Senseair eSENSE II Carbon Dioxide Transmitter Instruction Manual

June 5, 2024
Senseair

Senseair eSENSE II Carbon Dioxide Transmitter Instruction Manual

Installation Manual

eSENSE II (Disp)
CO2 sensor in a housing for mounting in ventilation ducts

General

The IAQ-sensor product eSENSE II (sensor for wall mounting) is designed to measure carbon dioxide (CO2) in rooms. Option – Disp displays the measured CO2 value in ppm (parts-per-million) on the LCD.
The units are designed for connecting to Direct Digital Control (DOC). The two parallel signal outputs OUT1 (0-10 V) and OUT2 (2-10 V or 4-20 mA) give linear signals corresponding to the measuring range.
The OUT2 output also indicates the status by setting the output voltage to 1 V or current to 2 mA when the sensor self-diagnostics detects any error.
Sensea,r An Asahi

To open the wall mounted housing

Figure 1 . Closed housing seen from the top and the side. The housing is opened by inserting a screw driver and pushing to the front side of the housing. The locking hooks will then be released.

Figure 2. Closed housing seen from the side.
The housing is opened by inserting a screw driver and pushing left (to the front side).
The locking hooks will then be released.

Figure 3. Closed housing seen from the side.
Never push to the right. The locking hooks may  and the housing is damaged

Dimensions

Electrical connections

The power supply has to be connected to and –=- . –=- Is considered as system ground. The same ground reference has to be used for the eSENSE unit and for the DOC/signal receiver.
The same ground reference has to be used for the eSENSE unit and for the control system!


Table I. Connections of the main terminal of eSENSE

Figure 4. The eSENSE II PCB seen from the front and the back. The OUT2 jumper is in the default position (voltage)

Configuration

jumper for OUT2 output The output OUT2 can be used as a voltage or current output. The output is configured by the jumper on top of the PCB. The configuration of the output can be changed by moving the jumper to the desired position. The output has to be reconfigured before the unit is powered up.

Self-diagnostics

The system contains complete self-diagnostic procedures that are executed automatically when the sensor is in operation. Sensors with display show a wrench it an error is fund. The wrench is shown during the first seconds after power up and if the measuring range 2000 ppm is exceeded. The output OUT2 indicates the same information by setting the output to 1 V or 2 mA.
NOTE: The sensor accuracy is defined at contiruous operation (at least 3 ABC periods after installation)

Read More About This Manual & Download PDF: