RTC FSC-1 Digital EC Motor Control User Manual
- June 5, 2024
- RTC
Table of Contents
RTC FSC-1 Digital EC Motor Control
Overview
The FSC-1 is a digital EC motor control. The control has a simple five button
interface with a four digit LED display. All programmable parameters can be
accessed through the user menu with the five button interface. There are two
ECM connectors with modulating outputs, one 0-10V output, and one 0-10V DC
input (MUST BE ISOLATED). The FSC-1 is compatible with Telco Green, Genteq,
Nidec, and U.S. motors. User parameters are stored in non-volatile memory, and
are retained even during a power outage. The FSC-1 is powered by 24V AC.
Genteq: Genteq motors use our 0-10V output(Terminal labeled “rpm”) as the
signal going to the motor. In this case, the motor selection(tyP) in the
software does not matter.
Normal Operation
Pulse Application
Every ten seconds the FSC-1 display will toggle between the current percent of
run speed and the current RPMs. The percent of run speed can be changed by
using the and keys followed by the save your changes. You also have the option
of using the control locally or remotely through a 10k potentiometer, 2 Speed
Switch, or a 0-10V reference where 0V is 0% and 10V is 100%, unless overridden
by the low speed and high speed limits. You can access programming mode by
holding the enter key for three seconds. 0-10 Application In the 0-10V
application you are provided a programmable 0-10V reference. The display shows
the selected voltage. The voltage is easily changed using the keys followed by
the key to save your changes.
Programming
Please refer to the “FSC-1 Menu Map” on page 3 for editing parameters within
program mode. To enter program mode hold the key for three seconds until
“APPS” is displayed. Use the and keys to navigate to the desired menu
parameter shown in column 1 of the menu map on page 3. To edit a menu key once
on the desired parameter. The current value will be displayed in column 2 of
the menu map on page 3. Also use the parameter will blink until the user
presses and keys to change values within a parameter. The to save the changes
or the key to cancel without saving.
If a key is not pressed for fifteen seconds, the control will return to normal
operating mode. Different parameters are as follows:
- “APPS”: Prompts the user to select which application to utilize.
- “SP1”: Sets the speed of the motor for Setpoint 1.
- “SP2”: Sets the speed of the motor for Setpoint 2.
- “LSPD”: Sets the lowest possible speed the motor will operate at. If the time passed the “LSPD” limit, the control will turn off.
- “hSPD”: Sets the highest possible speed the motor can operate at.
- “tyP”: Sets the type of motor the control is configured for. The FSC-1 is compatible with Telco Green, Genteq, Nidec and US motors.
- “re”: Selects local control or remote control type (10k Potentiometer, 2 Speed Switch or 0-10V Reference). When the 0-10V Reference(MUST BE ISOLATED) is utilized with Low Speed and High Speed limits, the FSC-1 will cap the percentage to what the limits are set to. So if Low Speed is set to 30%, anything up to 3 Volts will output 30%. If High Speed is set to 70%, 7 Volts and above will output 70%.
- “ver”: Allows the user to view the current software version number.
Alarms
Error messages on the FSC-1 will scroll across the display with a detailed message. This will help users to resolve issues faster. Possible errors are as follows:
- “oFF”- The FSC-1 is not receiving RPM feedback.To resolve an issue, refer to “Installation” on page 4 for proper wiring connections.
ARROW KEYS
- Up and Down: to navigate or adjust a menu parameter
- Right: to access column 2 for editing a parameter
- Left: to return to column 1 without saving a parameter
- Enter: to return to column 1 while saving a parameter
Installation
FRONT PANEL
SIDE VIEW
NIDEC/US MOTORS PERFECT SPEED
NIDEC/US MOTORS PERFECT SPEED 120
GENTEQ 142R
CONTACT US
Ph. 877-351-4702
Fax 919-845-8102
RTC-Solutions.com
Email: info@RTC-Solutions.com
4370 Oakes Road, Suite 700 Davie, Fl 33314
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>