2682600000 IE-CS-MBGW-2TX-1COM Serial/
Ethernet Converter/Modbus Gateway
Installation Guide
Introduction
Device IE-CS-MBGW-2TX-1COM is a multi-purpose Serial/Ethernet converter and
Modbus TCP/RTU-ASCII protocol gateway and is equipped with one configurable
RS232/422/485 port and two Ethernet RJ45 ports (acting like an unmanaged
2-Port switch).
If configured as a Serial/Ethernet converter it can be used to convert data
streams between serial and Ethernet networks. The converter supports standard
device server features like Virtual COM Mode, TCP Server/Client, or UDP
Server/Client operation modes.
Running as a Modbus protocol gateway it can be used to convert data streams
between protocols Modbus TCP (Ethernet) and Modbus ASCII/RTU (serial-based).
The device supports the operation modes “ASCII/RTU Master to TCP Slave
Gateway” and “TCP Master to ASCII/RTU Slave Gateway”.
The devices are designed for industrial applications and fitted with robust
housing. To ensure reliable, error-free operation, and to prevent damage or
injury, please read the operating instructions, all safety information
provided in this document, and any other safety information that was supplied
with the product.
Safety notice
| The device heats up during operation. Allow the unit to cool down or use
protective gloves when carrying out any work.
---|---
| The device may only be connected to the supply voltage shown on the product
label.
A higher voltage than specified will destroy the device.
The device must be supplied by a SELV source as defined in the Low Voltage
Directive 2014/35/EU and 2014/30/EU.
| Installation, commissioning, and maintenance may only be performed by
qualified electricians.
| Observe the operating instructions.
| • Indoor use and pollution degree II, it must be wiped with a dry cloth to
clean up the device and label.
• Do not block air ventilation holes.
• If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
• Shall be mounted in the Industrial Control Panel and the ambient temperature
does not exceed 70 degrees C.
---|---
Intended use: The device is intended for the realization of communication
networks within an industrial environment, it is intended to be used in a
restricted access location. The device may only be used within the scope of
the specified technical data. The device is intended to be mounted to a well-
grounded mounting surface, such as a metal panel. Any other use may result in
unintentional malfunction and damage. Observing the documentation is part of
the intended use.
Environmental conditions: This equipment is intended to be used in a
restricted access location. When planning the installation site make sure that
the ambient temperature during operation will not exceed the temperature given
in the technical data.
Also, make sure that the airflow will not be compromised by other devices.
Ensure that the mounted and wired device is not exposed to any mechanical
stress.
FCC compliance: This device complies with part 15 of FCC Rules. Operation
is subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Package Checklist
1 x Serial/Ethernet-Converter/Modbus-Gateway| 1 x Serial/Ethernet-Converter
/Modbus-Gateway
---|---
1 x 4-Pin Terminal connector| 1 x Wall mounting kit
Panel Layouts
IE-CS-MBGW-2TX-1 COM
Front Panel View
-
Terminal block for power input PWR1/PWR2
-
Grounding screw / Frame ground (Note: The shielding ground of the LAN port is electrically connected to the grounding screw)
-
Power input LEDs (PWR1 / PWR2)
-
Link/Activity LEDs Ethernet Ports
-
Data Transmission LEDs Serial Port
-
Serial Port (DB9 male Connector)
-
DIP Switches for serial line settings SW1: Sets Pull-Up resistor to 1 KΩ (ON) or 150 KΩ (OFF).
SW2: Sets Pull-Down resistor to 1 KΩ (ON) or 150 KΩ (OFF).
SW3: Enables / Disables Line Termination.
By factory default, all DIP switches are set to OFF. -
Ethernet RJ45 Ports 10/100BASE-T(X)
-
Article Number
-
Reset Button
-
DIN-rail kit
Mounting Dimensions
DIN-Rail Mounting
Slide the device onto DIN-rail and make sure that the Din-rail clip clicks
into the rail firmly.
STEP 1: Insert the top of the DINRail into the slot just below the stiff
metal spring.
STEP 2: The DIN-Rail attachment unit will snap into place as shown below.
To remove the device from the DIN rail simply reverse steps 1 and 2.
Grounding
| ATTENTION
– Grounding and wire routing help limit the effects of noise due to
electromagnetic interference (EMI).
– Do the ground connection from the ground screw to the grounding surface
prior to connecting devices.
– This product is intended to be mounted to a well-grounded mounting surface,
such as a metal panel.
– The shielding ground of the RJ45 ports is electrically connected to the
ground connection (screw).
---|---
| Warning
• Take into consideration the following guidelines before wiring the device
• The terminal block is mating with Plug and is suitable for 12-24AWG. Torque
value 4.5 lb-in.
• The temperature rating of the input connection cable should be higher than
105°C.
• Supplied by SELV source evaluated by UL 61010-1 or 61010-2-201 power supply
only.
Communication Connections
The Converter/Gateway is equipped with:
2 x RJ45 Ethernet Port 10/100BASE-T(X)/Auto MDI-X
1 x Serial Interface (DB9 male connector)
Please use RJ45 Ethernet Ports only cables suitable for the respective type of
communication and ensure that signals are protected from possible
interference.
10/100BASE-T(X) RJ45 Ports
The 10/100BASE-T(X) ports are used to connect to Ethernet-enabled devices. The
below table shows pinouts for both MDI (NIC-type) ports and MDI-X (HUB/Switch-
type) ports. Auto MDI-X ensures that both wiring schemes are supported
(Automatic crossover).
