ELITE 51.2V 100Ah Powerwall Battery Owner’s Manual

June 3, 2024
ELITE

ELITE 51.2V 100Ah Powerwall Battery

Revision history

Safety Precautions

  • It is very important and necessary to read the user manual carefully before installing or using the battery. Failure to follow any of the instructions or warnings in this document can result in electrical shock, serious injury, death, or may damage the battery and the whole system.
  • If the battery is stored for a prolonged time, it is required that they are charged every three months, and the SOC should be not less than 30%.
  • The battery needs to be recharged within 12 hours, after fully discharging.
  • Do not expose the cable outside.
  • All battery terminals must be disconnected before maintenance.
  • Do not use cleaning solvents to clean the battery.
  • Do not expose the battery to flammable or harsh chemicals or vapors.
  • Do not paint any part of the battery, including any internal or external components.
  • Do not connect the battery with PV solar wiring directly.
  • Any foreign object is prohibited to be inserted into any part of the battery.
  • Any warranty claims are excluded for direct or indirect damage due to the items above.

Note Before Installation

  • After unpacking, please check the battery and packing list first, if the battery is damaged or spare parts are missing, Please contact the dealer.
  • Before installation, be sure to cut off the grid power and make sure the battery is in the turned-off mode;
  • Wiring must be correct, do not mix-connect the positive and negative cables, and ensure no short circuit with the external device;
  • It is prohibited to connect the battery with AC power directly;
  • The embedded BMS in the battery is designed for 48VDC, please DO NOT connect the battery in series
  • It is prohibited to connect the battery with a different type of battery;
  • Please ensure the electrical parameters of battery system are compatible to the inverter;
  • Keep the battery away from fire or water

During operation

  • If the battery system needs to be moved or repaired, the power must be cut off first and the battery is completely shutdown;
  • It is prohibited to connect the battery with a different type of battery;
  • It is prohibited to put the batteries working with faulty or incompatible inverters;
  • In case of fire, only dry powder fire extinguishers can be used, liquid fire extinguishers are prohibited;
  • Please do not open, repair or disassemble the battery. We do not undertake any consequences or related responsibility due to violation of safety operation or violating of design, production and equipment safety standards

System Application Introduction

This product is a household energy storage battery pack. The system is matched with a 5kWh 51.2V 100Ah lithium iron phosphate battery pack.This product can be used in conjunction with electricity so that electricity consumption can be adjusted.This product supports a variety of application modes, such as spontaneous and self-use residual power surfing, peak clipping and valley filling, standby power supply, etc. The specific operation logic is as follows.

PV Self-use Surplus Power to Grid

Under the condition of good illumination in the daytime, the DC power from PV panel is changed into AC through an inverter to supply power for the household load. If the household load cannot run out of photovoltaic power, the remaining power will be stored in the battery.
If the battery is Full charged, photovoltaic power will be supplied to the grid. In the night or rainy days, photovoltaic cannot generate electricity. The battery supplies power to the home load through an inverter. If the battery SOC is low, the household load will take power from the grid.

Peak Shaving and Valley Filling

In some countries and regions where TOU price is implemented, if the difference between peak price and low price is large, the application mode of peak shaving and valley filling can be adopted in energy storage system. In the low electricity price period, the energy storage system is charged; in the peak period of electricity price, the energy storage system supplies power to the household load. It can avoid users using too much power grid when the electricity price is high, and save energy expenditure.

Standby Power Supply

In some extreme weather (such as tornadoes, typhoons, hail), or substation operation failure, power supply will be interrupted. If the energy storage system is installed, the user can still enjoy sufficient power guarantee under this situation.

Product Specification

No. Item Specification
1 Pack configuration 16S1P
2 Cell Model LF3.2V/100Ah
3 Charge Voltage 56V(3.5V/Cell)
4 Discharge cut-off Voltage 44.8V(2.8V/Cell)
5 Nominal Voltage 51.2V(3.2V/Cell)
6 Minimum Capacity 100Ah @ 0.5C discharge
7 Nominal Capacity 100Ah @ 0.5C discharge
8 Nominal Energy 5120Wh @ 0.5C discharge
9 Max Charge Current 100A
10 Max Cont Discharge Current 150A
11 Standard Charge Using 0.3C constant current charge to 56V, then using

constant voltage 56V charge to taper current 0.05C
12| Standard Discharge| Using 0.5C constant current discharge to 44.8V
13| Weight| About 55Kg

Product Performance

No. Item Test method Criteria
1 Capacity After standard charging, discharge the battery at 0.3C to the

capacity released by the 44.8V cut-off voltage.

| ≥100Ah
2| Cycle Life| After standard charging, discharge the battery at 0.5C to 44.8V. Repeated the above test cycle till retained capacity

is 80% of initial capacity.

| Cycles ≥2000times

Product Introduction

Interface and Key Introduction

| Definition| Specification| Criteria
---|---|---|---


1

| POWER Light| System no abnormal, always bright|
RUN Light| See Table 1, Table 3|
ALM Light| See Table 1, Table 3|
SOC Light| See Table 2, Table 3|

LED Working Status Indicators

Status| Normal/alarm

/protection

| RUN| ALM| Electricity indicator LED| Remark
---|---|---|---|---|---
●| ●| ●| ●| ●| ●| ●| ●
Power

off

| Dormancy| off| off| off| off| off| off| off| off| All off


Stand by

| Normal| Flash 1| off| ****

According to the electricity indicator

| Standby status
Alarm| Flash 1| Flash 3| Module low voltage



Charge

| Normal| Bright| off| According to the electricity indicator

(power indicator maximum LED flash 2)

| Maximum power LED flash (flash 2), overcharge alarm ALM no flash
Alarm| Bright| Flash 3
Overcharge protection| Bright| ****

off

| Bright| Bright| Bright| Bright| Bright| Bright| If there is no electricity, the indicator is in standby status
Temperature, over current, failure protection| ****

off

| ****

Bright

| ****

off

| ****

off

| ****

off

| ****

off

| ****

off

| ****

off

| ****

Stop charging




Discharge

| Normal| Flash 3| off| ****

According to the electricity indicator

|
Alarm| Flash 3| Flash 3
Under voltage protection| ****

off

| ****

off

| ****

off

| ****

off

| ****

off

| ****

off

| ****

off

| ****

off

| Stop discharging
Temperature, over current, short circuit,

reverse connection, failure protection

| ****

off

| ****

off

| ****

off

| ****

off

| ****

off

| ****

off

| ****

off

| ****

off

| ****

top discharging

Invalid| Normal| off| off| off| off| off| off| off| off| Stop charge/discharging

Description of capacity indicators

Status Charge Discharge

Capacity indicator

| L6

| L5

| L4

| L3

| L2

| L1

| L6

| L5

| L4

| L3

| L2

| L1




SOC

(%)

| 0~16.6%| off| off| off| off| off| Flash 2| off| off| off| off| off| Bright
16.6~33.2%| off| off| off| off| Flash 2| Bright| off| off| off| off| Bright| Bright
33.2~49.8%| off| off| off| Flash 2| Bright| Bright| off| off| off| Bright| Bright| Bright
49.8~66.4%| off| off| Flash 2| Bright| Bright| Bright| off| off| Bright| Bright| Bright| Bright
66.4~83%| off| Flash 2| Bright| Bright| Bright| Bright| off| Bright| Bright| Bright| Bright| Bright
83~100%| Flash 2| Bright| Bright| Bright| Bright| Bright| Bright| Bright| Bright| Bright| Bright| Bright
Operating indicator| Bright| | | Flash (flash 3)

LED Flash Notes

Flash mode Bright off
Flash 1 0.25S 3.75S
Flash 2 0.5S 0.5S
Flash 3 0.5S 1.5S

Interface Description

No. Specification Silk-screen Criteria

1

| Battery Positive| ****

P+

| ****

Anode output

2| Battery Negative| P-| Cathode output
3| Reset button| RESET| Reset battery(Press 3-6s)
4| Dial switch| ADD| Address setting, range 2~15
5| Dry connection| DRY| pin3 to pin4 often open, closed with low power alarm

Pin1 to pin2 often open, closed when failure or protection


6

| ****

RS485A terminal

| ****

RS485

| RS485 communication with monitoring equipment
7| CANbus terminal| CAN| CANbus and inverter connection ports
8| RS232 port| RS232| RS232 communication port
9| RS485A| RS485| RS485 paralleling communication port
10| RS485B| RS485| RS485 paralleling communication port

Battery Connection and Communication Instructions

  • Positive and negative output interface: Connect the positive (+) and negative electrode (-) through the DC isolator to the inverter battery positive and negative connection inlet.
  • RS485 :With a dual RS485 interface to check PACK information, with a default baud rate of 9600bps. To communicate with the monitoring equipment through the RS485, the monitoring equipment as the host, according to the address polling data, address setting range of 2~15.
  • RS232 :BMS can communicate with the upper computer through the RS232 interface, so as to monitor all kinds of information of the battery at the upper computer end, including battery voltage, current, temperature, state, SOC,SOH and battery production information, etc., the default baud rate is 9600bps.
  • CAN : With dual isolation CAN communication, default communication rate 500K, active communication portal between battery and inverter.
  • Dial switch settings:When the PACK is used in parallel, different PACK can be distinguished by setting the address on the BMS dial switch, avoid to set the same address.
  • The definition of the dial switch refers to the following table.
    Note; When the PACK is used in parallel, the bottom communication board need to be removed, then the dialing setting can be made, shown as pictures below: Address| Dial switch position
    ---|---
    | #1| #2| #3| #4
    0| OFF| OFF| OFF| OFF
    1| ON| OFF| OFF| OFF
    2| OFF| ON| OFF| OFF
    3| ON| ON| OFF| OFF
    4| OFF| OFF| ON| OFF
    5| ON| OFF| ON| OFF
    6| OFF| ON| ON| OFF
    7| ON| ON| ON| OFF
    8| OFF| OFF| OFF| ON
    9| ON| OFF| OFF| ON
    10| OFF| ON| OFF| ON
    11| ON| ON| OFF| ON
    12| OFF| OFF| ON| ON
    13| ON| OFF| ON| ON
    14| OFF| ON| ON| ON
    15| ON| ON| ON| ON

Electrical interface diagram

Electrical interface definition

RS232– adopts 6P6C vertical RJ11 socket

RJ11 pin| Defined

declaration

2| NC
3| TX(one board )
4| RX(one board )
5| GND
RS485– adopts 8 P8C vertical RJ45 socket| CAN– adopts 8P8C vertical RJ45 socket
---|---
RJ45 pin| Defined declaration| RJ45 pin| Defined declaration
1,8| RS485-B1| 9,10,11,14,16| NC
2,7| RS485-A1| 12| CANL
3,6| GND| 13| CANH
4,5| NC| 15| GND
RS485– adopts 8 P8C vertical RJ45 socket| RS485– adopts 8P8C vertical RJ45 socket
---|---
RJ45 pin| Defined declaration| RJ45 pin| Defined declaration
1,8| RS485-B| 9,16| RS485-B
2,7| RS485-A| 10,15| RS485-A
3,6| GND| 11,14| GND
4,5| NC| 12,13| NC

Battery Installation Instructions

Inventory List of Articles

Check the pack thoroughly after receiving the goods. If any items are missing or if there is any damage to the outer packaging or the unit itself in unpacking, please contact us immediately.

NO. Item Quantity Specification
A Battery pack 1 5KWh
B Mounting rack 1 SPCC
C Expansion screw 6 M6*60
D Instruction manual, warranty card 1 This document

Installation Steps

Tools for installation: drill, RJ45 clamp, screwdriver, M6 manual wrench, hammer; Space requirements: Observe the minimum clearance of the walls, detailed minimum clearance shown in the figure below to ensure adequate heat dissipation.

Direction Minimum clearance(mm)
Upper side 300
Underside 300
Side 500
Front 300
  1. Step 1 : install the wall mounted bracket to the wall
  2. Place the bracket on the wall, mark the position of the six holes and remove it to one side;
  3. Drill holes with a hole depth above 60mm to ensure sufficient strength to support the battery pack;
  4. Install the expansion screw in the hole and tighten it, then fix the wall mounted bracket with the expansion screw;
  5. Step 2: Hold the handle at the bottom of the battery, hang the battery pack on the wall mounted bracket;
  6. Step 3: Tighten the setscrews on left and right sides of the battery pack.

Battery Parallel Installation

When several batteries are going to be parallel connected, please do full discharge all the batteries and after that, parallel connect the batteries and charge them together with one charger .If you want to disconnect the battery and re-connect them again, do the same steps as above, so as to promise the deep cycle of the batteries.
When the batteries needs to be used in parallel, the maximum connection is 15 units.
The application needs power and communication connection as below, please select the appropriate attachment.

Connection step

Taking two batteries as an example, two parallel power lines are used to combine the positive and negative outputs of two batteries:
First, refer to the figure below to define the primary and slave batteries

  • Connect the positive electrode of the main battery (Pack 1) to the positive electrode of the slave battery (Pack 2);
  • Connect the negative electrode of the main battery (Pack 1) to the negative electrode of the slave battery (Pack 2);
  • Connect the positive electrode (Pack 1) of the main battery to the positive electrode of the inverter;
  • Connect the negative electrode of the main battery (Pack 1) with the negative electrode of the inverter;
  • Using RJ45 network cable to connect the parallel RS485 communication port of the main battery (Pack 1) with the parallel RS485 communication port of the slave battery (Pack 2) ;
  • Using RJ45 network cable to connect the CAN BUS communication port of the main battery (Pack 1) with the CAN BUS communication port of the inverter;
  • After the connection is complete, press the battery reset switch for 3 to 6 seconds to start the battery.Then switch the circuit breaker to the ON position, and the battery output is normal.Finally, open the inverter switch to power on the inverter, the system can work normally;

If necessary, add the appropriate isolator between the main battery pack (Pack

  1. and the inverter line.
    Note: when a single unit is used, the inverter uses the battery as the main machine to communicate; when multiple batteries are used in parallel, the batteries inside are connected in parallel through the RS485B hardware interface, RS485A/CANBUS communicates with the inverter.

