APC SURTD3000XLI Uninterruptible Power Supply Installation Guide
- June 5, 2024
- APC
Table of Contents
- APC SURTD3000XLI Uninterruptible Power Supply Installation
- INTRODUCTION
- Specifications
- **CONNECTING THE BATTERY MODULES AND ATTACHING THE FRONT BEZEL
- OPERATION
- MAINTENANCE AND TRANSPORT
- TROUBLESHOOTING, SERVICE, AND WARRANTY INFORMATION
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
APC SURTD3000XLI Uninterruptible Power Supply Installation
INTRODUCTION
The APCTM by Schneider Electric Smart-UPSTM RT is a high-performance, uninterruptible power supply (UPS). The UPS provides protection for electronic equipment from utility power blackouts, brownouts, sags, and surges and small utility fluctuations and large disturbances. The UPS also provides battery backup power for connected equipment until utility power returns to safe levels or the batteries are fully discharged. This user manual is available on the enclosed Documentation CD and on the APC by Schneider Electric website, www.apc.com.
INSTALLATION
Read the Safety Guide before installing the UPS.
Unpacking
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly. Check the package contents:
- UPS (with battery modules disconnected)
- Front bezel
- Literature kit containing:
- Product documentation
- Smart-UPS RT User Manuals CD
- Warranty Information
- XLT/XLI/XLTW models:PowerChuteTM software CD
- Serial cable
- 3000 VA XLI models: two output power cords, two input power cords
- 3000 VA models: conversion faceplate for accommodating a Network Management Card
- 5000 VA XLI models: four output power cords, Network Management Card documentation
Specifications
T EMPERATURE OPERATING STORAGE|
32° to 104° F (0° to 40° C)
5° to 113° F (-15° to 45° C) charge the UPS battery every six months
| This unit is intended for indoor use only. Select a location sturdy enough to handle the weight.
Do not operate the UPS where there is excessive dust or the temperature and humidity are outside the specified limits.
---|---|---
M AXIMUM E LEVATION|
OPERATING STORAGE| 10,000 ft (3,000 m)
50,000 ft (15,240 m)
| Ensure that the air vents on the front and rear of the UPS are not
blocked.
H UMIDITY| 0 to 95% relative humidity
W EIGHT| UPS 120 lbs (55 kg)
UPS with packaging 140 lbs (64 kg)
|
Wiring and Connecting the UPS
- 5000 VA XLI MODELS ONLY: HARDWIRING INSTRUCTIONS
- Wiring must be performed by a qualified electrician.
- Install a high magnetic 30/32 A utility circuit breaker.
- Adhere to all national and local electrical codes.
- Use #10 AWG gauge (5 mm2) wire.
- Switch the utility circuit breaker OFF.
- Remove the input access panel.
- Remove circular knockout .
- Run #10 AWG gauge (5 mm2) wire through the access panel, and connect the wires to the terminal block (Green: Ground, Brown: Hot, Blue: Neutral). Use an appropriate strain relief (not included).
- Switch the utility circuit breaker ON.
- Check line voltages.
- Replace the access panel.
**CONNECTING THE BATTERY MODULES AND ATTACHING THE FRONT BEZEL
**
BASIC CONNECTORS
CONNECTING EQUIPMENT AND POWER TO THE UPS
- Connect equipment to the UPS (cables not included for XLJ/XLT/XLTW models).
- Avoid using extension cords.
- 3000 VA XLJ/XLT/XLI/XLTW and 5000 VA XLJ/XLT/XLTW models: Using a power cord, plug the UPS into a two-pole, three-wire, grounded receptacle only.
- 5000 VA XLJ models: To draw full 5000 VA from the UPS have a qualified electrician cut off the input plug and hardwire the UPS to the appropriate power panel.
- Turn on all connected equipment. To use the UPS as a master ON/OFF switch, ensure all connected equipment is switched ON. The equipment will not be powered until the UPS is turned on.
