Weidmueller 2682600000 IE-CS-MBGW-2TX-1COM Serial/Ethernet Converter/Modbus Gateway Installation Guide

June 5, 2024
Weidmueller

2682600000 IE-CS-MBGW-2TX-1COM Serial/
Ethernet Converter/Modbus Gateway
Installation Guide

Introduction

Device IE-CS-MBGW-2TX-1COM is a multi-purpose Serial/Ethernet converter and Modbus TCP/RTU-ASCII protocol gateway and is equipped with one configurable RS232/422/485 port and two Ethernet RJ45 ports (acting like an unmanaged 2-Port switch).
If configured as a Serial/Ethernet converter it can be used to convert data streams between serial and Ethernet networks. The converter supports standard device server features like Virtual COM Mode, TCP Server/Client, or UDP Server/Client operation modes.
Running as a Modbus protocol gateway it can be used to convert data streams between protocols Modbus TCP (Ethernet) and Modbus ASCII/RTU (serial-based). The device supports the operation modes “ASCII/RTU Master to TCP Slave Gateway” and “TCP Master to ASCII/RTU Slave Gateway”.
The devices are designed for industrial applications and fitted with robust housing. To ensure reliable, error-free operation, and to prevent damage or injury, please read the operating instructions, all safety information provided in this document, and any other safety information that was supplied with the product.

Safety notice

| The device heats up during operation. Allow the unit to cool down or use protective gloves when carrying out any work.
---|---
| The device may only be connected to the supply voltage shown on the product label.
A higher voltage than specified will destroy the device.
The device must be supplied by a SELV source as defined in the Low Voltage
Directive 2014/35/EU and 2014/30/EU.
| Installation, commissioning, and maintenance may only be performed by qualified electricians.
| Observe the operating instructions.
| • Indoor use and pollution degree II, it must be wiped with a dry cloth to clean up the device and label.
• Do not block air ventilation holes.
• If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
• Shall be mounted in the Industrial Control Panel and the ambient temperature does not exceed 70 degrees C.
---|---

Intended use: The device is intended for the realization of communication networks within an industrial environment, it is intended to be used in a restricted access location.  The device may only be used within the scope of the specified technical data. The device is intended to be mounted to a well- grounded mounting surface, such as a metal panel.  Any other use may result in unintentional malfunction and damage. Observing the documentation is part of the intended use.
Environmental conditions: This equipment is intended to be used in a restricted access location. When planning the installation site make sure that the ambient temperature during operation will not exceed the temperature given in the technical data.
Also, make sure that the airflow will not be compromised by other devices.
Ensure that the mounted and wired device is not exposed to any mechanical stress.
FCC compliance: This device complies with part 15 of FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference,  and (2) this device must accept any interference received, including interference that may cause undesired operation.

Package Checklist

1 x Serial/Ethernet-Converter/Modbus-Gateway| 1 x Serial/Ethernet-Converter /Modbus-Gateway
---|---
1 x 4-Pin Terminal connector| 1 x Wall mounting kit

Panel Layouts

IE-CS-MBGW-2TX-1 COM
Front Panel View

  1. Terminal block for power input PWR1/PWR2

  2. Grounding screw / Frame ground (Note: The shielding ground of the LAN port is electrically connected to the grounding screw)

  3. Power input LEDs (PWR1 / PWR2)

  4. Link/Activity LEDs Ethernet Ports

  5. Data Transmission LEDs Serial Port

  6. Serial Port (DB9 male Connector)

  7. DIP Switches for serial line settings SW1: Sets Pull-Up resistor to 1 KΩ (ON) or 150 KΩ (OFF).
    SW2: Sets Pull-Down resistor to 1 KΩ (ON) or 150 KΩ (OFF).
    SW3: Enables / Disables Line Termination.
    By factory default, all DIP switches are set to OFF.

  8. Ethernet RJ45 Ports 10/100BASE-T(X)

  9. Article Number

  10. Reset Button

  11. DIN-rail kit

Weidmueller 2682600000 IE CS MBGW 2TX 1COM Serial Ethernet Converter Modbus
Gateway - figure 2

Mounting Dimensions

DIN-Rail Mounting

Slide the device onto DIN-rail and make sure that the Din-rail clip clicks into the rail firmly.
STEP 1: Insert the top of the DINRail into the slot just below the stiff metal spring.
STEP 2: The DIN-Rail attachment unit will snap into place as shown below.
To remove the device from the DIN rail simply reverse steps 1 and 2.

Grounding

| ATTENTION
– Grounding and wire routing help limit the effects of noise due to electromagnetic interference (EMI).
– Do the ground connection from the ground screw to the grounding surface prior to connecting devices.
– This product is intended to be mounted to a well-grounded mounting surface, such as a metal panel.
– The shielding ground of the RJ45 ports is electrically connected to the ground connection (screw).
---|---
| Warning
• Take into consideration the following guidelines before wiring the device
• The terminal block is mating with Plug and is suitable for 12-24AWG. Torque value 4.5 lb-in.
• The temperature rating of the input connection cable should be higher than 105°C.
• Supplied by SELV source evaluated by UL 61010-1 or 61010-2-201 power supply only.

Communication Connections

The Converter/Gateway is equipped with:
2 x RJ45 Ethernet Port 10/100BASE-T(X)/Auto MDI-X
1 x Serial Interface (DB9 male connector)
Please use RJ45 Ethernet Ports only cables suitable for the respective type of communication and ensure that signals are protected from possible interference.

