KLHA KM75B96 integrated temperature humidity light sensor User Manual

June 5, 2024
KLHA

KLHA KM75B96 integrated temperature humidity light sensor

KLHA KM75B96 integrated temperature humidity light sensor-
PROD

INTRODUCTION

KM75B96 using the standard RS485 bus MODBUS-RTU protocol, easy access to PLC, DCS and other instruments or systems for monitoring carbon dioxide, temperature, humidity, and illuminance state quantities.The internal use of high-precision sensing core and related devices to ensure high reliability and excellent long-term stability, can be customized RS232, RS485, CAN,4-20mA, DC0~5V\10V, ZIGBEE, Lora, WIFI, GPRS and other output methods.

Technical Parameters

Technical parameter Parameter value
CO2 range 0~5000ppm
--- ---
CO2 accuracy ±100ppm
Temperature measuring range -30℃~80℃
Temperature measuring accuracy ±0.5℃ @25℃
Humidity measuring range 0~100%RH
Humidity accuracy ±3%RH @25℃
Illuminance measuring range 0~65535Lux
Illuminance allow deviation ±7%
Repeatability test ±5%
Illuminance detection chip Import digital
Wavelength range 380nm~730nm
Communication Interface RS485
Default baud rate 9600 8 n 1
Power DC6~24V 1A
Running temperature -40~80°C
Working humidity 5%RH~90%RH

Product Size

KLHA KM75B96 integrated temperature humidity light sensor-
FIG1

wiring?KLHA KM75B96 integrated temperature humidity light sensor-
FIG2 KLHA KM75B96 integrated
temperature humidity light sensor-FIG3

Application solutionKLHA KM75B96 integrated temperature humidity light
sensor-FIG4

How to use?

KLHA KM75B96 integrated temperature humidity light sensor-
FIG5

Communication Protocol

The product uses RS485 MODBUS RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is 9600, 8, n, 1
Read Data (Function id 0x03)

Device ID Function id Start Address Data Length CRC16
01 03 00 00 00 03 05 CB

For the correct query frame, the devi ce will respond with data:01 03 06 00 7B 00 00 00 00 C5 7F , the response format is parsed as follows:

Device ID Function id Data Length 数据 1 数据 2 数据 3 Check Code
01 03 06 00 79 00 7A 00 7B C5 7F

Data Address Table

Address Start Address Description Data type Value range
40001 00 00 1#粉尘

PM2.5register

| Read only| 0~65535
40002| 00 01| 2#粉尘

PM2.5register

| Read only| 0~65535
40003| 00 02| 3#粉尘

PM2.5register

| Read only| 0~65535
40101| 00 64| model code| read/write| 0~65535
40102| 00 65| total points| read/write| 1~20
40103| 00 66| Device ID| read/write| 1~249
40104| 00 67| baud rate| read/write| 0~6
---|---|---|---|---
40105| 00 68| mode| read/write| 1~4
40106| 00 69| protocol| read/write| 1~10

Read and modify device address

Device ID Function id Start Address Data Length CRC16
FA 03 00 64 00 02 90 5F

Read or query device address
If you don’t know the c urrent device address and there is only one device on the bus, you can use the command FA 03 00 64 00 02 90 5F Query device address.

FA is 250 for the general address. When you don’t know the address, you can use 250 to get the real device address, 00 64 is the device model register. For the correct query command, the device will respond, for example the response data is: 01 03 02 07 12 3A 79, the format of which is as shown in the following table:

Device ID Function id Start Address Model Code CRC16
01 03 02 55 3C 00 01 3A 79

Change device address
For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66 00 02 E8 14 .

Device ID Function id Start Address Destination CRC16
01 06 00 66 00 02 E8 14

Read and Modify Baud Rate

Read baud rate
The device default factory baud rate is 9600. If you need to change it, you can change it according to the following table and the corresponding communication protocol . For example, read the current device’s baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows. Read the baud rate encoding of the current devic e. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600; 4 is 19200; 5 is 38400; 6 is 115200.
For the correct query command, the device will respond, for example the response data is: 01 03 02 00 03 F8 45, the format of which is as shown in the followin g table:

Device ID Function id Start Address Data Length CRC16
01 03 00 67 00 01 35 D5

Change the baud rate
For example, changing the baud rate from 9600 to 38400 , ie changing the code from 3 to 5, the command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 .

Device ID Function id Data Length Rate ID CRC16
01 03 02 00 03 F8 45

Read Correction Value

Read Correction Value
When there is an error between the data and the reference standard, we can reduce the display error by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, t hat is, the value range is 0 1000 or 64535 65535. For example, when the display value is too small, we can correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If you need to reduce, you can set a negative val ue, such as 100, corresponding to the hexadecimal value of FF 9C, which is calculated as 100 65535=65435, and then converted to hexadecimal to 0x FF 9C. The correction value starts from 00 6B. We take the first parameter as an example. The correction valu e is read and modified in the same way for multiple parameters.

Device ID Function id Start Address Data Length CRC16
01 03 00 6B 00 01 F5 D6

For the correct query command, the device will respond, for example the response data is: 01 03 02 00 64 B9 AF, the format of which is as shown in the following table:

Device ID Function id Data Length Data value CRC16
01 03 02 00 64 B9 AF

Change correction value
Fo r example, the current state quantity is too small, we want to add 1 to its true value, and the current value plus 100 correction operation command is:01 06 00 6B 00 64 F9 FD .

Device ID Function id Start Address Destination CRC16
01 06 00 6B 00 64 F9 FD

Disclaimer

This document provides all information about the product, does not grant any license to intellectual property, does not express or imply, and prohibits any other means of granting any intellectual property rights, such as the statement of sales terms and conditions of this product, other issues. No liability is assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and useof this product, including the suitability for the specific use of the product, the marketability or the infringement liability for any patent, copyright or other intel lectual property rights, etc. Product specifications and product descriptions may be modified at any time without notice.

Contact Us

  • Company: Shanghai Sonbest Industrial Co., Ltd KLHA Brand Division Address: Building 8,No.215 North east road, Baoshan District, Shanghai,China
  • Web: http://www.klha.com
  • Web: http://www.klha.com
  • SKYPE: soobuu
  • Email: sale@sonbest.com
  • Tel: 86 021 51083595 / 66862055 / 66862075 / 66861077

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

KLHA User Manuals

Related Manuals