- To power up the UPS press the button on the front panel.
- The UPS battery charges when it is connected to utility power. The battery charges to 90% capacity during the first three hours of normal operation. Do not expect full battery run capability during this initial charge period.
- For additional computer system security, install PowerChute Server Smart-UPS monitoring software.
OPTIONS
Refer to the APC by Schneider Electric web site, www.apc.com for available
accessories.
- External Battery Pack SURT192XLBP
- Rail Kit SURTRK2
- Isolation Transformer
- Service Bypass Panel
OPERATION
Indicator | Description |
---|
Online
| The Online LED illuminates when the UPS is drawing utility power and
performing double conversion to supply power to connected equipment.
On Battery
| The UPS is supplying battery power to the connected equipment.
Bypass
| The Bypass LED illuminates indicating that the UPS is in bypass mode.
Utility power is sent directly to connected equipment during bypass mode
operation. Bypass mode operation is the result of an internal UPS fault, an
overload condition or a user initiated command either through an accessory or
the manual bypass switch. Battery operation is not available while the UPS is
in bypass mode. Refer to Troubleshooting in this manual.
Fault
| The UPS detects an internal fault.
Refer to Troubleshooting in this manual.
Overload
| An overload condition exists. See Troubleshooting.
Replace Battery| The battery is disconnected or must be replaced. See
Troubleshooting.
Feature| Function
---|---
Power On
| Press this button to turn on the UPS. (See below for additional
capabilities.)
Power Off
| Press this button to turn off the UPS.
Feature| Function
---|---
Cold Start
| When there is no utility power and the UPS is off, press and hold the button to power up the UPS and connected equipment.
The UPS will emit two beeps. During the second beep, release the button.
Self-Test| Automatic: The UPS performs a self-test automatically when turned on, and every two weeks thereafter (by default). During the self-test, the UPS briefly operates the connected equipment on battery.
Manual: Press and hold the button for a few seconds to initiate the self-test.
USER-CONFIGURABLE ITEMS
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL SMART SLOT
ACCESSORY CARDS, OR TERMINAL MODE.
FUNCTION| FACTORY DEFAULT| USER SELECTABLE CHOICES| DESCRIPTION
Automatic Self-Test| On start-up and every 14 days, thereafter| On start-up
and every 7 days thereafter
On start-up and every 14 days thereafter
On start-up only No self-test
| Set the interval at which the UPS will execute a self-test.
Date of Last Battery Replacement| Manufacture date| Date of
battery replacement
| Reset this date when you replace the battery modules.
Minimum Run time Before Return from Shutdown| 0 seconds| 0 to 3600 s of run
time| Specify the minimum run time following a low battery shutdown, before
powering connected equipment.
Audible Alarm Setting| ON| ON, OFF| Enable or disable all alarms permanently.
Simple Shutdown Delay| 90 seconds| 0 to 1800 s| Set the interval between the
time when the UPS receives a simple shutdown command and the actual shutdown.
Simple Low Run Time Warning| 150 seconds| 0 to 1800 s| Change the warning
interval default to a higher setting if the operating system requires a longer
interval for shutdown.
The low battery warning beeps are continuous when 150 seconds of run time remain.
High Bypass Point| ****
255 VAC
| Output Voltage Setting 200 VAC:
210 – 280 VAC
208 VAC:
220 – 280 VAC
220 VAC:
235 – 280 VAC
230 VAC:
245 – 280 VAC
240 VAC:
255 – 280 VAC
| Maximum voltage that the UPS will pass to connected equipment during
internal bypass operation.
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL SMART
SLOT
ACCESSORY CARDS, OR TERMINAL MODE.
FUNCTION| FACTORY DEFAULT| USER SELECTABLE CHOICES| DESCRIPTION
Low Bypass Point| ****
160 VAC
| Output Voltage Setting 200 VAC:
160 – 185 VAC
208 VAC:
160 – 190 VAC
220 VAC:
160 – 195 VAC
230 VAC :
160 – 200 VAC
240 VAC:
160 – 205 VAC
| Minimum voltage that the UPS will pass to connected equipment during
internal bypass operation.
