Fieldpiece SC480 Job Link System Power Clamp Meter User Manual
- June 5, 2024
- Fieldpiece
Table of Contents
- Safety Information
- Description
- What’s Included
- Quick Start
- Measurements Dial
- Buttons
- Display Icons
- Easy to Read Display
- Measurement Dial
- Temperature
- Temperature Calibration
- Modular Expandability
- Works with Job Link® System
- Wireless Mode
- Wireless Specifications
- Wireless Compatibility
- Functions
- Certifications and Module IDs
- Specifications
- FCC Statement
- IC Statement
- I FEEL Statement
- Limited Warranty
- Obtaining Service
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Job Link® System Power Clamp Meter
OPERATOR’S MANUAL
Model SC480
Safety Information
Understand and follow operating instructions carefully.
A Warning identifies conditions and procedures that are dangerous to the user. A Caution identifies conditions and procedures that can cause damage to the Product or the equipment under test.
WARNING To avoid possible electric shock, personal injury, or death, follow these guidelines:
-
Use the meter only as specified in this manual; otherwise, the protection provided by the meter may be impaired.
-
Do not use it if the meter appears damaged. Visually inspect the meter to ensure the case is not cracked and the back case is securely in place.
-
Inspect and replace leads if insulation is damaged, metal is exposed, or probes are cracked. Pay particular attention to the insulation surrounding the connectors.
-
Do not use the meter if it operates abnormally as protection may be impaired.
-
Use only correct measurement category (CAT), voltage, and amperage-rated probes, test leads, and adapters for the measurement.
-
Do not use this meter to verify the presence of hazardous voltages on circuits that may have voltages generated from frequencies above 1000Hz as the low pass filter limits voltage measurements to below 1000Hz.
-
Do not use it during electrical storms or in wet weather.
-
Do not use around explosive gas, dust, or vapor.
-
Do not apply more than the rated voltage, as marked on the meter, between terminals, or between any terminal and earth ground.
-
Do not use without the battery and the back case properly installed.
-
Replace the battery as soon as the battery indicator appears to avoid false readings.
-
Remove the test leads from the circuit prior to removing the battery cover.
-
Do not attempt to repair this unit as it has no user-serviceable parts.
-
The temperature switch prevents leaving the thermocouple plugged in while measuring voltage.
-
Do not measure current while the test leads are in the input jacks.
-
When measuring high-frequency AC current, do not exceed the rated 600AAC of the clamp.
Failure to adhere may cause the clamp to heat up dangerously. -
Do not use the HOLD function to measure unknown potentials. When HOLD is turned on, the display does not change when a different potential is measured.
-
Do not use in CAT III or CAT IV environments without the protective cap of the test probe. The protective cap decreases the exposed probe metal <4mm. This decreases the possibility of arc flash from short circuits.
-
Do not place the magnet inside the Category IV panel.
Place it outside the panel instead.
CAUTION
To protect yourself, think “Safety First”:
- Voltages exceeding 30VAC or 60VDC pose a shock hazard so use caution.
- Use appropriate personal protective equipment such as safety glasses, face shields, insulating gloves, insulating boots, and/or insulating mats.
- Disconnect circuit power and discharge all high-voltage capacitors before testing resistance, continuity, diodes, or capacitance. Before each use:
- Perform a continuity test by touching the test leads together to verify the functionality of the battery and test leads.
- Use the 3 Point Safety Method. (1) Verify meter operation by measuring a known voltage. (2) Apply meter to the circuit under test. (3) Return to the known live voltage again to ensure proper operation.
- Use the proper terminals, functions, and range for your measurements.
- Never ground yourself when taking electrical measurements.
- Connect the black common lead to ground or neutral before applying the red test lead to potential voltage. Disconnect the red test lead from the voltage first.
- Always work with a partner.
- Keep fingers behind the finger guards on the probes.
All voltage tests: All voltage ranges will withstand up to 1000VDC/750VAC rms. Do not apply more than 1000VDC or 750VAC rms. Symbols used:
| Caution, risk of electric shock
---|---
Caution, refer to the manual.
Ground
Double insulation
WARNINGS
DISCONNECT AND UNPLUG TEST LEADS before opening the case.
TEST NCV FUNCTION ON KNOWN LIVE WIRE before using.
DO NOT APPLY VOLTAGE greater than 30VAC/VDC to the thermocouple or the jacks
when the rotary dial is on °F°C. (Use only Type K thermocouples)
DO NOT APPLY VOLTAGE TO THE JACKS when the rotary dial is on microamps. Even
low voltages can cause a current overload and potentially harm the meter.
Description
Your SC480 is the essential clamp meter with wireless functionality for the
HVACR professional.
Send your electrical measurements directly to the Job Link® System mobile app.
Leave the meter behind a closed blower door and view the current measurement
on your mobile device.
Help determine system efficiency by directly measuring the power consumption
(W) of the system.
Use this value to inform your customer of energy-saving measures you can take
to help them save money on their energy bills.
The SC480 is great for troubleshooting mini-split systems.
Reach those cramped mini-split connectors with the included RCT2 probe tips
for voltage and resistance measurements.
Plus, measure frequency (Hz) directly with clamp jaw. Hang your SC480 clamp
meter to any metallic surface with the heavy-duty magnet.
See both voltage and amperage readings at the same time on the big dual
display.
Verify the order of 3-phase voltage lines with just two leads. Capture L1L2
and L1L3 to check that motor lines are correctly installed with the Phase
Rotation test.
Take more accurate VAC and AAC readings on variable frequency drives with True
RMS sensing technology. Measure the starting amp draw of a compressor with
Inrush current mode.
Illuminate the way with a powerful LED built into the clamp jaw. Easily see
your measurements with the bright blue backlight on the display.
Take measurements more safely with one hand using the single test lead holder.
Test leads come with removable gold plated tips to reliably connect Fieldpiece
accessory heads.
What’s Included
- SC480 Job Link® System Clamp Meter
- ADLS2 Deluxe Test Leads Kit
- ASA2 Alligator Clips
- RCT2 Molex Probe Tips
- ATB1 Type K Thermocouple
- 1 Velcro Strap
- 9V Alkaline Battery (Not installed)
- ANC12 Protective Padded Case
- Operator’s Manual
Quick Start
- For electrical testing, connect test leads to a black “COM” and red “+” jacks.
- Rotate the dial to your desired measurement.
- Connect to test points and read the measurement.
- For temperature testing, remove test leads, slide the TEMP switch to the right and connect a Type K thermocouple.
Measurements Dial
The SC480 is loaded with the measurement parameters essential for HVACR
professionals.
Select the parameter on the dial you want to measure with the rotating
selector switch.
Buttons
Illuminate backlight.
Activate Inrush AAC capture mode.
Activate wireless to send measurements to Job Link° system mobile app. Wait 3
seconds before switching positions to save the setting.
Activate and cycle through Hold, Maximum, minimum, and real-time measurements.
(Press for 1 second to clear and exit)
Deactivate autoranging and select the range manually.
Cycle through displayed values on applicable switch positions. (Hold while
switching on to toggle high voltage warning beeper.)
Display Icons
Easy to Read Display
Easily see your measurements on the big dual display. You’ll never miss a reading no matter the lighting with the bright blue backlight to illuminate the way.
Measurement Dial
Volts AC (VAC) True RMS (50-400Hz)
Test power lines (120 to 480VAC), test 24VAC going to controls, and test
for transformer failure.
Ranges: 1000mV, 10V, 100V, 750V Resolution: 0.1mV Accuracy:
±(1.5%+ 10) 50Hz to 60Hz
±(2.0%+ 10) 60Hz to 400Hz
Unspecified at 400Hz and greater Minimum Input Voltage Range: >20 digits
Low Pass Filter: >1 kHz
Crest Factor: ≤ 3
Audio/Visual Hi-V Indicator: >30VACNDC
Input Impedance: 5M0
Overload Protection: 1000VDC or 750VAC RMS
Volts DC (VDC)
Select VDC and measure DC voltages on circuit boards on more advanced HVACR
systems and logic control boards.