PC Communication Connection

Instructions for the Use of the Upper Computer

  • A. Main Interface Connection After opening the main interface, the software will automatically search the existing serial port. If an effective serial port is found, the serial port will be automatically connected and communicated, and the battery parameters such as battery information, temperature information, single cell voltage, system state, alarm state, protection state, fault state will be read in real time. If no valid serial port is found, the prompt will pop up, and you need to manually open the serial port and start monitoring.
  • B. Interface Description

Main Control Description:

  1. Serial port: drop-down option, select the serial port to communicate.
  2. Baud rate: drop-down option, select the baud rate for communication.
  3. Address: drop-down option, the address to read corresponds to the dial code on the BMS board.
  4. Interval (s): drop-down option, interval between reading data from the BMS board. Unit: seconds
  5. Polling number: the number of addresses automatically polled by the host computer. For example, if the current address is 1 and the polling number is 3, the host computer will read the data of address 1 2 3 in turn.
  6. Open serial port: alternate function button, open or close serial port.
  7. Start monitoring: alternate function button, start or stop monitoring, monitor the time frequency of reading data, that is, moderate time interval.
  8. The data key as the address. The blue background white word indicates that the data displayed in the current interface is the data of the address.When the “polling number” is greater than 1, the host computer will alternately display the data of the polling address.
  9. Communication state: the communication state corresponding to the blue background and white word address.
  10. System state: the state in which BMS occurs. The font is blue when the state occurs, otherwise it is gray.
  11. Administrator password bar: some setup functions require an administrator password to be used, such as some function in 【System Settings】. (Note: When the password is entered correctly, the input box becomes green, and you have access to the administrator)
  12. Version: BMS software version number.
  13. S/N:bar code of the BMS board.
  14. PACK S/N:PACK SN
  15. This is the current time of the computer.
  16. Switch control: a button that controls BMS functions. When the button is red, it indicates that the function is off and when is green, it is on.

Open serial port, start monitoring

When the host computer starts, it will automatically search the available serial port. You can also manually open the string: first set the baud rate, address on the upper computer, then click button 6 to open the serial port, and then click button 7 to start monitoring.

Note: monitoring starts when the serial port is open.

Abnormal Situation Addressing
  1. What if the battery pack does not work properly after power on?

  2. A: The most direct way is to connect to the upper computer, through the upper computer to find the fault phenomenon, causes can be roughly analyzed from the upper computer interface prompt alarm, protection, fault and other information, it can also provide necessary reference for further testing.

  3. Under what circumstances will RS232 communication fail?
    A: The following steps can be taken to eliminate the problem:

  4. Confirm that at least one of the indicator lights of the battery pack is on or flashing, that is, the battery pack is in normal working condition;

  5. Confirm that the host computer software selects correct COM port (view device manager);

  6. Confirm whether the RS232 communication line is fully inserted into the corresponding communication interface of the battery pack.

  7. Under what circumstances will RS485 fail to paralleling batteries communication?

  8. A: The possibility of failure of parallel batteries communication is as follows: first ensure whether the parallel RS485 communication port has been connected, and then make sure that the address dialing position of the battery pack is correct, and make sure that the RS485 terminal Plug-in in the right place.

  9. What is the fault alarm mechanism?
    A: battery pack has fault alarm function, can be checked through upper computer software. Failure includes:

  10. Sampling failure: analog front-end and main control chip communication failure. When the fault occurs, the charge and discharge function is turned off, and the fault alarm can be automatically cleared after the fault is cleared.

  11. Temperature NTC failure: mainly detects whether the temperature NTC is short-circuited or disconnected. When the fault occurs, the charge and discharge function is turned off, and the fault alarm can be automatically cleared after the fault is cleared.

  12. Cell failure: the voltage diference of the cell exceeds 1V, or the diference between the total voltage detection voltage and the sum of single cell voltage is more than 5V, or the minimum voltage is less than 0.5V. The voltage sampling line disconnect also reports the same fault. When the fault is cleared, the fault alarm can be automatically cleared.

After the battery is connected to the system and shows over-current protection or short circuit protection. This is not a problem with the battery pack, but the capacity load of the electrical equipment is too large. Charging can remove the alarm, or extend the battery pack precharge circuit delay time.
Copyrights by Elite,All Rights Reserved.

Shenzhen Elite New Energy Co.,Ltd Tel.: +86-755 8486 2035 www.elitenewenergy.com
Email: [email protected]
Address: B1805, Rongde Times Square, Henggang, Longgang District, Shenzhen, China.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ELITE User Manuals

Related Manuals