Output Voltage| XLJ models:
200 VAC
XLT models:
208 VAC
XLTW models:
220 VAC
XLI models : 230 VAC
| 200, 208, 220,
230, 240 VAC
| Allows the user to select the on on-line output voltage.
Output Frequency| Automatic 50 ± 3 Hz or
60 ± 3 Hz
| 50 ± 3 Hz 60 ± 3 Hz
50 ± 1 Hz 60 ± 1 Hz
50 ± 0.1 Hz 60 ± 0.1 Hz
50 ± 3 Hz or 60 ± 3 Hz
| Sets the allowable UPS output frequency. Whenever possible, the output
frequency tracks the input frequency.
Number of External Battery Packs| 0| 0 to 100| Defines the number of external
connected battery packs for proper run time prediction.
Bypass Acceptable| Not required| Required/ Not required| Phase and frequency
lock required/not required before the UPS will switch to bypass.
CONNECTING THE EPO (EMERGENCY POWER OFF) OPTION
The output power can be disabled in an emergency by closing a switch connected to the EPO. Adhere to National and local electrical codes when wiring the EPO.The EPO switch is internally powered by the UPS for use with non-powered switch circuit breakers. The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and a SELV circuit (IEC standard). Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV. If circuit standard cannot be confirmed, use a contact closure switch. Use one of the following cable types to connect the UPS to the EPO switch:
- CL2: Class 2 cable for general use
- CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
- CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.
- CLEX: Limited use cable for use in dwellings and for use in raceways.
- For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable).
TERMINAL MODE TO CONFIGURE UPS PARAMETERS
3000 VA models:
Terminal Mode is a menu driven interface that enables configuration of the UPS by users not wishing to use PowerChute software or an optional Network Management Card. Connect the serial cable to the serial com connector on the back of the UPS. If PowerChute software is not installed do not perform steps 1 and 7.
- For Windows users: STOP the PowerChute Server using the following steps:
- From the Desktop, go to Start => Settings => Control Panel => Administrative Tools => Services.
- Select APC PowerChute Server – right click the mouse and select Stop. 1a. For Linux users: STOP the PowerChute Server using the following steps:
- Change directory to /etc/init.d.
- Initiate the command ./PowerChute stop.
- Open a terminal program. Example: HyperTerminal
- From the Desktop, go to Start => Programs => Accessories => Communication =>HyperTerminal.
- Double-click on the HyperTerminal icon.
- Follow the prompts to choose a name and select an icon. Disregard the message, “…mustinstall a modem,” if it is displayed. Click OK.
- Select the COM port that is connected to your UPS. The port settings are:
- bits per second – 9600
- data – bits 8
- parity – none
- stop bit – 1
- flow control – none
- Press ENTER
- Press 1 to modify the UPS parameters.
- Follow the prompts.
- Exit the terminal program.
- For Windows users: START the PowerChute Server using the following steps:
- From the Desktop, go to Start => Settings => Control Panel =>
- Administrative Tools => Services.
- Select APC PowerChute Server – right click the mouse and select Start.
- For Linux users: START the PowerChute Server using the following steps:
- Change directory to /etc/init.d.
- Initiate the command ./PowerChute start.
5000 VA models:
Terminal Mode is a menu-driven interface that enables the configuration of the UPS by users not using PowerChute software or the installed Network Management Card interfaces. Connect the serial cable to the serial port on the back of the UPS. If PowerChute software is not installed do not perform steps 1 and 5.
- For Windows users: STOP the PowerChute Server using the following steps:
- From the Desktop, go to Start => Settings => Control Panel => Administrative Tools => Services.
- Select APC PowerChute Server – right click the mouse and select Stop.
- For Linux users: STOP the PowerChute Server using the following steps:
- Change directory to /etc/init.d.
- Initiate the command ./PowerChute stop.
- Open a terminal program. Example: HyperTerminal
- From the Desktop, go to Start => Programs => Accessories => Communication =>HyperTerminal.
- Double-click on the HyperTerminal icon.
- Follow the prompts to choose a name and select an icon. Disregard the message, “…must install a modem,” if it is displayed. Click OK.
- Select the COM port that is connected to your UPS. The port settings are:
- bits per second – 9600
- data – bits 8
- parity – none
- stop bit – 1
- flow control – none
- Press ENTER
- Example for setting the number of external battery packs (SURT192XLBP): Once the blank terminal window is open, follow these steps to enter the number of battery packs:
- Press ENTER to initiate terminal mode. Press ENTER multiple times, until the prompt User Name: is displayed. Follow the prompts. Type slowly, waiting until each character appearson the screen prior to typing the next character.Network Management Card defaults:
- User Name: apc
- Password: apc
- Press 1 and ENTER to select Device Manager.
- Select the model by entering the corresponding number, then press ENTER.
- Press 3 and ENTER to select Configuration.
- Press 1 and ENTER to select Battery.
- Press 2 and ENTER to change the Battery Settings.
- Type in the number of external battery packs (four battery modules per pack), and
- Initiate the command ./PowerChute start.ENTER.
- (Number of packs: 1 = 1 SURT192XLBP, 2 = 2 SURT192XLBP etc.)
- Press 3 and ENTER to accept the changes.
- Press ESC multiple times (5) to return to the main menu.
- Press 4 and ENTER to log out.
- For Windows users: START the PowerChute Server using the following steps:
- From the Desktop, go to Start => Settings => Control Panel => Administrative Tools => Services.
- Select APC by Schneider Electric PowerChute Server – right click the mouse and select Start.
- For Linux users: START the PowerChute Server using the following steps:
- Change directory to /etc/init.d.
- Initiate the command ./PowerChute start.
MAINTENANCE AND TRANSPORT
Replacing the Battery Module
This UPS has an easy-to-replace, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the procedure. See your dealer or go to the APC by Schneider Electric website, www.apc.com for information on replacement battery modules.The battery replacement procedure must include replacing all battery modules in the UPS and connected external battery pack(s).
REMOVING BATTERY MODULES
REPLACING BATTERY MODULES
Disconnecting the Battery for Transport
- Always DISCONNECT THE BATTERY(s) before shipping in compliance with U.S.
- Department of Transportation (DOT) and IATA regulations. The battery(s) may remain in the UPS.
- Shut down and disconnect any equipment attached to the UPS.
- Shut down and disconnect the UPS from the power supply.
- Unplug the battery connectors. Refer to Replacing Battery modules in this manual.
- For shipping, instructions go to the APC by Schneider Electric web site, www.apc.com.
TROUBLESHOOTING, SERVICE, AND WARRANTY INFORMATION
Use the table below to solve minor installation and operation problems. Refer to the APC by Schneider Electric website, www.apc.com for assistance with complex UPS problems.
P ROBLEM AND P OSSIBLE C AUSE | S OLUTION |
---|
UPS WILL NOT TURN ON
Battery not connected properly.
button not pushed. UPS not connected to utility power supply.
Very low or no utility voltage.
| Check that the battery connectors are fully engaged.
Press the button once to power the UPS and the connected equipment. Check that the power cable from the UPS to the utility power supply is securely connected at both ends.
Check the utility power supply to the UPS by plugging in a table lamp. If the light is very dim, have the utility voltage checked.
UPS WILL NOT TURN OFF
button not pushed. Internal UPS fault.| Press the button once to turn the
UPS off.
Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.
UPS BEEPS OCCASIONALLY
Normal UPS operation when running on battery.| None. The UPS is protecting the
connected equipment.
UPS DOES NOT PROVIDE EXPECTED BACKUP TIME
The UPS battery(s) are weak due to a recent outage or battery(s) are near the
end of their service life.| Charge the battery(s). Battery modules require
recharging after extended outages. They wear faster when put into service
often or when operated at elevated temperatures. If the battery(s) are near
the end of their service life, consider replacing the battery(s) even if the
Replace Battery LED is not illuminated.
FRONT PANEL LED S FLASH SEQUENTIALLY
The UPS has been shut down remotely through software or an optional accessory
card.| None. The UPS will restart automatically when utility power returns.
ALL LED S ARE OFF AND THE UPS IS PLUGGED INTO
A WALL OUTLET
The UPS is shut down and the battery is discharged from an extended outage.|
None. The UPS will return to normal operation when the power is restored and
the battery has a sufficient charge.
BYPASS AND OVERLOAD LED S ILLUMINATE , UPS
EMITS A SUSTAINED ALARM TONE
The UPS is overloaded| The connected equipment exceeds the specified “maximum
load” as defined in
Specifications on the APC by Schneider Electric web site, www.apc.com.
The alarm remains on until the overload is removed. Disconnect nonessential equipment from the UPS to eliminate the overload condition.
P ROBLEM AND P OSSIBLE C AUSE | S OLUTION |
---|
BYPASS LED ILLUMINATES
The bypass switch has been turned on manually or through an accessory.| If
bypass is the chosen mode of operation, ignore the illuminated LED.
If bypass is not the chosen mode of operation move the bypass switch on the back of the UPS, to the normal position.
FAULT AND OVERLOAD LED S ILLUMINATE , UPS
EMITS A SUSTAINED ALARM TONE
The UPS has ceased sending power to connected equipment.| The connected
equipment exceeds the specified “maximum load” as defined in
Specifications on the APC by Schneider Electric web site, www.apc.com.
Disconnect nonessential equipment from the UPS to eliminate the overload condition.
Press the OFF button, then the ON button to restore power to connected equipment.
FAULT LED ILLUMINATES
Internal UPS fault.| Do not attempt to use the UPS. Turn the UPS off and have
it serviced immediately.
REPLACE BATTERY LED ILLUMINATES
Replace Battery LED flashes and short beep is emitted every two seconds to
indicate the battery is disconnected.
Weak battery.
Failure of a battery self-test.
| Check that the battery connectors are fully engaged.
Allow the battery to recharge for 24 hours. Then, perform a self-test. If the problem persists after recharging, replace the battery.
The UPS emits short beeps for one minute and the Replace Battery LED illuminates. The UPS repeats the alarm every five hours. Perform the self-test procedure after the battery has charged for 24 hours to confirm the Replace Battery condition. The alarm stops and the LED clears if the battery passes the self-test.
UPS OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE EXISTS
Very high, low, or distorted line voltage. Inexpensive fuel powered generators
can distort the voltage.| Move the UPS to a different outlet on a different
circuit. Test the input voltage with the utility voltage display.
D IAGNOSTIC U TILITY V OLTAGE
All five LEDs are illuminated| The line voltage is extremely high and should
be checked by an electrician.
There is no LED illumination| If the UPS is plugged into a properly
functioning utility power outlet, the line voltage is extremely low.
O NLINE LED
There is no LED illumination| The UPS is running on battery, or it is not
turned on.
The LED is blinking| The UPS is running an internal self-test.
Service
- If the unit requires service, do not return it to the dealer. Follow these steps:
- Review the Troubleshooting section of the manual to eliminate common problems. If the problem persists, contact APC by Schneider Electric Customer Support through the APC by Schneider Electric website, www.apc.com
- Note the model number and serial number and the date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models.
- Call Customer Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
- If the unit is under warranty, the repairs are free.
- Service procedures and returns may vary internationally. Refer to the APC by Schneider Electric website, www.apc.com for country-specific instructions.
- Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty.
- Note: When shipping within the United States, or to the United States always DISCONNECT ONE UPS BATTERY before shipping in compliance with U.S. Department of Transportation (DOT) and IATA regulations. The internal batteries may remain in the UPS.
