be found on the
identification plate attached to the unit casing.
Replacing Fan / Motor
The only items of the fan units unit likely to require replacement are the
fan/motor assemblies due to a failed motor or damaged impeller or damper
actuator.
Remove the access cover. Disconnect the incoming wiring from the connection
box (located on the fan scroll) on the particular fan/motor assembly to be
removed.
Remove the fan/motor fixings completely, other than the two slotted hole
fixings. Support the fan/motor assembly and loosen the slotted hole fixings.
The fan/motor assembly can now be turned and withdrawn from the unit.
After replacing the faulty item, refit the fan motor/assembly using the
slotted hole fixings to assist in supporting the assembly. Re-connect the
wiring. Replace the access cover.