Senseair K45 aSENSE Duct Co2 Temperature Sensor Instruction Manual

June 12, 2024
Senseair

Installation Manual
aSENSE Duct

K45 aSENSE Duct Co2 Temperature Sensor

CO2 / temperature sensor for mounting in ventilation ducts

Senseair K45 aSENSE Duct Co2 Temperature Sensor -

  1. Sampling probe

  2. Sealing gasket

  3. Largest locking nob

  4. 2 washers (Not included)

  5. 2screws (Nonincluded)

  6. O-ring 29,2×3,53 (Factory supplied mounted in box)

  7. PCB (Factory supplied mounted in box)

  8. Snap-in lid

  9. PG9 cable entry bushing

  10. Temperature sensor (to be put into the sampling tube)
    Mounting of aSENSE on to the duct.Senseair K45 aSENSE Duct Co2
Temperature Sensor - Fig1

  11. Hole with 25 mm diameter

  12. Temperature sensor with 110 mm cable mounted in the sampling probe

Mounting Instruction

Since there might be a substantial pressure difference in duct mounting applications, it is essential to avoid ambient air from suction into the duct mounting box. For correct function it is indispensable that the sealing of the box cover, the cable entry bushings, the cable feed through and the duct entrance are absolutely tight. The duct entrance may need extra sealing paste in order to prevent leakage. The PCB must be handed carefully and protected from electrostatic discharge.

  1. Electrical cable entry: The box has a factory mounted cable entry bushing in dimension PG9. Never feed more than one cable through each cable entry bushing, or else gas might leak through!
  2. Mounting the tube: Drill a hole (10) with 25 mm diameter (or 1 inch) for the sampling probe and two holes with 4 mm diameter for the screws (5) into the air duct and mount the tube (1) with the gasket (2). The sampling probe should be mounted with the largest locking knob on top. The unit can be mounted with the air coming from the left or right.
  3. Attaching the sensor box is made to the sampling probe by a snap-in bayonet fitting. First, carefully stick the temperature probe (11) into the sampling probe. (1). Orient the box onto the sampling probe so that the box upside is on the same side as the largest  locking knob (3). When the probe is fitted into the notches of the box, then turn the box clockwise until stop (see Figure 1). Position 1 indicates open where the box can be removed from the sampling probe. In position 2 the box is locked to the probe.

If, for some reason, the PCB must be removed, care must be taken to protect from electrostatic discharge! Normally, removing the PCB is NOT required.

Electrical connections

The power supply has to be connected to and is considered as system ground.
If the analogue output is connected to a controller the same ground reference has to be used for the aSENSE ‘Duct unit and for the control system! Unless different transformers are used, special precautions need to be taken.
The aSENSE Duct signal and power supply grounds are common.
The same ground reference has to be used for the aSENSE Duct unit and for the control system!
Connect the power after mounting. The analogue output should be connected before measuring.

Connection Terminal Function Electrical Data Remarks
Power (+)
Power ground (-) 24 V AC/DC+ (+-20%), 1W
24 V AC/DC- See note 1.

Out(1) CO2
Out(2) Temp| Analogue Output 1 (+) Standard 0 — 2000 ppm Analogue Output 2 (+) Standard 0 – 50 °C or 32 – 122 °F| 0 – 10 VDC or 0 – 20 mA,
2 – 10 VDC or 4 – 20 mA or According to label
Same as Output 1| According to positions of Out(1) and start point jumpers. See note 2.
According to positions of Out(2) and start point jumpers. See note 2.

Note 1: The ground terminal is used as negative power supply DG input or AC phase ground (halfwave rectifier). A single transformer may be used for the entire system.
Note 2: aSENSE Duct can deliver a voltage or a current loop for Out(1) / Out(2). To change between voltage and current output mode the hardware jumpers are used. There is one jumper for Out(1) and one for Out(2), so that one output can be a voltage output
and the other a current output. Both, voltage output and current outputs, can have start points 0% (0 – 10 V DC or 0 — 20 mA) or 20% (2 – 10 V DC or 4 – 20 mA). The same start point is used for both outputs. See the user manual.

Senseair K45 aSENSE Duct Co2 Temperature Sensor -
DimensionsTerminals and jumpers on aSENSE. The darker positions are default settings.

Dimensions

Senseair K45 aSENSE Duct Co2 Temperature Sensor -
Dimensions1

Dimensions of sensor in mm and (inches)

Document: Rev
IMAD196: 8
©2022 Senseair AB. All rights reserved.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals