Hawkeye H932 Current Transducers with Relay User Guide
- May 15, 2024
- hawkeye
Table of Contents
Current Monitoring | Current Transducers with Relay:
0 to 5 Vdc Analog Output
H932
Load Trending and Control Relay in One Package
H932 Current Transducers with Relay
The Hawkeye 932 provides accurate load trending information with a
proportional 0 to 5 Vdc output signal. This feature combined with an
integrated command relay makes this product ideal for start/stop and status
monitoring of motors.
The relay is fully isolated from the current sensor, and all relay connections
are externally available for maximum flexibility.
Self-powered
Self-powered analog current transducer with integral start/stop command relay
Saves time
Reduces the number of installed components…saves time and space
Retrofit
Self-gripping, split-core design for fast retrofit installation…no need to
remove conductor
Reduces installation
One device to install for start/stop and status
No external power
No external power required for current sensor
Increased flexibility
Selectable factory calibrated ranges up to 120 A for increased flexibility and
resolution
APPLICATIONS
- Load trending
- Motor control
- Fan/pump status
EXAMPLE LINEAR OUTPUT
Scale software as shown*Factory calibrated ranges selected with the
amperage range switch
SPECIFICATIONS
Sensor Power | Induced from monitored conductor |
---|---|
Insulation Class | 600 Vac RMS |
Frequency Range | 50/60 Hz |
Temperature Range | -15 to 60 °C (5 to 140 °F) |
Humidity Range | 10 to 90% RH non-condensing |
Accuracy | ±2% F.S. from 10% to 100% (selected range) |
Response Time | 2 sec. |
Terminal Block Torque | 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m2) |
Terminal Block Wire Size | 24 to 14 AWG (0.2 to 2.1 mm2) |
WARRANTY | |
Limited Warranty | 5 years |
AGENCY APPROVALS | |
Agency Approvals | UL 508 open device listing, CAT III, Pollution Degree 2, |
basic insulation
Note: Do not use LED status indicators as evidence of applied voltage
H932
Dimensional Drawing * Terminal block may extend up to 1/8” over the
height dimensions shown.
Slide switch may extend up to 1/4” over the height dimensions shown.
RELAY CONTACT RATINGS (N.O.)**
Resistive | 5 A @ 250 Vac, 30 Vdc |
---|
5 A @ 30 Vac, 30 Vdc
Inductive| 2 A @ 250 Vac, 30 Vdc
2 A @ 30 Vac, 30 Vdc
TYPICAL COIL PERFORMANCE
Voltage | AC | DC |
---|---|---|
24 (H932) | 15 | 15 |
12 ( H952) | 20 | |
Pull In Voltage (H952 only) | ||
12 Vdc | 8.4 Vdc | |
Drop Out Voltage (H952 only) | ||
12 Vdc | 3.0 Vdc |
ORDERING INFORMATION
MODEL | AMPERAGE RANGE | SENSOR OUTPUT | RELAY TYPE | RELAY COIL | Split-core | UL |
---|---|---|---|---|---|---|
H932 | 0 to 30/60/120 A | 0 to 5 Vdc | SPST, N.O. | 24 Vac/dc | HOUSING | • |
TRENDING & CONTROLLING MOTOR LOADS WITH THE HAWKEYE 932
Wiring Diagram
HQ0001767.H 0324
800.354.8556
+1 503.598.4564
sales@veris.com
intl@veris.com
veris.com