RISC GROUP RK315DT0000C WatchOUT Extreme Instruction Manual
- June 5, 2024
- RISC GROUP
Table of Contents
- Introduction
- Mounting
- Wall Mount Installation
- Changing Back Tamper position
- Terminal Wiring
- DIP Switch Settings
- Microwave Adjustment
- Technical Specification
- Ordering Information
- UL Compliance Section
- BUS Mode Installation
- DIP Switch Settings
- ProSYS Programming
- System Parameters
- RISCO Group Limited Warranty
- Documents / Resources
RK315DT0000C WatchOUT Extreme
Instruction Manual
Introduction
RISCO Group’s Dual Technology Outdoor Detector, WatchOUT 315DT, is a unique
detector with signal processing based on two Passive Infrared (PIR) channels
and two Microwave (MW) channels. The detector can operate as a regular relay
detector connected to any control panel, or as a BUS accessory when connected
to RISCO Group’s ProSYS control panel via the RS485 BUS, thus having the
unique remote control and diagnostic capabilities.
The instructions describe herein, describe the WatchOUT 315DT in Relay & BUS
mode.
Mounting
Mounting Considerations
Note:
- For low installations, below 1.7m (5’6″) in which pet immunity is required, use the supplied RL300F lens (low wall or fence installations).
- The detector’s pet immunity (height of an animal, no weight limit), is up to 70 cm (2’4″), when installing the detector at 2.2m (7’2″). If the installation is below the height mentioned above, the Pet Immunity decreases accordingly; every 10 cm (4″) decrease in installation height leads to a 10 cm (4″) decrease in pet immunity.
If possible, avoid pointing the detector at moving objects (swaying trees, bushes, etc.)
Ensure any objects do not obstruct the field of view for both technologies. Pay attention to growing trees or bushes, plants with big moving leaves, etc.
For installations with extensive vehicle traffic or targets beyond the
required detection range, it is recommended to adjust the MW sensitivity
and/or tilt the detector down.
Note:
Tilting the detector down may reduce the pet’s immunity
For optimum detection, select a location that is likely to intercept an intruder moving across the coverage pattern at a 45° trajectory.
NOTE: Disable Proximity AM during heavy rain (if WatchOUT 315DT is not sheltered) to prevent Proximity AM alerts.
Wall Mount Installation
Note:
The installation knockouts numbering is marked on the backplate.
-
Open the WatchOUT front cover (unlock C1, Figure 1).
-
Release internal base (unlock I1, Figure 2).
-
Select mounting installation as follows:
Flat Mounting:
• Open knockouts on an external base (Figure 3).
• B1 – B4: Wall mounting knockouts
• T1: Back tamper knockout
• W2 / W3: wires entry knockouts
45° angle Mounting (Left side mounting)
a. Open knockouts on an external base (Figure 3)
• L1, L2: Left mounting knockouts
• T3: Left tamper knockout
• W5 / W6: Wire entry knockouts
b. Remove tamper spring.
c. Replace tamper bracket (Item 1) with -
Insert external wires through external base W2, W3 (Flat Mounting) or W5, W6 (Left side mounting) (Figure 3).
-
Secure the external base to the wall.
-
Insert external wires and tamper wires through the internal base (Figure4).
-
Secure internal base to external base (lock I1, Figure2).
-
Close the front cover (Lock C1, Figure1) after wiring and setting DIP switches.
-
Walk test the detector.
|
---|---
|
Note
For 45° right side installation use the equivalent units on the external base
as follows:
Knockouts Description | Left | Right |
---|---|---|
Mounting Knockouts | L1, L2 | R1, R2 |
Tamper spring knockouts | T1, T3 | T2, T4 |
Tamper screw anchor | T5 | T6 |
Wiring Knockouts | W5, W6 | W7, W8 |
Changing Back Tamper position
The back tamper is by default secured on the right side of the internal base (rear view). If you wish to move it to the left side (rear view), do the following (Figure 5):
- Remove tamper screw 1 in order to release the tamper from position 7.
- Ensure tamper spring 2 rests over tamper wire base 4.
- Ensure plastic tamper bracket 3 rests over both 2 and 4.
- Secure tamper screw 1 into 3 over position 6.
Notes:
- Verify that you hear a “Click” when attaching the tamper spring to the wall.
- For pole installation, the tamper can be moved to the bottom right-hand side of the internal base.
