Honeywell TR21 Wall Modules Instruction Manual
- June 6, 2024
- Honeywell
Table of Contents
- Honeywell TR21 Wall Modules
- INSTALLATION INSTRUCTIONS
- PRODUCT DESCRIPTION
- SPECIFICATIONS
- Temperature Sensor
- Communications
- BEFORE INSTALLATION
- INSTALLATION
- Cover Disassembly
- Attaching the Cover
- Humidity Settings (DIP switch S1)
- TR23 and TR24 Wall Module Override (Bypass) Pushbutton and LED Operation
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Honeywell TR21 Wall Modules
INSTALLATION INSTRUCTIONS
FEATURES
The TR21, TR22, TR23, and TR24 family of wall modules include:
- Models with setpoint adjustment.
- Models with humidity output.
- Models with occupied/unoccupied override (bypass) with LED.
- Models with 3-position (auto/0/1) or 5-position (auto/0/1/2/3 speed) fan switch.
- LONWORKS® bus jack on all models except the TR21 and TR21-A models.
- Locking cover on all models.
- Operating range 45° to 99° F (7° to 37° C).
- Models (TR22 and TR23) with user-selectable temperature setpoint dials in Fahrenheit, Celsius, and Relative (- to +).
PRODUCT DESCRIPTION
The TR21, TR22, TR23, and TR24 are a family of direct-wired wall modules for use with:
- Spyder Unitary Controllers: PUL, PVL
- Excel 10 W7750, W7751a, W7752, and W7753 controllers
- Honeywell Excel 800, 600, 500, 100, and 80 (all fully programmable) controllers
- W7761 Controller
- ComfortPoint LON Controllers: CP-UL, CP-VL
All models have a space temperature sensor. Some models have a temperature
dial, setpoint adjustment, LONWORKS bus jack, override (bypass) with LED, and
fan switch.
NOTE: Refer to the TR21, TR22, TR23, and TR24 Wall Modules –
Specification Data, form 63-1321, for specific model features and additional
information.
SPECIFICATIONS
Models: For specific model information, see TR21, TR22, TR23, and TR24 Wall Modules – Specification Data, form 63-1321.
Environmental Ratings:
- Operating Temperature: 45° to 99° F (7° to 37° C).
- Shipping Temperature: -40° to 150° F (-40° to 65.5° C).
Accessories: 50007298-001 (pack of 12) medium, cover plate; 6-7/8 x 5 in. (175 x 127 mm).
Approvals: CE; UL94 plastic enclosure; FCC Part 15, Class B
Temperature Sensor
TR21, TR22, TR23, and TR24 20K Ohm Nonlinearized Sensor:
All models are furnished with a 20K Ohm nonlinear NTC temperature sensor that follows a specific temperature resistance curve. See Fig. 1 on page 2.
NOTE: The TR21-A wall module model has two (2) 20K Ohm nonlinear NTC temperature sensors in parallel, which provide 10K NTC temperature sensing necessary for averaging.
TR21, TR22, TR23, AND TR24 WALL MODULES
Communications
All wall modules (except the TR21 and TR21-A models) have a LONMARK® bus communications port. If needed, the jack plug must be removed in the field, and terminals 3 and 4 wired according to the installation instructions. The recommended wire size for the LONMARK® bus is Level IV, 22 AWG (0.34 sq.mm) plenum or non-plenum rated, non-shielded, twisted pair, solid conductor wire .
BEFORE INSTALLATION
CAUTION
Erratic System Operation Hazard.
Failure to follow proper wiring practices can introduce disruptive electrical
interference (noise). Keep wiring at least one foot away from large inductive
loads such as motors, line starters, lighting ballasts, and large power
distribution panels. Shielded cable is required in installations where these
guidelines cannot be met. Ground shild only to grounded controller case.
IMPORTANT
All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams.
- Wall module wiring can be sized from 16 to 22 AWG (1.31 to 0.33 sq. mm) depending on the application.
- The maximum length of wire from a device to a wall module is 1000 ft. (305 m).
- Twisted pair wire is recommended for wire runs longer than
INSTALLATION
Mount the wall module on an inside wall approximately 54 in. (1372 mm) from the floor (or in the specified location) to allow exposure to the average zone temperature. Do not mount the wall module on an outside wall, on a wall containing water pipes, or near air ducts. Avoid locations that are exposed to discharge air from registers or radiation from lights, appliances, or the sun. See “Cover Disassembly” on page 3. The wall module can be mounted on a wall, on a standard utility conduit box using No. 6 (3.5 mm) screws or on a 60 mm wall outlet box (see Fig. 3). When mounting directly on a wall, use the type of screws appropriate for the wall material.
Cover Disassembly
A snap-fit locking mechanism is used to attach the cover of the wall module to its subbase. To disassemble the cover from the subbase:
- Insert a thin, flat blade screwdriver into each of the two slots at the bottom of the module to release the two locking tabs. See Fig. 2 on page 2.
- Tilt the cover out and away from the subbase to release the top two locking tabs.
- To change the dial (e.g. from Fahrenheit to Celsius) release the two tabs on the inside of the front cover and remove the old dial.
Wiring
Attach the wires from the device sensor terminals to the appropriate wall
module terminals. See Table 1 on page 4.
CAUTION
Improper Electrical Contact Hazard. Screw type terminal blocks are designed to accept no more than one 16 AWG (1.31 sq. mm) conductor. Connect multiple wires that are 16-18 AWG (1.31-0.82 sq. mm) with a wire nut. Include a pigtail with this wire group and attach the pigtail to the individual terminal block.
Wiring Wall Modules
Wire the terminal block as follows:
- For single wires, strip 3/16 in. (5 mm); for multiple wires going into one terminal, strip 1/2 in. (13 mm) insulation from the conductor.
- If two or more wires (20 to 22 AWG only) are being inserted into one terminal, twist the wires together before inserting. See Fig. 5.
- Insert the wire in the required terminal location and tighten the screw to complete the termination.
- Review and verify the terminal connection wiring and DIP switch settings illustrated in Table 1 on page 4.
NOTE: Wire the Lon connection (terminals 3 and 4) using Level IV 22 AWG (0.34 mm2) plenum or non-plenum rated, unshielded, twisted pair, solid conductor wire.
Wiring Examples
Table 1 on page 4 illustrates DIP switch settings and terminal connections for
the wall modules. Refer to the TR21, TR22, TR23, and TR24 Wall Modules –
Specification Data, form 63-1321, for additional DIP Switch information.
IMPORTANT
SW 2 on DIP Switch S2 is used for factory calibration of the temperature
setpoint potentiometer. Depending on calibration, this switch may be set in
either the On or Off position.
DO NOT change the position of this switch.
NOTES:
- The TR21 and TR22 models do not use DIP Switch S1 and S3.
- DIP Switch S1 is used only on the humidity models, TR21-H and TR23-H.
- Models TR21 and TR21-A use terminals 1 and 2 only. Model TR21-J uses terminals 1, 2, 3, and 4 only.
- STRIP 1/2 IN. (13 MM) FROM WIRES TO BE ATTACHED AT ONE TERMINAL.
- TWIST WIRES TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS).
- CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE INSERTING INTO THE TERMINAL AND TIGHTENING THE SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION.
Attaching the Cover
When all wiring is complete, attach the cover of the Wall Module as follows:
- Optional: For models with a temperature dial, insert the two setpoint screws into the inside of the cover to set the desired temperature range limit. See Fig. 4.
- Press the cover straight down onto the subbase until it snaps into place.
- For models with a temperature dial, insert the desired dial through the opening in the cover. Align the keyed shaft on the knob with the keyed slot into the fitting on the subbase, then press down until it snaps into place.
Wiring and DIP switch settings:
See Table 1 to determine DIP switch positions and terminal usage for each
controller.
Table 1. DIP Switch Settings and Terminal Connections.
TR22 and TR23 Setpoint Adjustment
For the TR22 and TR23 Wall Modules with a setpoint adjustment, the controller
must be programmed for the values in Table 2 and Table 3.
Table 2. Setpoint Values.
Setpoint Value | Program Setting |
---|---|
55°F (13°C) | 2.773 V |
65°F (18°C) | 2.148 V |
75°F (24°C) | 1.345 V |
85°F (29°C) | 0.43 V |
Table 3. Wall Module Setpoint Configuration.
Model | Setpoint | Resistance (Ohms) |
---|---|---|
°F Absolute | 55°F | 9574 |
85°F | 1426 | |
Relative | -9°F offset from 70°F | 9574 |
+9°F offset from 70°F | 1426 | |
°C Absolute | 12°C | 9945 |
30°C | 1150 |
TR23-KL and TR23-H-KL
The TR23-KL and TR23-H-KL ship in packs of 20 and are supplied without
setpoint adjustment knobs. Knobs can be ordered separately. See Table 4 for
Knob model numbers.
Table 4. Knob Model Numbers
Model | Description |
---|---|
KNOB-C | Celsius scale knob (pack of 20) |
KNOB-F | Fahrenheit scale knob (pack of 20) |
KNOB-O | Relative scale knob (pack of 20) |
Humidity Settings (DIP switch S1)
The humidity sensing control mode is set with this 2-position DIP switch.
