Hawkeye H932 Current Transducers with Relay User Guide

May 15, 2024
hawkeye

Hawkeye H932 Current Transducers with Relay Current Monitoring | Current Transducers with Relay:
0 to 5 Vdc Analog Output
H932
Load Trending and Control Relay in One Package

H932 Current Transducers with Relay

The Hawkeye 932 provides accurate load trending information with a proportional 0 to 5 Vdc output signal. This feature combined with an integrated command relay makes this product ideal for start/stop and status monitoring of motors.
The relay is fully isolated from the current sensor, and all relay connections are externally available for maximum flexibility.

Self-powered
Self-powered analog current transducer with integral start/stop command relay
Saves time
Reduces the number of installed components…saves time and space
Retrofit
Self-gripping, split-core design for fast retrofit installation…no need to remove conductor
Reduces installation
One device to install for start/stop and status
No external power
No external power required for current sensor
Increased flexibility
Selectable factory calibrated ranges up to 120 A for increased flexibility and resolution

APPLICATIONS

  • Load trending
  • Motor control
  • Fan/pump status

EXAMPLE LINEAR OUTPUT
Scale software as shownHawkeye H932 Current Transducers with Relay - Fig
1*Factory calibrated ranges selected with the amperage range switch

SPECIFICATIONS

Sensor Power Induced from monitored conductor
Insulation Class 600 Vac RMS
Frequency Range 50/60 Hz
Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10 to 90% RH non-condensing
Accuracy ±2% F.S. from 10% to 100% (selected range)
Response Time 2 sec.
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m2)
Terminal Block Wire Size 24 to 14 AWG (0.2 to 2.1 mm2)
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals UL 508 open device listing, CAT III, Pollution  Degree 2,

basic insulation

Note: Do not use LED status indicators as evidence of applied voltage

H932
Dimensional Drawing * Terminal block may extend up to 1/8” over the height dimensions shown.
Slide switch may extend up to 1/4” over the height dimensions shown.
RELAY CONTACT RATINGS (N.O.)**

Resistive 5 A @ 250 Vac, 30 Vdc

5 A @ 30 Vac, 30 Vdc
Inductive| 2 A @ 250 Vac, 30 Vdc
2 A @ 30 Vac, 30 Vdc

TYPICAL COIL PERFORMANCE

Voltage AC DC
24 (H932) 15 15
12 ( H952) 20
Pull In Voltage (H952 only)
12 Vdc 8.4 Vdc
Drop Out Voltage (H952 only)
12 Vdc 3.0 Vdc

ORDERING INFORMATION

MODEL AMPERAGE  RANGE SENSOR OUTPUT RELAY TYPE RELAY COIL Split-core UL
H932 0 to 30/60/120 A 0 to 5 Vdc SPST, N.O. 24 Vac/dc HOUSING

TRENDING & CONTROLLING MOTOR LOADS WITH THE HAWKEYE 932
Wiring DiagramHawkeye H932 Current Transducers with Relay - Fig
3

HQ0001767.H 0324
800.354.8556
+1 503.598.4564
[email protected]
[email protected]
veris.com

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

hawkeye User Manuals

Related Manuals