KLHA KD67B10 Network Type Large Screen LCD Wall Mounted Temperature User Manual
- June 5, 2024
- KLHA
Table of Contents
KLHA KD67B10 Network Type Large Screen LCD Wall Mounted Temperature
Technical Parameters
Technical parameter | Parameter value |
---|---|
Brand | KLHA |
Temperature measuring range | -30℃~80℃ |
Temperature measuring accuracy | ±0.5℃ @25℃ |
Humidity measuring range | 0~100%RH |
Humidity accuracy | ±3%RH @25℃ |
Communication Interface | RS485 |
Default baud rate | 9600 8 n 1 |
Power | DC9~24V 1A |
Display | LCD |
Running temperature | -40~80°C |
Working humidity | 5%RH~90%RH |
Product Size
How to wiring?
RS485 Wiring
V+
|
PWR+
V
|
PWR-
A+
| RS485 A+
B-|
RS485 B+
×Note: When wiring, connect the positive and negative poles of the power supply first, and then connect the signal wire.
Application solution
How to use?
Click “SET” to enter the baud rate and change the address setting:
Fl and F2 change the baud rate and the def a ult is 9600, 9.6 means 9600
There are five baud rates that can be set:
2400, 4800, 9600, 19200, 38400
F3 and F4 change address
Press “SET” a second time to enter the temperature upper and lower limit
adjustment:
Fl and F2 change the upper temperature limit
F3 and F4 change the lower temperature limit
Press the third “SET” to enter the upper and lower lim its of humidity
adjustment:
Fl and F2 change the upper limit of humidity
F3 and F4 change the lower limit of humidity
Press “SET” the fourth time to save the settings
Communication Protocol
The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device leaves the factory, and the default baud rate is 9600,8,n,1 .
Read data (function code 0x03)
Inquiry frame (hexadecimal), sending example: query 1 data of 1# device, the upper computer sends the command: 01 03 00 00 00 02 C4 0B .
Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
01 | 03 | 00 00 | 00 02 | C4 0B |
For the correct query frame, the device will respond with data: 01 03 04 00 7A 00 00 DB EA , response format:
Address | Function Code | Length | Data 1 | Data 2 | Check Code |
---|---|---|---|---|---|
01 | 03 | 04 | 00 79 | 00 7A | DB EA |
Data description: The data in the command is hexadecimal, take data 1 as an example, 00 79 is converted to decimal value as 121, assuming the data magnification is 100, then the real value is 121/100=1.21, Others and so on.
Common data address table
Configuration Address| Register Address| Register Description| Data Type|
Value Range
---|---|---|---|---
40001| 00 00| temperature| Read Only| 0~65535
40002| 00 01| humidity| Read Only| 0~65535
40101| 00 64| Model Code| Read/Write| 0~65535
40102| 00 65| total number of measuring points| read/write| 1~20
40103| 00 66| device address| read/write| 1~249
40104| 00 67| baud rate| read/write| 0~6
40105| 00 68| communication mode| read/write| 1~4
40106| 00 69| protocol type| read/write| 1~10
Read and modify device address
(1) Read or query device address
If you don’t know the current device address and there is only one device on
the bus, you can query the device address through the commandFA 03 00 66 00 01
71 9E .
Device Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
FA | 03 | 00 66 | 00 01 | 71 9E |
FA means 250 is the general address, when you don’t know the address, you can
use 250 to get the real device address, 00 66 is the device address register.
For the correct query command, the device will respond, for example, the
response data is: 0 1 03 02 00 01 79 84, and its format parsing is shown in
the following table:
Device Address | Function Code | Start Address | Model Code | Check Code |
---|---|---|---|---|
01 | 03 | 02 | 00 01 | 79 84 |
In the response data, the first byte 01 represents the real address of the current device.
(2) Change device address
For example, if the current device address is 1 and we want to change it to
02, the command is: 01 06 00 66 00 02 E8 14 .
Device Address | Function Code | Register Address | Target Address | Check Code |
---|---|---|---|---|
01 | 06 | 00 66 | 00 02 | E8 14 |
After the change is successful, the device will return the information: 02 06 00 66 00 02 E8 27 , and its format analysis is shown in the following table:
Device Address | Function Code | Register Address | Target Address | Check Code |
---|---|---|---|---|
02 | 06 | 00 66 | 00 02 | E8 27 |
In the response data, after the modification is successful, the first byte is
the new device address.
Generally, after the device address is changed, it will take effect
immediately. At this time, the user needs to change the query command of his
software accordingly.
Read and modify baud rate
(1) Read baud rate
The default factory baud rate of the device is 9600. If you need to change it,
you can change it according to the following table and the corresponding
communication protocol. For example, to read the baud rate ID of the current
device, the command is: 01 03 00 67 00 01 35 D5 , the format is parsed as
follows.
Device Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
01 | 03 | 00 67 | 00 01 | 35 D5 |
Read the baud rate code of the current device. Baud rate code: 1 is 2400; 2 is
4800; 3 is 9600; 4 is 19200; 5 is 38400; 6 is 115200.
For the correct query command, the device will respond, for example, the
response data is: 01 03 02 00 03 F8 45, and its format analysis is shown in
the following table:
Device Address | Function Code | Data Length | Baud Rate Code | Check Code |
---|---|---|---|---|
01 | 03 | 02 | 00 03 | F8 45 |
According to the baud rate code, 03 is 9600, that is, the baud rate of the current device is 9600.
(2) Change the baud rate
For example, change the baud rate from 9600 to 38400, that is, change the code
from 3 to 5, the command is: 01 06 00 67 00 05 F8 16 .
Device Address | Function Code | Register Address | Target Baud Rate | Check Code |
---|---|---|---|---|
01 | 06 | 00 67 | 00 05 | F8 16 |
Change the baud rate from 9600 to 38400, that is, change the code from 3 to 5. The new baud rate will take effect immediately, and the device will lose response at this time, and the baud rate of the device needs to be checked accordingly Modified.
Read and modify correction value
(1) Read correction value
When there is an error between the data and the reference standard, we can
reduce the display error by adjusting the correction value. The correction
difference can be modified in a rang e of plus or minus 1000, that is, the
value range is 0-1000 or 64535 -65535. For example, when the displayed value
is too small by 100, we can correct it by adding 100. The command is: 01 03 00
6B 00 01 F5 D6 . In the command, 100 is hexadecimal 0x64 ;If you need to
reduce it, you can set a negative value, such as -100, the corresponding
hexadecimal value is FF 9C, the calculation method is 100 65535=65435, and
then converted to hexadecimal, it is 0x FF 9C. Device The correction value
starts from 00 6B. We take the first parameter as an example to illustrate.
When there are multiple parameters, the correction value is read and modified
in the same way.
Device Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
01 | 03 | 00 6B | 00 01 | F5 D6 |
For the correct query command, the device will respond, for example, the response data is: 01 03 02 00 64 B9 AF, and its format parsing is shown in the following table:
Device Address | Function Code | Data Length | Correction Value | Check Code |
---|---|---|---|---|
01 | 03 | 02 | 00 64 | B9 AF |
In the response data, the first byte 01 represents the real address of the current device, and 00 6B is the first state correction value register. If the device has multiple parameters, other parameters operate in the same way as this The same, generally temperature and humidity have this parameter, and lighting generally does not have this parameter.
(2) Change the correction value
For example, if the current state is too small, we want to add 1 to its real
value, and add 100 to the current value. The correction operation command is:
01 06 00 6B 00 64 F9 FD .
Device Address | Function Code | Register Address | Target Address | Check Code |
---|---|---|---|---|
01 | 06 | 00 6B | 00 64 | F9 FD |
After the operation is successful, the device will return the information: 01 06 00 6B 00 64 F9 FD , after the successful change, the parameters will take effect immediately.
Disclaimer
This document provides all information about the product, does not grant any license to intellectual property, does not express or imply, and prohibits any other means of granting any intellectual property rights, such as the statement of sales terms and conditions of this product, other issues. No liability is assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use of this product, including the suitability for the specific use of the product, the marketability or the infringement liability for any patent, copyright or other intellectual property rights, etc. Product specifications and product descriptions may be modified at any time without notice.
Contact Us
Company: Shanghai Sonbest Industrial Co., Ltd KLHA Brand Division
Address:Building 8,No.215 North east road,Baoshan District,Shanghai,China
Web: http://www.klha.com
Web: http://www.klha.com
SKYPE: soobuu
Email: sale@sonbest.com
Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>