- Batteries may remain connected in the XBP during shipment. Not allunits utilize XLBPs.
- Write the RMA# provided by Customer Support on the outside of the package.
- Return the unit by the insured, prepaid carrier to the address provided by Customer Support.
Limited Factory Warranty
Schneider Electric IT Corporation (SEIT) warrants its products to be free from
defects in materials and workmanship for a period of two (2) years from the
date of purchase. The SEIT obligation under this warranty is limited to
repairing or replacing, at its own sole option, any such defective products.
Repair or replacement of a defective product or parts thereof does not extend
the original warranty period. This warranty applies only to the original
purchaser who must have properly registered the product within 10 days of
purchase. Products may be registered online at warranty.apc.com.SEIT shall not
be liable under the warranty if its testing and examination disclose that the
alleged defect in the product doesn’t exist or was caused by end-user or any
third person misuse, negligence, improper installation, testing, operation or
use ofthe product contrary to SEIT recommendations or specifications. Further,
SEIT shall not be liable for defects resulting from 1) unauthorized attempts
to repair or modify the product, 2) incorrect or inadequate electrical voltage
or connection, 3) inappropriate on-site operation conditions, 4) Acts of God,
5) exposure to the elements, or 6) theft. In no event shall SEIT have any
liability under this warranty for any product where the serial number has been
altered, defaced, or removed.
EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY
OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR
FURNISHED UNDER THISAGREEMENT OR IN CONNECTION HEREWITH.SEIT DISCLAIMS ALL
IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A
PARTICULAR PURPOSE. SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED,
OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT
RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE
PRODUCTS.THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF
ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE
SEIT SOLE LIABILITY AND PURCHASER EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH
WARRANTIES. SEIT WARRANTIES EXTEND ONLY TO THE ORIGINAL PURCHASER AND ARE NOT
EXTENDED TO ANY THIRD PARTIES.IN NO EVENT SHALL SEIT, ITS OFFICERS,
DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FORANY FORM OF INDIRECT, SPECIAL,
CONSEQUENTIAL, OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR
INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT,
IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEIT HAS
BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEIT
IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT
ORINDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE,
LOSS OF DATA,COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR
OTHERWISE.NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT
LIABILITY FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS
FRAUDULENT MISREPRESENTATION OF TO THE EXTENT THAT IT CAN NOT BE EXCLUDED OR
LIMITED BY APPLICABLE LAW. To obtain service under warranty you must obtain a
Returned Material Authorization (RMA) number from customer support.Customers
with warranty claim issues may access the SEIT worldwide customer support
network through the APC by Schneider Electric web site: www.apc.com. Select
your country from the country selection drop-down menu. Open the Support tab
at the top of the web page to obtain information about customer support in
your region. Products must be returned with transportation charges prepaid and
must be accompanied by a brief description of the problem encountered and
proof ofdate and place of purchase.
APC by Schneider Electric Worldwide Customer Support
Customer support for this or any other APC by Schneider Electric product is available at no charge in any of the following ways:
- Visit the APC by Schneider Electric website, www.apc.com to access documents in the APC Knowledge Base and to submit customer support requests. www.apc.com (Corporate Headquarters)
- Connect to localized APC by Schneider Electric website for specific countries, each of which provides customer support information. www.apc.com/support/
- Global support searching APC Knowledge Base and using e-support.
- Contact the APC by Schneider Electric Customer Support Center by telephone or e-mail.
- Local, country-specific centers: go to www.apc.com/support/contact for contact information.
- For information on how to obtain local customer support, contact the APC by Schneider Electric representative or another distributor from whom you purchased your APC by Schneider Electric product.
References
- APC, a flagship brand of Schneider Electric - APC USA
- APC, a flagship brand of Schneider Electric - APC USA
- APC, a flagship brand of Schneider Electric - APC USA
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>