MDI Port Pinouts | MDI-X Port Pinouts | 8-pin RJ45 |
---|---|---|
Pin | Signal | Pin |
1 | Tx+ | 1 |
2 | Tx- | 2 |
3 | Rx+ | 3 |
6 | Rx- | 6 |
Serial Interface DB-9 Connector
Pinouts DB-9 Connector (male)
Pin #| RS-232
(DTE Device)| RS 422 1| RS-48511
(4-wire)| RS-485
(2-wire)|
---|---|---|---|---|---
1| DCD| RX-| RX-| DATA-|
2| RXD| RX+| RX+| DATA+
3| TXD| TX+| TX+| —
4| DTR| TX-| TX-| —
5| GND| GND| GND| GND
6| DSR| —| —| —
7| RTS| | | —
8| CTS| | | —
9| RI| —| —| —
Note: Table with correct pinouts for RS-422 and RS-485 4-wire interface modes. In previous document V1.3, the assignments for RX-/RX+ and TX-/TX+ were reversed!
Device Access (Login to Web Interface)
For configuration, the Web interface can be accessed via the following factory default settings:
IP address / Netmask: | 192.168.1.110 / 255.255.255.0 |
---|---|
Username: | admin |
Password: | Weidmueller |
Connect the PC to any Ethernet port of the Converter/Gateway and set the PC’s
IP address to a free one in the range 192.168.1.0 / 255.255.255.0
Start a web browser and enter the IP address of the connected device into the
browser’s address line (http://192.168.1.110).
After the appearance of the prompt (login) enter the login credentials. After
confirmation of your input with “OK,” the home page of the Converter/Gateway
will be displayed.
Device Reset
- Press the reset button for < 5 seconds to reboot the device (Warm Start).
- Press the reset button for >= 5 seconds to reset the Converter/Gateway to factory-default settings.
LED Indicators
Description of front panel LED indicators:
LED | Color | Status | Description |
---|---|---|---|
PWR1 | Green | On | Power is supplied to power input PWR1. |
PWR2 | Green | On | Power is supplied to power input PWR2. |
Eth1 | Green | On | Ethernet Port 1 is connected. |
Blinking | Data is transmitted. | ||
Eth2 | Green | On | Ethernet Port 2 is connected. |
Blinking | Data is transmitted. | ||
Rx | Amber | On | Receiving serial data. |
Tx | Green | On | Transmitting serial data. |
Disposal information
Observe the notes for proper disposal of the product. You can find the notes here:
https://www.weidmueller.com/disposal
Specifications
Interfaces
Ethernet Ports| 2 x RJ45 10/100BASE-T(X) auto-negotiation speed, F/H duplex
mode and auto MDI/MDI-X connection
Serial Port| lx DB9 connector (male)
• Interface Settings RS-232/422/485
• Baud Rates 110 bps to 460800 bps
• Data Bits 7, 8
• Parity odd, even, none, mark, space
• Stop Bits 1, 2
• RS-232: TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
• RS-422: Rx-, Rx+, Tx+, Tx-, GND
• RS-485 4 wire: Rx-, Rx+, Tx+, Tx-, GND
• RS-485 2 wire: Data-, Data+, GND
• Flow Control XON/XOFF, RTS/CTS, DTR/DSR
LED Indicators| PWR 1 / 2 (Power supply)
Eth 1 / 2 (Ethernet Port Link / Activity)
Tx / Rx (Serial Port Data Transmit / Receive)
DIP Switch| SW1:Sets Pull-Up resistor to 1 KO (ON) or 150 0 (OFF) SW2:Sets
Pull-Down res. to 1 KO (ON) or 150 KO (OFF) SW3: Enables (ON) / Disables (OFF)
Line Termination
Power supply
Input Voltage| 24 V DC (12 to 48 V DC), 2 redundant inputs
Current Consumption| 0.05 A — 0.1 A
Connection| One removable 4-pin terminal block, Wiring cable 12- 24AWG
Overload Current Protection| Present
Reverse Polarity Protection| Present
Physical Characteristics
Housing| IP30 protection, metal
Dimension (W x H x D)| 26.1 x 110 x 75.2 mm (1.02 x 4.33 x 2.95 inch)
Weight| 200 g
Installation| DIN-rail, Wall
Environmental conditions
Operating Temperature| -40 to 70°C (-40 to 158°F)
Storage Temperature| -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity| 5 to 95% (non-condensing)
Altitude| up to 2000 m
Regulatory Approvals
Safety| UL 61010-1; UL 61010-2-201
EMC| EN 55032, EN 55024, FCC Part 15 Subpart B Class A, IEC 61000-4-2 ESD:
Contact: 4 kV; Air: 8 kV,
IEC 61000-4-3 RS: 80 MHz bis 1 Ghz: 3 V/m,
IEC 61000-4-4 EFT: Power: 0.5 kV; Signal: 0.5 kV, IEC 61000-4-5 Surge: Power:
0,5 kV; Signal: 1 kV, IEC 61000-4-6 CS: 3 Vrms
Shock| IEC 60068-2-27
Free Fall| IEC 60068-2-31
Vibration| IEC 60068-2-6
MTBF
Time| 1.479.078 hrs
Database| Telcordia SR332
Warranty
Time Period| 15 years
Contact Information
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26, 32758 Detmold / Germany
Phone +49 (0) 5231 14-0, Fax +49 (0) 5231 14-292083
E-Mail weidmueller@weidmueller.com,
Internet www.weidmueller.com