Ranges: 1000mV, 10V, 100V, 1000V
Resolution: 0.1mV Accuracy: ±(0.5% + 5)
Input Impedance: 5M0
Overload Protection: 1000VDC or 750VAC rms
Non Contact Voltage (NCV)
Use NCV to check 24VAC from a thermostat or live voltage up to 600VAC.
Always test a known live source before using. A segment graph and RED LED will
display the presence of voltage. An audible beep increases from intermittent
to continuous as the intensity of field (EF) increases.
AC Voltage Detection Range: 24VAC to 600VAC (50-60Hz)
Amps AC (AAC) True RMS (50-60Hz)
Test isolated power lines Press SELECT once on VAC/AAC/Hz position. Read AAC
in the upper display and VAC on the lower display at the same time.
Ranges: 100A, 600A
Resolution: 0.01A
Crest factor: ≤ 3
Accuracy: ±(2.0% + 10)
Minimum Input Current Range: >20 digits
Overload Protection: 600AAC
Jaw Opening: 1.2in (30 mm)
Frequency (Hz) Through Clamp
Measure Hz on variable frequency drive motors. Turn the dial to VAC/AAC/ Hz
and press SELECT twice. Hz will show in the upper display and VAC on the lower
display at the same time.
Range: 10Hz to 400Hz
Resolution: 0.1Hz
Accuracy: ±(0.1% + 5)
Minimum current range: >7AAC (10 to 100Hz); >20AAC (100 to 400Hz) on
100AAC range; >25AAC (10 to 400Hz) on 600AAC range.
Overload Protection: 600AAC
Inrush AAC Current
Inrush mode captures the starting amp draw of a motor. Starting an amp draw
can assist in diagnosing a motor before it fails.
Activate Inrush mode
- Rotate selector switch to VAC/AAC/Hz.
- Press SELECT once to show AAC on the upper display. Press INRUSH on the right side of the meter to activate Inrush Mode.
- Clamp jaw around the motor’s start wire.
- Turn motor on. The starting amp draw will hold on the upper display.
- Press INRUSH to clear captured reading. Press INRUSH for 2 seconds to exit.
Inrush measurement period: 100-milliseconds
Minimum input: >2A on 100A range; >20A on 600A range
Note AAC or Hz through the clamp and VAC through the test leads can be measured simultaneously. However, if only AAC, Frequency (Hz), or Inrush AAC is measured through the clamp, test leads and thermocouples must be unplugged from the meter.
Amps AC (AAC), Frequency (Hz) through the clamp, and Inrush AAC current is measured in the VAC/AAC/Hz switch position shown above.
MicroAmps DC (µADC)
Test flame rectifier diodes on a heater control. Connect leads between the
flame sensor probe and control module. Turn the heating unit on. When the
flame is on, there should be a measurable µADC signal, typically under 10µADC.
Compare the measurement to the manufacturer’s specification to determine if
replacement is necessary.
Ranges: 1000µA
Resolution: 0.1µA
Accuracy: ±(1.0% + 5)
Volts burden: 5V
Overload Protection: 600VDC or 600VAC rms
Capacitance (MFD)
Test motor start and run capacitors. Capacitors are one of the most failure-
prone components in an HVACR system. Disconnect from power and any resistors
found between terminals. Discharge capacitor before testing.
If dIS.C is displayed, the capacitor needs to be fully discharged to test.
Press SELECT three times to enter Capacitance mode.
Ranges: 10nF, 100nF, 1000nF, 10µF, 100µF, 1000µF, 10mF
Accuracy: ±(3% + 15) 10nF, ±(3% + 5) 100nF to 1000µF, ±(5% + 5) 10mF
Resolution: 0.01nF
Overload Protection: 600VDC or 600VAC rms
Resistance (Ω)
Used for”ohming out” a compressor. A 0.010 resolution is useful to test the resistance between the terminal poles because the values are typically very low. Resistance is the default test in this switch position. For best practice, use a megger (Fieldpiece SMGS) to measure motor winding insulation to the ground.
Ranges: 100Ω, 1000Ω, 10kΩ,100kΩ, 1000kΩ, 10MΩ, 50MΩ
Resolution: 0.01Ω
Accuracy: ±(1.0% + 15) 100Ω, ±(1.0% + 5) 1000Ω to 100kΩ, ±(1.5% + 5)
1000kΩ, ±(3.0% + 5) 10MΩ to 50MΩ
Open circuit volts: -1.1VDC typical, -3.2VDC (100Ω range)
Overload Protection: 600VDC or 600VAC rms
Continuity ( )
Perfect for checking isolated fuses, use the continuity function to test whether a circuit is open (no beep, no green LED) or closed (beep and green LED). Press SELECT once to enter Continuity mode.
Range: 100Ω
Resolution: 0.010
Response time: 100ms
Audible beep: <30Ω
Visual Indicator: Green LED
Overload Protection: 600VDC or 600VAC rms
Diode Test ( )
Test diodes for proper forward and reversed-biased functions. A voltage
will display in forwarding bias and “Or in reversed-bias. Press SELECT twice
to enter Diode mode.
Test current: 0.8mA (Approx.)
Accuracy: ±(1.5% + 5)
Open circuit volts: 3.2VDC typical
Audible beep: <0.05V
Visual Indicator: Green LED
Overload Protection: 600VDC or 600VAC rms
Temperature
Plug any Type K thermocouple directly into the meter to measure temperature. The meter beeps when a thermocouple is plugged in and double beeps when unplugged. Measure outdoor dry bulb temperature for target superheat while at the condenser with the Type K thermocouple input.
The insulated cold junction is located inside the meter and allows for accurate measurements even in rapidly changing ambient temperatures (going from rooftop to freezer). No adapter is required.
By default, °F will show on the top display and °C on the bottom display.
Range: -58°F to 2372°F, (-50°C to 1300°C)
Resolution: 0.1°
Accuracy: ±(1°F)* 32°F to 120°F, ±(1°C) 0°C to 49°C
±(1%+2°F) 32°F to 932°F, ±(1%+1°C) 0°C to 500°C
±(2%+6°F) -58°F to 32°F, ±(2%+3°C) -50°C to 0°C
±(2%+6°F) 932°F to 2372°F, ±(2%+3°C) 500°C to 1300°C
Sensor type: Type K thermocouple
Overload protection: 30 VDC or 30VAC RMS
*After field calibration
Temperature Calibration
Thermocouples (T/C) are not calibrated directly. Instead, each T/C jack (T1 and T2) must be calibrated to the particular T/C that is plugged into it. Though it’s possible for calibration to hold for years, it’s best practice to calibrate regularly if only to verify accuracy. Labeling your T/C, T1 or T2, will help ensure using the same T/C for T1 and T2 ports.
Calibration is quick and easy, requiring just a known temperature to calibrate to. Ice water is probably the most accurate and readily available known temperature (32.0°F, 0.0°C) in the field.
- Rotate the dial to the °F °C position.
- Plug one thermocouple to be calibrated into the Type K input.
- Unscrew A and B and remove the battery cover.
- Stabilize a large cup of ice water. Stir the rice with the water until the temperature stays at a stable value.
- Immerse the thermocouple probe and let it stabilize. Keep stirring water to prevent thermocouples from direct contact with ice.
- Use a small screwdriver to adjust the calibration Temp Cal pot below the battery as close to 32°F(0°C) as you would like.
Note: J1-12 switch is for factory calibration purposes only. Do not switch from 12.
Power (Watts, VAr, VA, PF)
Help determine system efficiency by measuring the power exerted by the
system. The actual power consumed by the system is called Active Power and is
measured in watts (W or kW). Reactive loads, inductors, and capacitors,
dissipate zero power, but they drop voltage and draw current giving the
deceptive impression they do dissipate power. This is called Reactive Power
and is measured in Volt-Amps-Reactive (VAr). The combination of reactive and
real power is called Apparent Power and is the product of a system’s voltage
and current, without phase angle consideration. Apparent Power is measured in
Volt-Amps (VA).