10/100BASE-T(X) RJ45 Ports
The 10/100BASE-T(X) ports are used to connect to Ethernet-enabled devices. The below table shows pinouts for both MDI (NIC-type) ports and MDI-X (HUB/Switch- type)  ports. Auto MDI-X ensures that both wiring schemes are supported (Automatic crossover).

MDI Port Pinouts MDI-X Port Pinouts 8-pin RJ45
Pin Signal Pin
1 Tx+ 1
2 Tx- 2
3 Rx+ 3
6 Rx- 6

Serial Interface DB-9 Connector
Pinouts DB-9 Connector (male)

Pin #| RS-232
(DTE Device)| RS 422 1| RS-48511
(4-wire)| RS-485
(2-wire)|
---|---|---|---|---|---
1| DCD| RX-| RX-| DATA-|
2| RXD| RX+| RX+| DATA+
3| TXD| TX+| TX+| —
4| DTR| TX-| TX-| —
5| GND| GND| GND| GND
6| DSR| —| —| —
7| RTS| | | —
8| CTS| | | —
9| RI| —| —| —

Note: Table with correct pinouts for RS-422 and RS-485 4-wire interface modes. In previous document V1.3, the assignments for RX-/RX+ and TX-/TX+ were reversed!

Device Access (Login to Web Interface)

For configuration, the Web interface can be accessed via the following factory default settings:

IP address / Netmask: 192.168.1.110 / 255.255.255.0
Username: admin
Password: Weidmueller

Connect the PC to any Ethernet port of the Converter/Gateway and set the PC’s IP address to a free one in the range 192.168.1.0 / 255.255.255.0
Start a web browser and enter the IP address of the connected device into the browser’s address line (http://192.168.1.110).
After the appearance of the prompt (login) enter the login credentials. After confirmation of your input with “OK,” the home page of the Converter/Gateway will be displayed.

Device Reset

  • Press the reset button for < 5 seconds to reboot the device (Warm Start).
  • Press the reset button for >= 5 seconds to reset the Converter/Gateway to factory-default settings.

LED Indicators

Description of front panel LED indicators:

LED Color Status Description
PWR1 Green On Power is supplied to power input PWR1.
PWR2 Green On Power is supplied to power input PWR2.
Eth1 Green On Ethernet Port 1 is connected.
Blinking Data is transmitted.
Eth2 Green On Ethernet Port 2 is connected.
Blinking Data is transmitted.
Rx Amber On Receiving serial data.
Tx Green On Transmitting serial data.

Disposal information

Observe the notes for proper disposal of the product. You can find the notes here:

https://www.weidmueller.com/disposal

Specifications

Interfaces

Ethernet Ports| 2 x RJ45 10/100BASE-T(X) auto-negotiation speed, F/H duplex mode and auto MDI/MDI-X connection
Serial Port| lx DB9 connector (male)
• Interface Settings RS-232/422/485
• Baud Rates 110 bps to 460800 bps
• Data Bits 7, 8
• Parity odd, even, none, mark, space
• Stop Bits 1, 2
• RS-232: TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
• RS-422: Rx-, Rx+, Tx+, Tx-, GND
• RS-485 4 wire: Rx-, Rx+, Tx+, Tx-, GND
• RS-485 2 wire: Data-, Data+, GND
• Flow Control XON/XOFF, RTS/CTS, DTR/DSR
LED Indicators| PWR 1 / 2 (Power supply)
Eth 1 / 2 (Ethernet Port Link / Activity)
Tx / Rx (Serial Port Data Transmit / Receive)
DIP Switch| SW1:Sets Pull-Up resistor to 1 KO (ON) or 150 0 (OFF) SW2:Sets Pull-Down res. to 1 KO (ON) or 150 KO (OFF) SW3: Enables (ON) / Disables (OFF) Line Termination
Power supply
Input Voltage| 24 V DC (12 to 48 V DC), 2 redundant inputs
Current Consumption| 0.05 A — 0.1 A
Connection| One removable 4-pin terminal block, Wiring cable 12- 24AWG
Overload Current Protection| Present
Reverse Polarity Protection| Present
Physical Characteristics
Housing| IP30 protection, metal
Dimension (W x H x D)| 26.1 x 110 x 75.2 mm (1.02 x 4.33 x 2.95 inch)
Weight| 200 g
Installation| DIN-rail, Wall
Environmental conditions
Operating Temperature| -40 to 70°C (-40 to 158°F)
Storage Temperature| -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity| 5 to 95% (non-condensing)
Altitude| up to 2000 m
Regulatory Approvals
Safety| UL 61010-1; UL 61010-2-201
EMC| EN 55032, EN 55024, FCC Part 15 Subpart B Class A, IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV,
IEC 61000-4-3 RS: 80 MHz bis 1 Ghz: 3 V/m,
IEC 61000-4-4 EFT: Power: 0.5 kV; Signal: 0.5 kV, IEC 61000-4-5 Surge: Power: 0,5 kV; Signal: 1 kV, IEC 61000-4-6 CS: 3 Vrms
Shock| IEC 60068-2-27
Free Fall| IEC 60068-2-31
Vibration| IEC 60068-2-6
MTBF
Time| 1.479.078 hrs
Database| Telcordia SR332
Warranty
Time Period| 15 years

Contact Information
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26, 32758 Detmold / Germany
Phone +49 (0) 5231 14-0, Fax +49 (0) 5231 14-292083
E-Mail weidmueller@weidmueller.com, Internet www.weidmueller.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals