Vent-Axia 444367 Through The Wall Heat Recovery Fan Installation Guide
- August 22, 2024
- Vent-Axia
Table of Contents
Vent-Axia 444367 Through The Wall Heat Recovery Fan
IMPORTANT INFORMATION
PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS.
**Installation and Wiring Instructions for the Tempra SELV Range of Heat
Recovery Fans.**
IMPORTANT:
READ THESE INSTRUCTIONS
BEFORE COMMENCING THE INSTALLATION
DO NOT install this product in areas where the following may be present or occur:
- Excessive oil or a grease laden atmosphere.
- Corrosive or flammable gases, liquids or vapours.
- Ambient temperatures higher than 40°C or less than – 5°C.
- Possible obstructions which would hinder the access or removal of the Fan.
SAFETY AND GUIDANCE NOTES
-
A. All wiring to be in accordance with the current I.E.E. Regulations, or the appropriate standards of your country and MUST be installed by a suitably qualified person.
-
B. The Fan should be provided with a local isolator switch capable of disconnecting all poles, having a contact separation of at least 3mm.
-
C. Ensure that the mains supply (Voltage, Frequency, and Phase) complies with the rating label.
-
D. The electrical supply to this fan is 24V DC SELV from the transformer/controller. This means the fan may be installed within reach of a person using a fixed bath or shower, i.e. in a nearby wall.
However, the fan must not be placed where it could be submerged in water or regularly exposed to direct water spray, e.g. from a shower head whether permanently fixed or movable. -
E. Only connect the products from the Lo-Carbon Tempra SELV range since the fans are specially designed to work on 24V DC and are not compatible with other Vent-Axia controllers. Do not connect more than one fan to the controller.
-
F. The controller must not be installed in a shower cubicle or enclosure. It must be away from direct sources of water spray and out of reach of a person using a fixed bath or shower. Site away from direct sources of heat.
-
G. The controller needs free air circulation and must not be covered with any insulating material such as might be in a ceiling or roof void.
-
H. The Fan should only be used in conjunction with the appropriate Vent-Axia products.
-
I. The fan should only be used in conjunction with fixed wiring.
-
J. Exhaust fans may adversely affect the safe operation of appliances burning gas or other fuels
(including those in other rooms) due to back flow of combustion gases. These gases can potentially result in carbon monoxide poisoning. After installation of an exhaust fan such as a partition fan or a duct fan the operation of flued gas appliances should be tested by a competent person to ensure
that back flow of combustion gases does not occur. -
K. The Fan should not be used where it is liable to be subject to direct water spray for prolonged periods of time.
-
L. The horizontal duct should be arranged to slope slightly downwards away from the Fan.
-
M. This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory and mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning the use of the appliance in a safe way and understand the hazards involved.
-
N. Children shall not play with the appliance.
-
O. Cleaning and user maintenance shall not be made by children without supervision
Disposal
This product should not be disposed of with household waste.
Please recycle where facilities exist.
Check with your local authority for recycling advice.
DESCRIPTION
Through the wall Mounted Heat Recovery Fan
The Vent-Axia Lo-Carbon Tempra SELV is suitable for refurbishment or new
build, kitchen, bathroom, toilet or utility applications. The unit meets the
performance requirements for intermittent extract fans under the Building
Regulations Part F 2010 (table 5.1a) and also for continuous running products
Tempra SELV is available in 6 models.
444368 – Tempra SELV P| Constant trickle speed with pull cord or switch live
to boost airflow.
---|---
403833 – Tempra SELV LP
444369 – Tempra SELV T| Constant trickle speed with switch live to boost
airflow with adjustable 5-50 min overrun timer and optional 3-minute delay on
timer
403835 – Tempra SELV LT
444370 – Tempra SELV HTP| Constant trickle speed with pull cord or switch live
to boost airflow with adjustable 5-50 min overrun timer and optional 3-minute
delay on timer or internal humidistat adjustable 60- 90% RH.
403837 – Tempra SELV LHTP
SELV Controller
The controller can be installed surface or recess mounted using a Vent Axia back box 410020 (not supplied) or any standard single gang mounting box with a minimum depth of 25mm.
A. INSTALLATION
WALL MOUNTING
Models P,T & HTP are designed for use in a wall with a maximum thickness of
318mm fitted with a 110mm Soil pipe or Wall Sleeve (Stock Ref No 445529).