Power Factor (PF) is the ratio of the power the system draws from the main power supply and the power the system actually consumes. An ideal PF is 1, meaning the system consumes all the power it draws. Due to the inductive and capacitive loads of the system, however, this is not possible.
To take the power reading you need to measure both voltage and amperage simultaneously. Connect test leads to main power supply terminals and secure amp clamp around the same line that the positive (red) test lead is connected to.
See Power Factor on the top display and Power on the bottom display. Press SELECT to toggle Active Power (W), Reactive Power (VAr), and Apparent Power (VA).
CAUTION! DO NOT MEASURE VOLTAGE LINES OR EXPOSE THE METER TO LIVE POWER LINES EXCEEDING 750VAC/1000VDC NOMINAL VOLTAGE.
Power (Watts, VAr, VA, PF)
Accuracy: Stated accuracy @ 73°F±9°F (23°C±5°C), <75%RH
Effective Current Range: 2AAC to 600AAC
Effective Voltage Range: 80VAC to 750VAC
Effective Frequency Response: 50Hz to 60Hz
Power accuracies unspecified for non-sinusoidal current waveforms
Active Power (W)
Ranges: 1000W, 10kW, 100kW, 450kW
Resolution: 0.1W
Accuracy: ±(5.0% + 5) >10A ±(10.0% + 5) 2A to 10A on 450kW range
Reactive Power (VAr)
Ranges: 1000VAr, 10kVAr, 100kVAr, 450kVAr
Resolution: 0.1VAr
Accuracy: ±(5.0% + 5) >10A on 1000VAr range ±(10.0% + 5) 2A to 10A
Apparent Power (VA)
Ranges: 1000VA, 10kVA, 100kVA, 450kVA
Resolution: 0.1VA
Accuracy: ±(5% + 5) >2A
Power Factor (PF)
Ranges: -1.00 to -0.30 and 0.30 to 1.00
Resolution: 0.01 PF
Accuracy: ±(5.0% + 5) >10A, ±(10.0% + 5) 2A to 10A PF readings will be
displayed on upper display
Phase Rotation Test (L1 L2, L1L3)
Connect 3-phase power lines in the correct order to the terminals of a motor to ensure the motor turns in the intended direction. Incorrect wiring can damage some equipment. The terminals on the motor are usually marked 11, L2, and L3; however, the wires supplying power usually are not. Perform a simple phase rotation test with two test leads to quickly identify the order of 3-phase power lines.
Range: 80±5 VAC to 600VAC (50Hz to 80Hz)
Resolution: 0.1 V
Accuracy: ±(1.5% rdg + 10 dgts)
Overload Protection: 600VDC or AC rms
How to Perform a Phase Rotation Test
Set 1: Select Function
Switch to L1L2 L1L3. Plug black test lead into the COM (L1) port and the red test leads to the VD (L2 L3) port on the SC480.
You will see”Ll L2″ blinking to indicate the phase rotation test is ready to begin.
Step 2: Connect Leads
Connect both black and red test leads to any two of the three-phase voltage lines in question. The line voltage will hold on the bottom display. Blinking Ll and U disappear. L3 will blink on the top display to indicate the test is ready for Step 2.
Important: Step 2 must be performed within 5 seconds of completing Step 1 or “Err” will show and Step 1 must be repeated.
Step 3: Move Red Lead
With the black lead still on “Ll”, move the red test lead to the third 3-phase voltage line. The line voltage will hold on the bottom display. The top display will show L123 indicating forward or L321 indicating reversed.
Simply swap any two lines to change the direction. You can verify this by performing the test again.
Phase Rotation Testing Tips
- The measured voltage during the phase rotation test must be >80.0±5VAC. If not, the phase rotation test can not be performed, and “Err” will show on the top display.
- After the phase rotation test is complete, press the SELECT button to begin a new phase rotation test.
- Be sure to connect test leads to 3-phase voltage lines for at least 2 seconds until the voltage reading holds on the bottom display
- Phase rotation test cannot be performed on Hi-frequency voltage signals. Be sure voltage lines are within 50-80Hzto perform the phase rotation test.
Modular Expandability
Your SC480 is compatible with all Fieldpiece Accessory Heads. With Fieldpiece Accessory Heads, you can measure any available parameter, and read the measurement on your new meter’s display in real-time, Hold, Max, and min.
Rotate the selector to VDC and stay in the mV range. Remove the probe tips of your test leads, and connect your accessory head (model AAV3 shown).
Visit www.fieldpiece.com to see all of the different Accessory Heads that Fieldpiece offers.
Works with Job Link® System
Do More with the Job Link® System
Directly document critical electrical measurements at the job site, and add
them to professional PDF reports. No separate transmitter is required.
Combine your new clamp meter with other Job Link System tools to create
seamless reports. Show customers what needs to be done (Pre-work) and prove
how that work helped (Post-work).
Other Job Link® System Tools
- SM480V Refrigerant Manifold + Micron Gauge (4 Port)
- SM380V Refrigerant Manifold + Micron Gauge (3 Port)
- 3KH6 Wireless Charge and Air Test Kit
- JL3KR4 Wireless Charge Test Kit
- SRS3 Wireless Refrigerant Scale
Go to www.fieldpiece.com for all Job Linke System options.
Wireless Mode
Send electrical measurements wirelessly from 5C480 directly to the Job Link° mobile app. No JL2 transmitter is required.
- Select any switch position other than L1 L2 and NCV.
- Press WIRELESS ON/OFF to toggle wireless mode. To maximize battery life, the wireless mode is OFF by default. To save the WIRELESS ON/OFF setting, allow 3 seconds before switching positions.
- Assign your meter to the Job Link app tool manager.
- Tap on the Electrical tab in the Job Link measurement screen and begin logging measurements from your clamp meter.
Wireless Specifications
Wireless range: Up to 1000 feet (305m) line of sight. Distance decreases
through obstructions.
Wireless frequency: 2.4 GHz
Wireless Compatibility
Minimum Device Requirement:
BLE 4.0 devices running iOS® 7.0 or Android™ 5.0 (Latest compatibility at www.fieldpiece.com)
Functions
Auto Power Off
Auto power off or APO will automatically turn off your meter after 30 minutes of inactivity. By default, it is activated and APO will show on the display. To disable it, turn the meter off. Hold and power the meter by turning the selector dial to any range. Release after the beep. APO will no longer display over the battery icon.
Hold/Max/min
Press to cycle through Hold, Maximum, minimum, or real-time measurements. When MAX MIN is displayed, you are seeing the real-time measurement, but Max and min values are still being recorded. Press for 1 second to clear and exit. Press to logs an SC480 measurement in Job Link mobile app. See Wireless Section for Job Link compatibility details.
High Voltage Warning
The symbol will display when measuring >30VACNDC. An audible beep will be heard and red LED will be shown. To toggle the high voltage beeper, hold SELECT when turning on. “Beep On” or “Beep Off” is shown on the display when toggled
Battery Replacement
When your meter’s battery is low, the battery icon will appear empty and blink for 30 seconds.” bAtt” will display and the meter will power off.
Turn the dial to the OFF position, disconnect test leads and remove the battery cover with the magnet strap on the back of your meter. Remove the old battery and replace it with a standard 9V battery only. Be sure to re-insert the magnet strap before re-installing the battery cover.
Backlight Illumination
See your measurements in dark environments.
Press to illuminates the display. Illumination will stay on for 5 minutes
before turning off automatically. Illumination can be turned off at any time
by pressing .
Manual Ranging
Press to disables auto-ranging and set your clamp meter to a specific range. Manual ranging applies to VAC, VDC, MFD, W, and resistance (0). Press for 1 second to exit manual ranging and return to auto-ranging.
Certifications and Module IDs
| UL 61010-1, Third Edition
---|---
EN61010-1, EN61010-2-032
EN61010-2-033, EMC EN61326-1
FCC ID: 2ALHR005
RCM (N22675)
WERE
Restrictions of Hazardous Substances Compliant
IC: Industry Canada
22518-BT005
I FEEL: Federal Telecom Institute
RCPFI2A19-0287
CATIV 600V, CATIII 1000V or above. Included test leads are gold-plated and
have removable safety caps.