Terminal Wiring
+,- | 12 VDC |
---|---|
ALARM | N.0 relay, 24VDC , 0.1A |
FREE YEL | This terminal is a free pin that can be used to connect wires |
and EOL resistors
TAMPER| N.0 switch, 24VDC , 0.1A
FREE GREEN| This terminal is a free pin that can be used to connect
wires and EOL resistors
AM| Normally closed AM relay output (24VDC, 0.1A) indicates Anti Masking
alarm or any trouble in the detector (not including dust/dirty lens).
The Proximity AM enables receiving sabotage alerts before the detector is
damaged or masked, using both microwave channels.
Note:
When DIP8 is defined as Enabled this relay also opens momentarily when a
Proximity AM attempt occurs.
LED ENABLE| Used to remotely control the LEDs when DIP1 is set to ON.
Enable: input is +12V OR no terminal connection
Disable: Connect the input to OV
DUST| N.O. collector max 70 mA. Indicates that the lens is dirty and
requires cleaning.
TEST| Used to perform remote alarm testing to the detector by applying 0
volts to this terminal.
Success: The alarm relay is momentarily opened.
Failure: AM relay is opened
SET/ UNSET| This input enables to control of Anti-masking and LEDs
operation in accordance to the system status, Set (Arm) / Unset (Disarm).
While the system is armed this feature prevents an intruder from gaining
knowledge of the detector’s status and disables Anti- masking detection.
System Status Input Status AM Relay LEDs
Set (Arm) OV Off Off
Unset (Disarm) 12V or no connection On* On**
- DIP7 is ON (Anti masking enabled)
** DIP1 is ON (LEDs enabled) and LEDs ENABLE input terminal is enabled (+12V OR no terminal connection).
DIP Switch Settings
DIP 1: LEDs operation
On: LEDs Enabled
Off: LEDs Disabled
DIP 2-3: Detection Sensitivity
Sensitivity | DIP2 | DIP3 |
---|---|---|
Low | Off | Off |
Mid | Off | On |
Normal (Default) | On | Off |
Maximum* | On | On |
- In maximum sensitivity sway recognition is disabled to achieve maximum sensitivity
DIP 4: Anti masking Sensitivity On: High Off: Low
DIP 5: Detector’s optics
On: Barrier/Long-range Off: Wide angle
DIP 6: Red LED /3 LED
On: Red LED only
Off: 3 LEDs
DIP 7: Anti masking operation On: Enabled Off: Disabled
DIP 8: Proximity AM On: Enabled Off: Disabled
Microwave Adjustment
Adjust the Microwave coverage area by using the trimmer on the PCB.
Walk test
Two minutes after applying power, walk test the protected area to verify
proper operation.
For installations on uneven surfaces slide the PCB inside the internal base to
the appropriate setting according to the desired height (1.0m, 1.5m, 2.2m,
2.7m) as printed on the bottom left corner of the PCB or use the standard
swivel accessory.
For reducing the detection range, slide the PCB up or tilt the swivel down.
LEDs Display
LED | State | Description |
---|---|---|
YELLOW | Steady | Indicates PIR detection |
Flashing | Indicates Active IR AM (Anti mask) detection | |
GREEN | Steady | Indicates MW detection |
Flashing | Indicates Proximity AM detection | |
RED | Steady | Indicates ALARM |
Flashing | Indicates malfunctioned communication with ProSYS (BUS mode only) | |
All LEDs | Flashing (One after another) | Unit initialization on power-up |
Notes:
- DIP-Switch 1 should be in the ON position to enable LED indications.
- Only one LED is active at any one time. For example, in the case of both PIR and MW detection, either the steady YELLOW LED or the steady GREEN LED is displayed (the first to detect), followed by the Alarm RED
- In order to prevent the analysis of detection technologies such as PIR, Microwave, Active IR AM, and Proximity AM, set DIP Switch 6 (SW1) to ON. Only the red LED will be activated.
Relay Mode/BUS Mode Jumper
J-BUS jumper (located on the PCB between the red and green LEDs) is used to
define the detector’s mode of operation as follows:
Standard Swivel Installation
The Outdoor detector packaging contains a standard swivel for flexible
installation. Please follow the instructions below for mounting the detector
with the Standard Swivel:
-
Open WatchOUT front cover (Unlock C1, Figure1).
-
Release internal base (Unlock I1, Figure 2).
-
Open knockouts on an external base (Figure 6, Detail B)
• W1: Wires knockout
• S1, S2: Knockouts for securing the external base to Standard Swivel
• S3: External base locking screw knockout -
On the swivel, the accessory removes the required swivel cable wiring knockout S2, S7 or S9 (Figure 6, Detail A).
-
Remove the back tamper from the internal base (see “Changing Back Tamper Position” paragraph) and connect it to S5 (Figure 6, Detail A) on the Standard Swivel.
Note:
Ensure that you see the engraved UP mark on the upper front face of the swivel. -
Select the mounting installation type as follows:
Wall Mounting
a. Insert external cable wiring through knockouts S2, S7, or S9 and extract them (including the tamper wires) through the Swivel Wires Passage (Figure 6, Detail B).
b. Secure swivel to the wall through holes S1, S3, S6, and S8.
Swivel Conduit Mounting (using Conduit Metal Swivel Adaptor – CSMA, Figure 6, Detail A)
Note:
The CSMA is required when wall external wiring is used and a protection pipe is required. The CSMA should be ordered separately – P/N RA300SC0000A.
a. Choose the direction upon which to mount the CSMA according to the required diameter: 16mm (0.63 inches) or 21mm (0.83 inches).
b. Insert conduit to the CSMA.
c. Secure CSMA to the wall through points (M1, M4).
d. Insert external cables and tamper wires from the conduit through the swivel wires passage of the swivel (Figure 6, Detail A).
e. Secure swivel to the wall through holes S1, S3, S6, and S8.
Note:
The Tamper spring S5 (Figure 7) should make contact with the wall through the tamper spring holes M2 or
M3 on the CSMA. Make sure to hear the tamper “Click” when connecting to the wall. -
Insert tamper wires and external cable wiring from Standard Swivel through knockout W1 on the external base (Figure 6, Detail B).
-
Connect the external base to the swivel using the dedicated snaps (Figure 7).
Note:
Do not open or close the Swivel Assy Screw since it is used for connecting the swivel parts only. -
Secure external base to swivel with two screws fastened to knockouts S1 and S2 (Figure 7).
-
Insert the supplied angle locking screw from the external base through the angle locking screw knockout S3 on the external base to the standard swivel (Figure 7).
-
Tilt and Rotate the Standard Swivel to the desired position. Once the Standard Swivel is in the desired position, secure the angle locking screw.
-
Line up the internal base onto the external base. Insert all wiring cables through the internal base.
-
Secure internal base to external base (Lock I1, Figure 2).
-
To readjust the Standard Swivel when the PCB is installed (Figure 7):
a. Bend down the black foam located below the RED LED on the PCB (enough to reach the Swivel locking screw).
b. Use a Philips screwdriver to release the locking screw (see Figure 8).
c. Tilt and/or Rotate the Standard Swivel to the desired position.
d. Secure the angle locking screw.
Note:
When marks on the two movable parts are aligned (Figure 8), the Standard Swivel is in 0° vertical /horizontal position. Each click from this position represents a shifting of 5° in a vertical/horizontal position. -
Close the front cover (Lock C1, Figure 1) and walk test the detector.
Note:
The screw has to pass through External Base and be locked to the swivel.
Replacing Lenses
- Unlock the six screws that hold the lens holding sleeve from the back of the front cover.
- To release the protective sleeve, gently push the lens from the external side of the front cover.
- Disconnect the lens from the sleeve by gently pushing the lens clips that secure it to the sleeve.
- Replace the lens. Place the 4 clips of the lens into the matching holes on the sleeve.
- Insert the protective sleeve back into place on the front cover. Pay attention to placing the sleeve over the sealing rubber.
- Secure the 6 holding screws back to their place.
Lens Types
Note:
The detector’s Pet Immunity (height of an animal, no weight limit), is up to
70 cm (2’4″), when installing the detector at 2.2m (7’2″). If the installation
is below the height mentioned above, the Pet Immunity decreases accordingly;
every 10 cm (4″) decrease in installation height leads to a 10 cm (4″)
decrease in pet immunity.
Technical Specification
Electrical
Current consumption| 30mA at 12 VDC (Stand by)
42mA at 12 VDC (MAX with LED ON)
Voltage requirements| 9 -16 VDC
Alarm contacts| 24 VDC. 0.1A
AM contacts| 24 VDC. 0.1A
Dust output| Open collector 70mA max
Physical|
Size: LxWxD| 230 x 123 x 124mm (9 x 4.8 x 4.88 in.)
Weight| 0.632 Kg (1.41b)
Environmental
RF immunity According to EN50130-4
Operating/Storage temperature I -30°C to 60°C (-22°F to 140°F)
Ordering Information
Standard Units
Model | Description |
---|---|
WatchOUT 315DT | WatchOUT DT + Swivel |
Note:
Each of the detectors contains a standard swivel and 3 replacement lenses (P/N
engraved on the Lens) 1.7m low installation pet (RL300F), long-range (RL300R),
and barrier lens (RL300B).
Accessories Kits
Model | Description | Weight |
---|---|---|
RA300B | WatchOUT Barrier Swivel Kit | 0.1 Kg (0.23 lb) |
RA300P | WatchOUT Pole Adaptor Kit | 0.25 Kg (0.55 Ib) |
RA300C | WatchOUT Conduit Adaptor Kit | 0.6 Kg (1.27 Ib) |
RA300HS | WatchOUT Demo Housing | – – |
RA300SC | WatchOUT Swivel Metal Conduit Adaptor | 1Kg (2.2 Ib) |
Camera Option
Model | Description |
---|---|
WatchOUT VC1 | WatchOUT Camera Cover Adaptor |
WatchOUT VC017 | WatchOUT Narrow Camera |
WatchOUT VCO53 | WatchOUT Wide Camera |
WatchOUT VCPS | WatchOUT Camera 220V Power Supply |
WatchOUT VCPS | WatchOUT Camera 120V Power Supply |
UL Compliance Section
To comply with UL, note the following:
-
The unit is intended for outdoor installation where unwanted alarms are tolerable. If not, it is recommended to connect it to the trouble circuit of a listed compatible control unit.
-
A dead zone of 5 ft should be considered during installation.
-
The camera option is not UL listed.
-
Disclaimer: PET feature has not been tested or verified by UL.
0.6 power factor inductive load can be used on the relays. -
Relay mode is intended to be connected to a listed compatible control unit or power supply that provides 4 hours of standby power.
-
It may be necessary to set the detector at maximum sensitivity to achieve maximum distance.
-
Do not connect the DUST output to a UL-listed product.
-
When the detectors are connected to the BUS of the ProSYS panel, the detectors are to be powered from either the ProSYS (Version 7.55) panel or a listed compatible burglar alarm power supply that has an output voltage range that does not exceed 9-16 VDC, has a minimum of 4 hrs. of standby power, and is suitable for mercantile use.
BUS Mode Installation
Introduction
The information in this section relates to WatchOUT 315DT installation in BUS
Mode only. Up to 32 BUS detectors can be installed on the ProSYS RS485 BUS,
saving cabling time and enabling remote control and diagnostics.
Terminal Wiring
+,-| Used for the connection of 12VDC power supply. Connect the (+) terminal
to the AUX RED and the (—) terminal to the COM BLK of the ProSYS terminals
---|---
YELLOW| Used for data communication with the ProSYS. Connect to the terminal
to the BUS YEL of the ProSYS
GREEN| Used for data communication with the ProSYS. Connect to the terminal to
the BUS GRN of the ProSYS
TAMPER| Used for the wiring for tamper detection. see below
LED ENABLE| Used for the wiring for tamper detection. see below
Note:
All terminals that are not mentioned in the table above are unused.
DIP Switch Settings
DIP Switch Number | Description |
---|---|
01-May | Used to set the detector ID number. Set the ID number in the same way |
as for any other ProSYS accessory (Refer to the ProSYS installation
instruction manual)
06-Aug| Not used
without ID: DIP Switches 1 – 5
ID | 1 | 2 | 3 | 4 | 5 |
---|---|---|---|---|---|
1 | OFF | OFF | OFF | OFF | OFF |
2 | ON | OFF | OFF | OFF | OFF |
3 | OFF | ON | OFF | OFF | OFF |
4 | ON | ON | OFF | OFF | OFF |
5 | OFF | OFF | ON | OFF | OFF |
6 | ON | OFF | ON | OFF | OFF |
7 | OFF | ON | ON | OFF | OFF |
8 | ON | ON | ON | OFF | OFF |
9 | OFF | OFF | OFF | ON | OFF |
10 | ON | OFF | OFF | ON | OFF |
11 | OFF | ON | OFF | ON | OFF |
12 | ON | ON | OFF | ON | OFF |
13 | OFF | OFF | ON | ON | OFF |
14 | ON | OFF | ON | ON | OFF |
15 | OFF | ON | ON | ON | OFF |
16 | ON | ON | ON | ON | OFF |
17 | OFF | OFF | OFF | OFF | ON |
18 | ON | OFF | OFF | OFF | ON |
19 | OFF | ON | OFF | OFF | ON |
20 | ON | ON | OFF | OFF | ON |
21 | OFF | OFF | ON | OFF | ON |
22 | ON | OFF | ON | OFF | ON |
23 | OFF | ON | ON | OFF | ON |
24 | ON | ON | ON | OFF | ON |
25 | OFF | OFF | OFF | ON | ON |
26 | ON | OFF | OFF | ON | ON |
27 | OFF | ON | OFF | ON | ON |
28 | ON | ON | OFF | ON | ON |
29 | OFF | OFF | ON | ON | ON |
30 | ON | OFF | ON | ON | ON |
31 | OFF | ON | ON | ON | ON |
32 | ON | ON | ON | ON | ON |
ProSYS Programming
The following section describes the additional software programming options,
added to the ProSYS software, that concern the settings of the WatcOUT DT as a
BUS detector. Up to 32 BUS detectors can be added to the system (16 in ProSYS
16) and each of them comes at the expense of a zone in the system.
It is recommend reading and fully understand the ProSYS Installation and User
Manuals, before programming the WatchOUT.
Notes:
The WatchOUT is compatible with the ProSYS software Version 4. xx and above.
The without can be programmed via the U/D Software from UD Version 1.8 and
above.
For maximum operation stability, it is best NOT to exceed a total of 300
meters (1000 feet) of wiring when connecting the WatchOUT to the BUS.
Adding / Deleting the WatchOUT DT
The WatchOUT is part of a new accessory category, BUS zones. Therefore,
Adding/Deleting the
WatchOUT is identical to any other accessory with the following exception:
Each BUS Zone Detector should be assigned to a Regular Zone.
Any BUS detector can be assigned to a physically wired zone or to a virtual
zone.
Physical zone: Any zone on the ProSYS PCB (zones 1-8) or on a wired zone
expander (ZE08, ZE16).
Virtual zone: Any zone on a BUS zone expander defined as BZ08 or BZ16.
Notes:
Virtual BUS zones are cost-effective. They enable you to expand your system
zones without adding physical zone expanders.
The virtual BUS zone expander can be used only for BUS zone detectors.
To add a BUS zone expander select type BZ08 or BZ16 when adding a zone
expander (Quick key [7][1][2] ).
-
To Add / Delete the WatchOUT DT
1. From the installer menu enter the Add/Delete menu: Quick Key [7][1][9][5] for BUS Zones detectors.
2. Use the keys to position the cursor over the BUS ZoneID number for which you want to assign (or delete) a detector.
Note:
Make sure that the detector’s physical ID number is identical to the ID number you select during programming.
3. Place the cursor on the TYPE field and use the key to select ODT15 for the WatchOUT DT detector.
4. Press to confirm.
5. Repeat the process for the other BUS detectors. -
Assigning the WatchOUT DT to a Zone
1. From the main installer menu enter Zones: One by One option (Quick key [2][1])
2. Select the zone number that you want to assign the BUS detector.
Note:
If you defined a BUS Zone Expander, select a zone number from the virtual zones (defined by the BUS zone expander).
3. Define Partitions, Groups, Zone Type, and Zone Sound.
4. In the Termination category select [5] BUS Zone followed by The following display appears:
Z:001 LINK TO:
ID:01 TYPE=ODT15
5. Select the BUS zone number to assign to the programmed zone. The type field will be updated automatically when selecting the zone.
6. Press The loop response category is not applicable to a BUS zone and the following display appears:
Z:001 RESPONSE:
N/A-BUS ZONE
7. Press assign label and press . -
Configuring the WatchOUT DT Parameters
1. To access the WatchOUT settings option press [2][0][3] from the main installer menu. The following display appears:
B-ZONE PRMS:
ZONE#=001 (M:ZZ)
2. Select the zone that the BUS zone was assigned to and press You can now program the WatchOUT parameters as follows:
Zones Miscellaneous: BUS Zone
Quick Keys
|
Parameter Default
---|---
[2][0][3][zzz] [1]| LEADS 3 LEDS
Defines the LEDs operation mode.
[2][0][3][zzz] [1][1]| Off
Disables the LEDS operation.
[2][0][3][zzz] [1][2]| Red Only
Only the Red led will operate. This option is highly recommended to avoid the
possibility that the intruder will -Learn- the detector behavior.
[2][0][3][zzz] [1][3]| 3 LEDS
All 3 LEDs will operate.
[2][0][3][zzz] [2]| PIR Sensitivity Normal
Defines the sensitivity of the detector(MW + PIR)
[2][0][3][zzz] [2][1]..[4]| Sensitivity Options
1)Low
2)Medium| 3)Normal
4)High
[2][0][3][zzz] [3]| MW Range Trimmer
Defines the microwave channel range. The maximum is 23m.
[2][0][3][zzz] [3][1]..(71| MW Range options
1)Minimum 3) 40% 5) 80% 7) Trimmer (MW is defined 2)20% 4) 60% 6) Maximum by
the trimmer setting on the PCB)
[4[2][0][3][zzz] ]| Anti-Mask sensitivity Low sensitivity
Defines the sensitivity of the active IR AM
[2][0][3][zzz] [4][1]..[2]| Anti-Mask sensitivity option
- Low Sensitivity 2) High Sensitivity
[2][0][3][zzz] [5]| Lens Type Wide Angle
Defines the actual Lens of the detector
[2][0][3][zzz] [5][1]..[2]| Lens Type Options - Wide Angle 2) Barrier / Long Range
[2][0][3][zzz] [6]| Anti-Mask Enable
Defines the operation of Anti Masking detection
[2][0][3][zzz] [6][1]..[2]| Anti-Mask Options - Disable 2) Enable (Default)
[2][0][3][zzz] M| Arm/Disarm No
Defines the operation of the LEDs anti-masking detections while the detector is armed
[2][0][3][zzz] MIll| No
Active IR AM and Proximity AM (Anti masking) is enabled
LEDs behave according to the LEDs parameter definition
[2][0][3][zzz] [7][2]| Yes
Active IR AM and Proximity AM (Anti masking) is disabled LEDs are disabled
[2][0][3][zzz] [8]| Proximity AM Disable
Defines the operation of the Proximity Anti Masking detection
[2][0][3][zzz] [8][1]..[2]| Proximity AM Options - Disable (Default) 2) Enable
NOTE: Disable Proximity AM during heavy rain (if WatchOUT 315DT is not sheltered) to prevent Proximity AM alerts.
System Parameters
System: System Control
Quick Keys | Parameter Default: |
---|---|
[1][2][36] | IR AM=Tamper No |
Used to determine the operation of Active IR Anti Masking detection Yes:
Active IR Anti mask detection will activate a tamper alarm.
No: Active IR Anti mask detection will be regarded as a trouble event.
M[4[37]| Prox AM=Tamper No
Used to determine the operation of the Proximity Anti Masking detection Yes:
Proximity Anti mask detection will activate the tamper alarm.
No: Proximity Anti mask detection will be regarded as a trouble event.
Diagnostics
The ProSYS enables you to test parameters that reflect the operation of the
detector.
- From the main user menu press [4] to access the Maintenance menu.
- Enter the Installer code (or sub-installer) and press .
- Press [9] [1] for the BUS Zones diagnostic menu.
- Enter the digit of the zone that you want to test and then press . The system will perform the diagnostics test and a list of test parameters will appear, as indicated in the table below.
- Use the keys to view the diagnostics test results.
User Menu: 4) Maintenance →9) Diagnostic →1) BUS Zone
Quick Keys | Parameter |
---|---|
[4][9][1][zzz] | Detector Input Voltage: Display the input voltage of the |
detector.
PIR 1 Level: PIR channel 1 DC level. Range 0.1v – 4v
PIR 1 Noise Level: PIR channel 1 AC level. Range 0VAC (No noise) – 4VA
PIR 2 Level: PIR channel 2 DC level. Range 0.1v – 4v
PIR 2 Noise Level: PIR channel 2 AC level. Range 0VAC (No noise) – 4VA
MW 1 Level:
MW channel 1 DC level Range 0.1v – 4v
MW 1 Noise Level:
MW channel 1 AC level (0VAC (No noise) – 4VAC)
MW 2 Level: MW channel 2 DC level Range 0.1v – 4v
MW 2 Noise Level: MW channel 2 AC level (0VAC (No noise) – 4VAC
WatchOUT 315DT FCC Compliance Section (US version):
FCC Part 15 Note:
This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to Part 15 of the FCC rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more
of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment to an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician.
FCC Warning:
The manufacturer is not responsible for any radio or TV interference caused by
unauthorized modifications to this equipment. Such modifications could void
the user’s authority to operate the equipment.
FCC ID: JE41CAV005
CE Compliance Section (European and German versions):
Risco Ltd. hereby declares that this equipment is in compliance with the
essential requirements and other relevant provisions of Directive 1999/5/EC.
For the CE Declaration of Conformity please refer to our website:
www.riscogroup.com.
WatchOUT 315DT applicable countries (European version):
WatchOUT 315DT applicable countries (German Version):
AT, CZ, SL, DE, TR, RU, EE
Notes
RISCO Group Limited Warranty
RISCO Group and its subsidiaries and affiliates (“Seller”) warrant its
products to be free from defects in materials and workmanship under normal use
for 24 months from the date of production. Because Seller does not install or
connect the product and because the product may be used in conjunction with
products not manufactured by the Seller, Seller cannot guarantee the
performance of the security system which uses this product. Seller’s
obligation and liability under this warranty are expressly limited to
repairing and replacing, at Seller’s option, within a reasonable time after
the date of delivery, any product not meeting the specifications. Seller makes
no other warranty, expressed or implied, and makes no warranty of
merchantability or of fitness for any particular purpose.
In no case shall the seller be liable for any consequential or incidental
damages for breach of this or any other warranty, expressed or implied, or
upon any other basis of liability whatsoever.
The seller’s obligation under this warranty shall not include any
transportation charges or costs of installation or any liability for direct,
indirect, or consequential damages or delay.
Seller does not represent that its product may not be compromised or
circumvented; that the product will prevent any personal injury or property
loss by burglary, robbery, fire, or otherwise; or that the product will in all
cases provide adequate warning or protection.
Seller, in no event, shall be liable for any direct or indirect damages or any
other losses that occurred due to any type of tampering, whether intentional
or unintentional such as masking, painting, or spraying on the lenses,
mirrors, or any other part of the detector.
The buyer understands that a properly installed and maintained alarm may only
reduce the risk of burglary, robbery, or fire without warning, but is not
insurance or a guarantee that such event will not occur or that there will be
no personal injury or property loss as a result thereof.
Consequently, the seller shall have no liability for any personal injury,
property damage, or loss based on a claim that the product fails to give a
warning. However, if the seller is held liable, whether directly or
indirectly, for any loss or damage arising under this limited warranty or
otherwise, regardless of cause or origin, the seller’s maximum liability shall
not exceed the purchase price of the product, which shall be the complete and
exclusive remedy against the seller.
No employee or representative of Seller is authorized to change this warranty
in any way or grant any other warranty.
WARNING: This product should be tested at least once a week.
RTTE Compliance Statement:
Hereby, RISCO Group declares that this equipment is in compliance with the
essential requirements and other relevant provisions of Directive 1999/5/EC.
For the CE Declaration of Conformity please refer to our website:
www.riscogroup.com.
Contacting RISCO Group
RISCO Group is committed to customer service and product support. You can
contact us through our website
(www.riscogroup.com) or at the following
telephone and fax numbers:
United Kingdom
Tel: +44-161-655-5500
E-mail: support-uk@riscogroup.com|
USA
Tel: +1-631-719-4400
E-mail: support-usa@riscogroup.com
---|---
Italy
Tel: +39-02-66590054
E-mail: support-it@riscogroup.com |
China (Shanghai)
Tel: +86-21-52-39-0066
E-mail: support-cn@riscogroup.com
Spain
Tel: +34-91-490-2133
E-mail: support-es@riscogroup.com |
Australia
Tel: +1-800-991-542
E-mail: support-au@riscogroup.com
France
Tel: +33-164-73-28-50
E-mail: support-fr@riscogroup.com |
Israel
Tel: +972-3-963-7777
E-mail: support@riscogroup.com
Belgium
Tel: +32-2522-7622
E-mail: support-be@riscogroup.com
This RISCO product was purchased at:|
---|---
All rights reserved.
No part of this document may be reproduced in any form without prior written
permission from the publisher.
Only P/N: RK315DT00USB is UL approved
© RISCO Group 04/2015
Documents / Resources
| RISC
GROUP RK315DT0000C WatchOUT
Extreme
[pdf] Instruction Manual
RK315DT0000C WatchOUT Extreme, RK315DT0000C, WatchOUT Extreme
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>