Models LP,LT & LHTP are designed for use in a wall with a maximum thickness of
460mm fitted with a 110mm Soil pipe.
-
Using the template provided mark the 4 wall fixing positions, the hole for the wall pipe and mains cable entry point.
-
Cut a hole through the wall and insert the soil pipe or wall sleeve.
Slope the sleeve slightly downwards away from the fan and cement both ends into position flush with the wall Fig 1. -
Undo 2 fixing screws and lift off Cover Plate Fig 2 & 3.
-
Remove 2 screws and detach Electrical Cover fig 4.
-
Lift where indicated to engage hinges Fig 5 and open Door Fig 6.
-
Feed flexible LV cable from PSU through one of the rear entry points or the side entry point as required. And then the door Fig 7 & 8.
-
Fit Chassis to wall with 4 fixing screws carefully aligning the hole in the back of the Tempra with the Wall Pipe Fig 9.
-
Remove screws and Heat Exchanger Retaining Clamp kit Fig 10. (Discard polybag)
-
Insert Heat Exchanger through Chassis and into Wall pipe Fig 11.
Note: Line up key on top of Heat Exchanger with slot in Chassis. -
Fit Heat Exchanger Retaining Clamp with the screws provided Fig 12.
-
Close Door and connect 24V Supply as described in section B – Wiring, Adjust any settings as required see section C – Setup. Fig 13
-
Re fit Electrical Cover with 2 screws indicated In Fig 14.
-
Re fit Cover Plate and tighten 2 screws Fig 15 &16. Ensure Pull cord is engaged in Lower Slot.
-
The Tempra unit is also fitted with a “manual summer setting” which allows the unit to be set to extract only, helping to prevent a dwelling becoming too warm in hot summer conditions. When first installed this shutter/vent should be open. Fig.16 To activate the summer setting it should be shut.
-
Make good on outside wall with the wall Cover bezel provided, ensure the arrow on the bezel is at the top. Fix/seal to the wall with a suitable sealant.
Important:- Please ensure that you apply sufficient sealant to hold the
bezel to the wall. (If the wall surface is not suitable for using sealant 2
screws can be located through the 2 bosses provided).
Note:- Do not seal the bezel to the heat exchanger, this needs to be
removed for cleaning at regular intervals.
**B. WIRING
**
WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM
THE POWER SUPPLY DURING THE INSTALLATION / OR MAINTENANCE.
IMPORTANT
- The fan should only be used in conjunction with fixed wiring.
- The cross – sectional area of supply cord used should range from 1 -1.5mm2.
- Cable entry can only be made from the rear of the fan.
- Allow sufficient 24V flexible cable when connecting fan, to ensure hinged door opens freely.
- The Controller is suitable for connection to 220-240V 50Hz supply and 24V SELV to the fan.
- The fan is a class ll double insulated product and MUST NOT be earthed.
- Select and follow the appropriate wiring diagram. (Fig. 18 or 19)
- Check all connections have been made correctly and ensure all terminal connections and cable clamps are securely fastened.
Fig 18
Continuous trickle (6l/s or 9l/s) with pullcord boost facility SELV P,LP and SELV HTP, LHTP
Fig 19
Continuous trickle (6l/s or 9l/s) with switch live boost facility
C. SETUP
WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY DURING THE INSTALLATION / OR MAINTENANCE.
TRICKLE SPEED SELECTION (6l/s or 9l/s) – (Fig. 20)
In Trickle running mode the fan can extract at either 6l/s (22m3/h) or 9l/s
(32m3/h) flow rate. The fan will boost to 15l/s (54m3/h) when the LS /
Humidity / Pull cord connection is switched.
- Factory set at 6l/s (22m3/h).
- Remove jumper connector (JP2) if 9l/s (32m3/h) extract flow rate is required.
PULLCORD OPERATION (P,LP AND HTP,LHTP MODELS)
THE PULLCORD ACTIVATES THE BOOST TO ON OR OFF.
TIMER ADJUSTMENT (T,LT AND HTP,LHTP MODELS) (FIG. 20)
THE TIMER IS ONLY ACTIVATED VIA THE LS CONNECTION.
- The controller is factory set at 15 minutes approx. The overrun time period can be adjusted from 5-50 minutes by altering the adjuster on the control PCB.
- To INCREASE the operating time, use a small screwdriver to turn the TIMER adjuster CLOCKWISE.
- To REDUCE the operating time, use a small screwdriver to turn the TIMER adjuster ANTI CLOCKWISE.
- In addition a 3 minute delay on timer is included this can be de-activated by removing (JP3).
HUMIDITY SET-POINT ADJUSTMENT SVHTP MODEL (FIG. 20)
NOTE:- ON INSTALLATION IT IS POSSIBLE THAT THE HUMIDITY CONTROLLER WILL RUN CONTINUOUSLY UNTIL IT HAS ACCLIMATIZED TO THE ENVIRONMENT.
- The controller is factory set to switch on at about 70% RH. The humidity set point can be adjusted from 60-90%RH by altering the adjuster on the control PCB.
- To LOWER the set-point use a small screwdriver to turn the HUMIDITY adjuster ANTI-CLOCKWISE. This makes the controller MORE sensitive.
- To RAISE the set-point use a small screwdriver to turn the HUMIDITY adjuster CLOCKWISE. This makes the controller LESS sensitive.
D. MAINTENANCE.
WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY DURING MAINTENANCE.
The fan should be cleaned to ensure there is no build up of dirt or other deposits.
-
Remove 2 screws and lift off Cover Plate assembly Fig 21 & 22.
-
Lift where indicated to engage hinges Fig 23 and open Door Fig 24.
-
Remove Retaining Plate, Carefully slide out the Heat Exchanger Fig 25 & 26 and wash in warm water using a mild detergent, dry thoroughly and re assemble in reverse order to above.
E. Spares
The following spares may be ordered from Vent-Axia
Part Description
Item | Part No | Description | Models used |
---|---|---|---|
1. | 445885 | Heat exchanger (Short) | P,T & HTP |
2. | 445886 | Motor chassis assembly | P,LP,T,LT,HTP & LHTP |
3. | 445892 | SELV Cover assembly | P,LP,T,LT,HTP & LHTP |
4. | 495742 | SELV power supply unit | P,LP,T,LT,HTP & LHTP |
5. | 445889 | Pullcord PCB | P & LP (only) |
6. | 445890 | Timer PCB | T & LT (only) |
7. | 445891 | HTP PCB | HTP & LHTP (only) |
8. | 455630 | Pullcord Assembly | P,LP,HTP & LHTP |
9. | 447838 | Wall cover bezel | P,LP,T,LT,HTP & LHTP |
10. 403878 | Heat exchanger (Long) | LP,LT & LHTP |
PRODUCT FICHE
For Residential Ventilation Units (Complying Commission Delegated Regulation (EU) No 1254/2014)
Name:| Vent-Axia| Vent-Axia| Vent-Axia| Vent-Axia|
Vent-Axia| Vent-Axia
---|---|---|---|---|---|---
Model ID (Stock Ref.) :| Lo-Carbon Tempra SELVP – 444368| Lo-Carbon Tempra
SELV LP – 403833| Lo-Carbon Tempra SELV T – 444369| Lo-Carbon Tempra SELV LT –
403835| Lo-Carbon Tempra SELV HTP – 444370| Lo-Carbon Tempra SELV LHTP –
403837
SEC Class| E| E| E| E| B| B
SEC Value (‘Average’)| 41.30| 41.30| 41.68| 41.68| 43.99| 43.99
SEC Value (‘Warm’)| 18.67| 18.67| 18.85| 18.85| 19.89| 19.89
SEC Value (‘Cold’)| 80.79| 80.79| 81.54| 81.54| 86.06| 86.06
Label Required? (Yes/No=Out of scope)| No| No| No| No| No| No
Declared as: RVU or NRVU/UVU or BVU| RVU-BVU| RVU-BVU| RVU-BVU| RVU-BVU| RVU-
BVU| RVU-BVU
Speed Drive| Multi-Speed| Multi-Speed| Multi-Speed| Multi-Speed| Multi-Speed|
Multi-Speed
Type HRS (Recuperative, Regenerative, None)| Recuperative| Recuperative|
Recuperative| Recuperative| Recuperative| Recuperative
Thermal Eff: [ (%), NA(if none)]| 78| 78| 78| 78| 78| 78
Max. Flow Rate (m3/h)| 54.00| 54.00| 54.00| 54.00| 54.00| 54.00
Max. Power Input (W): (@Max.Flow Rate)| 26.60| 26.60| 26.60| 26.60| 26.60|
26.60
LWA: Sound Power Level (dB)| 53.52| 53.52| 53.52| 53.52| 53.52| 53.52
Ref. Flow Rate (m3/s)| 0.01| 0.01| 0.01| 0.01| 0.01| 0.01
Ref. Pressure Diff. (Pa)| N/A| N/A| N/A| N/A| N/A| N/A
SPI [W/(m3/h)]| 0.70| 0.70| 0.70| 0.70| 0.70| 0.70
Control Factor & Control Typology: (CTRL/ Typology)| | | | | |
Control Factor; CTRL| 1.00| 1.00| 0.95| 0.95| 0.65| 0.65
Control Typology| Manual Control| Manual Control| Clock Control| Clock
Control| Local Demand Control| Local Demand Control
Declared: -Max Internal & External Leakage Rates(%) for BVUs or carry over
(for regenerative heat exchangers only), -&Ext. Leakage Rates (%) for Ducted
UVUs;| N/A| N/A| N/A| N/A| N/A| N/A
Mixing Rate of Non-Ducted BVUs not intended to be equipped with one duct
connection on either supply or extract air side;| N/A| N/A| N/A| N/A| N/A| N/A
Position and description of visual filter warning for RVUs intended for use
with filters, including text pointing out the importance of regular filter
changes for performance and energy efficiency of the unit| N/A| N/A| N/A| N/A|
N/A| N/A
For UVUs (Instructions Install Regulated Supply/Extract Grilles Façade)| In
F&W| In F&W| In F&W| In F&W| In F&W| In F&W
Internet Address (for Disassembly Instructions)| www.vent-
axia.com| www.vent-axia.com| www.vent-axia.com| www.vent-
axia.com| www.vent-axia.com| www.vent-axia.com
Sensitivity p. Variation@+20/-20 Pa: (for Non-Ducted Vus)| N/A| N/A| N/A| N/A|
N/A| N/A
Air Tightness-ID/OD-(m3/h) (for Non-Ducted Vus)| N/A| N/A| N/A| N/A| N/A| N/A
Annual Electricity Consumption: AEC (kWh/a)| 10.15| 10.15| 9.43| 9.43| 5.53|
5.53
Annual Heating Saved: AHS (kWh/a)| | | | | |
AHS: Average| 41.30| 41.30| 41.68| 41.68| 43.99| 43.99
AHS: Warm| 18.67| 18.67| 18.85| 18.85| 19.89| 19.89
AHS: Cold| 80.79| 80.79| 81.54| 81.54| 86.06| 86.06
The Guarantee
Applicable only to products installed and used in the United Kingdom. For
details of guarantee outside the United Kingdom
contact your local supplier.
Vent-Axia guarantees its products for two years from date of purchase against
faulty material or workmanship. In the event of
any part being found to be defective, the product will be repaired, or at the
Company’s option replaced, without charge, provided that the product:-
- Has been installed and used in accordance with the instructions given with each unit.
- Has not been connected to an unsuitable electricity supply. (The correct electricity supply voltage is shown on the product rating label attached to the unit).
- Has not been subjected to misuse, neglect or damage.
- Has not been modified or repaired by any person not authorised by the company.
IF CLAIMING UNDER TERMS OF GUARANTEE
Please return the complete product, carriage paid to your original supplier or
nearest Vent-Axia Centre, by post or personal visit.
Please ensure that it is adequately packed and accompanied by a letter clearly
marked “Guarantee Claim” stating the nature of
the fault and providing evidence of date and source of purchase.
The guarantee is offered to you as an extra benefit, and does not affect your
legal rights
Head Office: Fleming Way, Crawley, West Sussex, RH10 9YX.
EU Authorised Representative: Vent-Axia, Sigarenmaker 5 – 5521DJ, Eersel,
Nederland, authorisedrep@vent-axia.nl
UK NATIONAL CALL CENTRE,
Newton Road, Crawley, West Sussex, RH10 9JA
SALES ENQUIRIES: Tel: 0344 8560590
Fax: 01293 565169
TECHNICAL SUPPORT: Tel: 0344 8560594 Fax: 01293 539209
Web:-www.vent-axia.com
Email:- info@vent-axia.com
As part of the policy of continuous product improvement Vent-Axia reserves the
right to alter specifications without notice.