CATIII 1000V, CATIV 600 class II, and pollution degree 2 indoor use comply
with CE, RoHS compliant.
CATIII is designated for measurements performed in the building installation.
CATIV is for measurements performed at the source of the low-voltage
installation.
Specifications
Display: 10000 count dual display
Backlight: 5-minute duration with auto-off, blue color
Overrange: “Or or”-Oris displayed
Measurement rate: 3.3 times per second, nominal
Zero: Automatic
Operating environment: 32°F to 122°F (0°C to 50°C) at <70%RH
Storage temperature: -4°F to 140°F (-20°C to 60°C), 0 to 80%RH (with the
battery removed)
Accuracy: Stated accuracy @ 73°F±9°F (23°C±5°C), <75%RH
Temperature coefficient: 0.1 x (specified accuracy) per °C [0°C to 19°C
(32°F to 66°F), 28°C to 50° C (82°F to 122°F)] APO (Auto Power Off):
Approx. 30 minutes
Power: Single standard 9-volt battery, NEDA 1604, JIS 006R IEC 6F22
Battery life: 100 hours typical alkaline (No wireless, no backlight)
Low battery indication: The battery icon blinks and “ban” is displayed
when the battery voltage drops below the operating level
Dimensions: 247mm(H) x 79mm(W) x 48mm(D)
Weight: Approx. 345g including battery
Altitude: Up to 6562 ft (2000m)
Overload protection: 1000VDC or 750VAC RMS unless otherwise stated
Test leads: Use UL-listed test leads that comply with UL61010-031 rated
CATIV 600V, CATIII 1000V, or above. Included test leads are gold-plated and
have removable safety caps.
Please operate the instrument following all instructions of the operator’s manual to avoid impairing the safety of the product.
FCC Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
FCC Caution:
Any changes or modifications not expressly approved by the party responsible
for compliance could void the user’s authority to operate this equipment.
This device complies with Part 15 of the FCC Rules. Operation is subject to
the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
This device and its antenna(s) must not be co-located or operating in conjunction with any other antenna or transmitter.
IMPORTANT NOTE: FCC Radiation Exposure Statement:
This equipment complies with FCC radiation exposure limits set forth for an
uncontrolled environment. This equipment should be installed and operated with
a minimum distance 20cm between the radiator & your body.
IC Statement
This device contains license-exempt transmitter(s)/receiver(s) that comply with Innovation, Science, and Economic Development Canada’s license-exempt RSS(s). Operation is subject to the following two conditions:
- This device may not cause interference.
- This device must accept any interference, including interference that may cause undesired operation of the device.
IMPORTANT NOTE: IC Radiation Exposure Statement:
This equipment complies with IC RSS-102 radiation exposure limits set forth
for an uncontrolled environment. This equipment should be installed and
operated with a minimum distance of 20cm between the radiator & your body.
I FEEL Statement
The operation of this equipment is subject to the following two conditions: (1) this device or device may not cause harmful interference, and (2) this device or device must accept any interference, including interference that may cause undesired operation.
Limited Warranty
This product is warranted against defects in material or workmanship for one
year from the date of purchase from an authorized Fieldpiece dealer.
Fieldpiece will replace or repair the defective unit, at its option, subject
to verification of the defect.
This warranty does not apply to defects resulting from abuse, neglect,
accident, unauthorized repair, alteration, or unreasonable use of the machine.
Any implied warranties arising from the sale of a Fieldpiece product,
including but not limited to implied warranties of merchantability and fitness
for a particular purpose, are limited to the above. Fieldpiece shall not be
liable for loss of use of the machine or other incidental or consequential
damages, expenses, or economic loss, or for any claim of
such damage, expenses, or economic loss.
State laws vary. The above limitations or exclusions may not apply to you.
Obtaining Service
Visit www.fieldpiece.com/rma for the latest information on how to obtain service. Warranty for products purchased outside of the U.S. should be handled through local distributors. Visit our website to find your local distributor.
SC480
© Fieldpiece Instruments, Inc 2021; v16
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>