aap HM-MINI-12V Auto Resetting Smoke Detector Instructions

June 5, 2024
AAP

aap HM-MINI-12V Auto Resetting Smoke Detector

aap-HM-MINI-12V-Auto-Resetting-Smoke-Detector-PRO

Suggested Mounting Locations

Smoke alarms must be located in escape routes on all levels within the household unit. On levels containing sleeping spaces, they must be installed within the sleeping space, or within 3 meters of every sleeping space door and they must be audible through closed doors. Always Refer to NZS 4514:2009 or the latest standard for full installation recommendations.

Operation & Testing

Pressing the Test Button will activate test mode, triggering both the Relay and the Buzzer. The HM-MINI12V smoke detector should be tested every month. The smoke detector sounder will automatically reset, when all the smoke has cleared. The alarm system sounders may need to be deactivated from the control keypad. Hush feature. When the smoke detector has been activated, pressing the test button for 1 second, will silence that smoke detectors sounder. This will not hush the controllers, sounders or other smoke detectors connected.aap-
HM-MINI-12V-Auto-Resetting-Smoke-Detector-FIG-2

Specifications

  • Detection Type Photoelectric Chamber
  • Power Source 9-16 Volts DC
  • Standby Current 5mA
  • Alarm Current 25mA
  • Buzzer Output 85db @ 3 meters
  • Output Relay N/O and N/C Contacts
  • 50mA max (2K2 EOL fitted)
  • Dimensions 51mm x Ø45mm (smoke) Ø64mm (base)
  • Standards: GB4715-2005, EN14604, UL217

Connection Diagram

Panel Programming (ESL, ESX, Elite S & S-Lite only)
You will need to tell the panel what zone the smoke detector is connected to. In Program mode press <123> then put in the zone (1-8) that the smoke is on <1-8> now turn On option <5> . With this feature turned On, when the smoke detector is triggered the Alarm will activate even if the system is disarmed. Also the sirens will pulse On and Off making a different sound to a normal burglar alarm. The user will have to clear the alarm with their normal alarm code. i.e. P 123 E 8 E 5 E (zone 8 is now a 24 Hour Fire zone)

Built-in 2K2 EOL
The HM-MINI-12V has a built-in 2K2 EOL resistor Which allows you to easily wire one detector, directly to a Zone Input on an Elite series control panel. (see diagram A) If you are using a different control panel or wish to wire multiple HM-MINI-12V’s to the same zone (see diagram B, C & D) you will need to remove the 2K2 EOL Jumper.

Multiple Detectors in Parallel Connection (using N/O Contacts)

Multiple Detectors in Series Connection (using N/C Contacts) Daisy-chain wiring

Multiple Detectors in Series Connection (using N/C Contacts) Individual wiring