Refer to Fig. 4 on page 3 for location of DIP switch S1.
NOTE: These switch settings apply only to the TR21-H and TR23-H models.
To change the setting, first disconnect the power, then set SW1 and SW2
according to Table 5.
Table 5. DIP Switch S1 Settings.
Wall Module Model
| ****
Sensing Control
| Individual Switches
---|---|---
1| 2
TR21-H TR23-H
| 0-10 Vdc| OFF| OFF
0-5 Vdc| OFF| ON
4-20 mA| ON| OFF
TR23 and TR24 Wall Module Override (Bypass) Pushbutton and LED Operation
When Used With Excel 10 Controllers:
The Excel 10 controllers (W7750, W7751, W7752, and W7753) provide timed
occupied and unoccupied temperature setpoints for the Wall Module, see Fig. 6.
The override pushbutton is used to change the controller into the modes shown
in Table 6 and illustrated in Fig. 7 on page 6. The override (bypass) LED
displays the override status of the controller.
Table 6. Wall Module Operation.
Pushbutton Held Down | Controller Model | LED Status |
---|---|---|
0 to 1 second | No override | Off |
1 to 4 seconds | Timed occupied override | On |
4 to 7 seconds | Unoccupied override | Single blink per second |
Longer than 7 seconds | No override | Off |
not applicable | Continuous occupied overridea | Two blinks per second |
Remote function, which is generated from the network.
When Used With Excel 600/500/100/80/50 Controllers:
The application engineer/programmer can program the override (bypass) and LED
to operate in any manner desired. The override (bypass) input is a dry
contact, normally open, momentary digital input when the wall module does not
have a fan switch. When a fan speed switch (basically a series of resistances
based on fan switch position) is present, the override button is an analog
input. See Table 4 for resistances.
When Used With T7350 Thermostat:
TR21, TR21-A, TR21-H, TR22, TR23, and TR24 are the models compatible with the
T7350 thermostat. When using with the T7350 thermostat be sure to use the
relative +/- offset knob only. The Celsius and Fahrenheit knobs will not work
properly with the T7350 Thermostat.
TR22-F5, TR23-F3, and TR23-F5 Wall Module Fan Switch
With the switch in the far left position (Auto), the fan automatically runs at
the speed determined by the controller temperature control algorithm. With the
switch in the 0 position, the fan is off. Position 1 is fan speed 1, etc. The
wall module fan speed switch overrides the temperature control algorithm.
When Used With Excel 10 Controllers:
The Excel 10 Controllers (W7750, W7751, W7752, and W7753) can be programmed so
that the fan speed switch and override button function the way that the
application engineer/programmer wants. See Table 7 for controller-programming
resistances. Switch 1 on Dip Switch S2 adds 10k Ohms resistance when OPEN (for
Excel 600-80 controllers) and removes it when CLOSED (for Excel 10
controllers).
Table 7. Program Settings for Wall Modules with Fan Switch using Excel 10
Controllers.
For Switch Position | Resistance (Ohms) | Comment |
---|---|---|
Auto | 1861 ±119 | Left most position |
0 | 2686 ±127 | Fan Off position |
1 | 3866 ±139 | |
2 | 3041 ±130 | |
3 | 4601 ±146 | Right most position |
Override button closed | Closed circuit |
When Used With Excel 600/500/100/80/50 Controllers:
Excel 600/500/100/80 Controllers can be programmed so that the fan speed
switch and override button function the way that the application
engineer/programmer wants. See Table 8 for controller-programming resistances.
Switch 1 on Dip Switch S2 adds 10k Ohms resistance when OPEN (for Excel 600-80
controllers) and removes it when CLOSED (for Excel 10 controllers).
Table 8. Program Settings for Wall Modules with Fan Switch using Excel
600/500/100/80 Controllers.
For Switch Position | Resistance (Ohms) | Comment |
---|---|---|
Auto | 11.861K ±119 | Left most position |
0 | 12.686K ±127 | Fan Off position |
1 | 13.866K ±139 | |
2 | 13.04K ±130 | |
3 | 14.60K ±146 | Right most position |
Override button closed | 10K ±100 |
LONWORKS® is a registered trademark of Echelon® Corporation. LONMARK® and the LonMark Logo are trademarks of the LonMark Association. Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com ® U.S. Registered Trademark © 2009 Honeywell International Inc. 62-0267—09 E.K. Rev. 09-09 Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Toronto, Ontario M1V 4Z9